Plan Review Details - Permit 16110959
Plan Review Stops For Permit 16110959
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By cthroop Date 2016-12-22 Time 09:55 Rev Time 0.00
Received By cthroop Date 2016-12-22 Time 09:54 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-23 Cont ID  
Sent By cthroop Date 2016-11-23 Time 11:29 Rev Time 0.00
Received By cthroop Date 2016-11-23 Time 11:27 Sent To E
Notes
2016-11-23 11:33:19BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PLANS SUBMITTED APPEAR TO BE FOR PROPOSED WORK.
 PROVIDE FLOOR PLAN OF EXISTING KITCHEN AND MASTER BATH
 WITH ANY PROPOSED CHANGES IN FRAMING MEMEBERS.
 2. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
 3. PLUMBING AND ELECTRICAL REVIEW REQUIRED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By mvaldes Date 2016-12-21 Time 18:10 Rev Time 0.00
Received By mvaldes Date 2016-12-21 Time 17:59 Sent To B
Notes
2016-12-21 18:10:57ROUTED TO CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By mvaldes Date 2016-12-05 Time 13:51 Rev Time 0.00
Received By mvaldes Date 2016-12-05 Time 13:33 Sent To P
Notes
2016-12-05 13:43:211ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE GFCI RECEPTACLE OUTLET LOCATIONS ON THE
 KITCHEN LAYOUT TO VERIFY COUNTER-TOP SPACING
 REQUIREMENTS. FBC-R SECTIONS E3901.2.4 & E3902.6.
  
 2] A MINIMUM OF 2 SMALL APPLIANCE CIRCUITS SHALL SERVE
 THE KITCHEN COUNTER-TOP RECEPTACLE OUTLETS IN
 ACCORDANCE WITH FBC-R SECTION E3901.3. A NOTE WILL
 SUFFICE
  
 3] PROVIDE A GFCI RECEPTACLE OUTLET WITHIN 3' OF THE
 SINK IN BATHROOM LAYOUT PER FBC-R SECTION E3901.6.
  
 4] THE BATHROOM SHALL BE FED WITH A MINIMUM 20 AMPERE
 BRANCH CIRCUIT PER FBC SECTION E3703.4. A NOTE WILL
 SUFFICE.
  
 5] SMOKE ALARMS REQUIRED IN ACCORDANCE WITH FBC-R
 SECTIONS 314 & 315, IF EXISTING ADD A BLOCK NOTE.
  
 6] ALL NEW RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
 PER FBC-R SECTION E4002.14. ADD A BLOCK NOTE.
  
 7] THE SCOPE OF THE WORK, JOB ADDRESS & APPLICABLE CODE
 SHALL APPEAR ON THE DRAWING ALONG WITH THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 CITY AMENDMENTS 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-12-13 Time 15:34 Sent To  
Notes
2016-12-13 15:34:27RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-07 Cont ID  
Sent By gjohnson Date 2016-12-07 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2016-11-21 Time 09:16 Sent To  
Notes
2016-11-23 09:16:41BLDG MISC 1

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By gjohnson Date 2016-12-22 Time 14:30 Rev Time 0.00
Received By gjohnson Date 2016-12-22 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-07 Cont ID  
Sent By gjohnson Date 2016-12-07 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2016-12-07 Time 09:57 Sent To  
Notes
2016-12-07 10:01:191ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SCOPE OF WORK . REPLACE PLUMBING FIXTURES TO
 REMAIN IN EXISTING LOCATION? . WPB AMEND TO FBC 107.2.1
  
 2. COMPLY WITH ELECTRICAL AND BUILDING COMMENTS. WPB
 AMEND TO FBC 107.2.1