Plan Review Details - Permit 16111042
Plan Review Stops For Permit 16111042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By jwitmer Date 2017-01-09 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-01-09 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 07:57 Rev Time  
Received By jwitmer Date 2016-12-06 Time 07:32 Sent To  
Notes
2016-12-06 07:56:58BUILDING PROVISO/ RED LINED:
 SHEET A2.1 DOOR 115A PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-ACCESSIBILITY CODE 404.2.4. MANEUVERING
 CLEARANCES AT DOOR.
 404.2.4 MANEUVERING CLEARANCES. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE OR
 HINGE SIDE CLEARANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By rlecky Date 2017-01-03 Time 13:47 Rev Time 0.00
Received By rlecky Date 2017-01-03 Time 13:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By rlecky Date 2016-12-01 Time 14:07 Rev Time 0.00
Received By rlecky Date 2016-12-01 Time 12:43 Sent To  
Notes
2016-12-01 14:08:56PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS
 SUITABLE FOR A HEALTH CARE FACILITY/ EXAM ROOMS AS
 DEFINED IN ARTICLE 517 OF THE NATIONAL ELECTRICAL CODE.
 NEC 517.1, 517.11, 517.13
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By pleduc Date 2017-01-05 Time   Rev Time 0.00
Received By pleduc Date 2017-01-05 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-28 Cont ID  
Sent By pleduc Date 2016-11-28 Time   Rev Time 0.00
Received By pleduc Date 2016-11-28 Time 12:33 Sent To  
Notes
2016-11-28 12:40:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
  
 1) INFORMATIONAL :
  
 SHEET LS 2.1 - THERE IS AN INCORRECT REFERENCE, "2015",
 TO NFPA 101. THE CORRECT REFERENCE IS 2012, WHICH WAS
 EFFECTIVE DECEMBER 31, 2014.
  
 THOUGH IT DOES NOT APPEAR TO HAVE A NEGATIVE IMPACT TO
 YOUR SUBMITTAL, PLEASE ENSURE COMPLIANCE AND MAKE THE
 APPLICABLE CORRECTIONS TO YOUR RECORDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-09 Cont ID  
Sent By ccole Date 2017-01-09 Time 10:48 Rev Time 0.00
Received By ccole Date 2016-12-28 Time 10:39 Sent To  
Notes
2016-12-29 10:40:04B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-11-23 Time 11:26 Sent To  
Notes
2016-11-23 11:26:09B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 07:57 Rev Time  
Received By jwitmer Date 2016-12-06 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By ccole Date 2017-01-09 Time 10:48 Rev Time 0.00
Received By ccole Date 2017-01-09 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 07:05 Rev Time 0.00
Received By ccole Date 2016-12-02 Time 17:34 Sent To  
Notes
2016-12-05 07:09:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16111042
 12/5/16
  
 1) THE HP BTUH CAPACITIES AND EFFICIENCY RATINGS SHOWN
 ON THE EQUIPMENT SCHEDULE DON'T MATCH THE CAPACITIES
 SHOWN IN THE ENERGY CALCULATIONS.
  
 2) INDICATE THE REQUIRED CLEARANCE DISTANCES FOR THE
 O/A INTAKES- SECTION 401.4.
  
 3) INDICATE HOW THE O/A INTAKE OPENINGS WILL BE
 PROTECTED- SECTION 401.5.
  
 4) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE SHUTOFF DAMPER CONTROLS FOR
 THE O/A INTAKES. PLEASE NOTE IF MOTORIZED DAMPERS ARE
 TO BE INSTALLED, THEY SHALL BE IN COMPLIANCE WITH
 SECTION C402.4.5.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  