Plan Review Details - Permit 16110986
Plan Review Stops For Permit 16110986
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 10:22 Rev Time 0.00
Received By ccole Date 2017-03-15 Time 13:55 Sent To  
Notes
2017-03-16 13:55:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 08:49 Rev Time 0.00
Received By ccole Date 2017-01-17 Time 15:51 Sent To  
Notes
2017-01-17 15:52:04CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 16:48 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 14:28 Sent To  
Notes
2016-11-22 14:28:11ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 10:22 Rev Time 0.00
Received By ccole Date 2017-03-17 Time 10:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 08:38 Rev Time 0.00
Received By ccole Date 2017-01-24 Time 08:38 Sent To  
Notes
2017-01-24 08:49:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110857
 1/24/17
  
 1) TWO SETS OF PLANS ARE REQUIRED FOR REVIEW- ONLY ONE
 REVISED SET WAS SUBMITTED- SECTION 107.1 WPB AMENDMENTS
 TO THE FBC.
  
 2) SECOND REQUEST FOR PLAN SHEET A1.1 TO BE SIGNED AND
 SEALED BY THE ARCHITECT.
  
 3) SECOND REQUEST FOR ENGINEER'S SEAL AND SIGNATURE ON
 THE ROOF STAND INSTALLATION SUBMITTAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 16:48 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 16:48 Sent To  
Notes
2016-11-22 17:02:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110986
 11/21/16
  
 1) THE SUBMITTED ARCHITECTURAL PLAN MUST BEAR THE
 SIGNATURE AND SEAL OF THE ARCHITECT PER SECTION
 61G1-16.003 FLORIDA ADMINISTRATIVE CODE. WHY IS THIS
 PLAN BEING SUBMITTED WHEN NEITHER THE WALK-IN COOLER OR
 ICE MAKER ARE NUMBERED AND INCLUDED IN THE EQUIPMENT
 SCHEDULE? PLEASE NOTE THAT THE LOCATION OF THE WALK IN
 COOLER DOOR AS SHOWN IN THE SUBMITTAL DOESN'T MATCH THE
  
 LOCATION ON THE PLAN.
  
 2) THE ALUMINUM ROOF STAND SUBMITTAL HAS A COPIED
 ENGINEER'S SEAL. REFER TO SECTION 61-G15-23.002 AND
 PROVIDE A CLEAR, LEGIBLE SUBMITTAL WITH AN ORIGINAL
 SIGNATURE AND SEAL BY THE ENGINEER OF RECORD.
  
 3) PROVIDE A DRAWING INDICATING THE LOCATION OF THE
 CONDENSER ON THE ROOF WITH REQUIRED CLEARANCE DUISTANCE
 JMEASUREMENTS TO THE ROOF EDGES- SEE SECTION 304.11
 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  