Plan Review Details - Permit 16110980
Plan Review Stops For Permit 16110980
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-12-08 Cont ID  
Sent By cthroop Date 2016-12-08 Time 11:51 Rev Time 0.00
Received By cthroop Date 2016-12-08 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 10:19 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By mvaldes Date 2016-12-07 Time 16:04 Rev Time 0.00
Received By mvaldes Date 2016-12-07 Time 16:04 Sent To B
Notes
2016-12-07 16:18:541ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] THE APPLICABLE CODES SHALL APPEAR ON THE DRAWINGS,
 SPECIFY WHICH EDITION OF THE NEC THE SOLAR SYSTEM WAS
 DESIGNED TOO MEET. FBC 107
  
 2] PLEASE SIZE OUTPUT CONDUCTORS AT 125% PER NEC 690.
 (VERIFY WIRE SIZE FROM INVERTER OUTPUT TO
 INTERCONNECTION POINT)
  
 3] CLARIFY AIC RATING OF DISCONNECT SWITCH TO MATCH
 EXISTING FIELD CONDITIONS. NEC 110.9 & 110.10
  
 4] IF THE SOLAR SYSTEM IS BEING TAP OFF THE LINE SIDE
 OF THE SERVICE THE DISCONNECT SHALL BE SE RATED IN
 ADDITION TO BEING LISTED FOR SOLAR APPLICATIONS & THE
 NUETRAL SHALL BE BONDED TO THE CASE. NEC 230 & 250.
  
 5] IF ANY QUESTIONS PLEASE CONTACT ME, KEEP IN MIND NEW
 COMMENTS MAY BE NOTED UPON RESUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-08 Cont ID  
Sent By cthroop Date 2016-12-08 Time 11:51 Rev Time 0.00
Received By cthroop Date 2016-11-22 Time 09:31 Sent To  
Notes
2016-11-23 09:32:09ROUTED TO ELECTRICAL INBOX
 *TRAVELLING WITH 16110982*