| Plan Review Stops For Permit 16111042 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-01-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2017-01-09 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2017-01-09 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-06 |
Time |
07:57 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2016-12-06 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2016-12-06 07:56:58 | BUILDING PROVISO/ RED LINED: | | | SHEET A2.1 DOOR 115A PLEASE PROVIDE COMPLIANCE WITH | | | 2014 FBC-ACCESSIBILITY CODE 404.2.4. MANEUVERING | | | CLEARANCES AT DOOR. | | | 404.2.4 MANEUVERING CLEARANCES. MINIMUM MANEUVERING | | | CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH | | | 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL | | | WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE OR | | | HINGE SIDE CLEARANCE. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | | DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-01-03 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2017-01-03 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2017-01-03 |
Time |
13:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-12-01 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-12-01 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2016-12-01 14:08:56 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS | | | SUITABLE FOR A HEALTH CARE FACILITY/ EXAM ROOMS AS | | | DEFINED IN ARTICLE 517 OF THE NATIONAL ELECTRICAL CODE. | | | NEC 517.1, 517.11, 517.13 | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY | | | CONSERVATION REQUIREMENTS. FBC C405 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-373-3701 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-01-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-01-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-01-05 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-11-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-11-28 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2016-11-28 12:40:55 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | | | | 1) INFORMATIONAL : | | | | | | SHEET LS 2.1 - THERE IS AN INCORRECT REFERENCE, "2015", | | | TO NFPA 101. THE CORRECT REFERENCE IS 2012, WHICH WAS | | | EFFECTIVE DECEMBER 31, 2014. | | | | | | THOUGH IT DOES NOT APPEAR TO HAVE A NEGATIVE IMPACT TO | | | YOUR SUBMITTAL, PLEASE ENSURE COMPLIANCE AND MAKE THE | | | APPLICABLE CORRECTIONS TO YOUR RECORDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-01-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-01-09 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-28 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-06 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-11-23 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2016-12-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-12-06 |
Time |
07:57 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2016-12-06 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-01-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-01-09 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-01-09 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-05 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-02 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2016-12-05 07:09:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16111042 | | | 12/5/16 | | | | | | 1) THE HP BTUH CAPACITIES AND EFFICIENCY RATINGS SHOWN | | | ON THE EQUIPMENT SCHEDULE DON'T MATCH THE CAPACITIES | | | SHOWN IN THE ENERGY CALCULATIONS. | | | | | | 2) INDICATE THE REQUIRED CLEARANCE DISTANCES FOR THE | | | O/A INTAKES- SECTION 401.4. | | | | | | 3) INDICATE HOW THE O/A INTAKE OPENINGS WILL BE | | | PROTECTED- SECTION 401.5. | | | | | | 4) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE SHUTOFF DAMPER CONTROLS FOR | | | THE O/A INTAKES. PLEASE NOTE IF MOTORIZED DAMPERS ARE | | | TO BE INSTALLED, THEY SHALL BE IN COMPLIANCE WITH | | | SECTION C402.4.5.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|