Plan Review Details - Permit 16110863
| Plan Review Stops For Permit 16110863 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-12-01 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-12-01 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-13 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-12 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-01 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-18 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-13 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-13 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2016-12-13 14:01:59 | MECHANICAL PROVISOS | | | | | | IN AN EFFORT TO HELP EXPEDITE THE FIELD INSPECTIONS, | | | THE PROPOSED PLANS ARE APPROVED, HOWEVER A REVISION | | | WILL BE REQUIRED TO ORGANIZE THE PLANS, AND CORRECT | | | DEFICIENCIES AND CONFLICTS BETWEEN THE SUBMITTED | | | CAPTIVEAIRE SCHEDULES AND PLANS, AND THE MAIN BALL PARK | | | MECHANICAL PLANS. | | | | | | AN EXAMPLE IS LISTED BELOW: | | | 1) HOOD #1 (TAG-33) | | | THE CAPTIVEAIRE SCHEDULE IS LISTING THE SUPPLY AIR AT | | | 2005 CFMS, HOWEVER THE PLAN IS SPECIFYING MUA-S-3-3 AT | | | 3600 CFMS. | | | | | | PLEASE PROVIDE AT TIME OF INSPECTION: | | | | | | 1) THE CORRECTED PLANS AND SCHEDULES. | | | 2) A HOOD SUMMARY SHEET LISTING THE HOOD NUMBER, HOOD | | | LOCATION, AND THE CORRELATING PLAN SHEETS THAT SHOW THE | | | DUCT LAYOUTS AND DETAILS, THE FAN SCHEDULES, AND THE | | | FAN LOCATIONS. | | | 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE SELKIRK GREASE DUCT. | | | 4) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | | ROOFTOP FANS, CURBS, AND MUA'S. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-01 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-01 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2016-12-01 15:55:21 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110863 | | | 12/1/16 | | | | | | 1) BECAUSE OF THE LACK OF GREASE DUCT AND FAN | | | INFORMATION I AM NOT ABLE TO PERFORM A COMPLETE REVIEW | | | ON THE SYSTEMS AS REQUIRED BY THE FLORIDA MECHANICAL | | | CODE. | | | | | | THE LACK OF THESE DETAILS AND SPECIFICATIONS WILL ALSO | | | RESULT IN FAILED INSPECTIONS IN THE FIELD. | | | | | | THEREFORE, IN ORDER TO APPROVE EACH PERMIT FOR THE | | | HOODS (#16110858- ASTROS, & 16110861- NATIONALS) PLEASE | | | ADD THE THE GREASE DUCT DETAILS AND THE MUA AND EXHAUST | | | FAN INFORMATION AND SCHEDULES FOR EACH HOOD. IF THIS | | | MEANS SUBMITTING THE CORRELATING PLAN SHEETS FROM THE | | | MAIN | | | | | | PLANS THAT WOULD BE ACCEPTABLE, BUT PLEASE HIGHLIGHT | | | THE ALL CORRELATING DETAILS AND EQUIPMENT SCHEDULES. | | | | | | TYPICAL PLAN DETAILS INCLUDE DUCT SPECIFICATIONS- TYPE | | | AND GAUGE OF DUCTS, DUCT SIZES, DUCT RUNS, CLEAN-OUT | | | LOCATIONS, CLEARANCES TO COMBUSTIBLES, CONNECTION AND | | | SUPPORT DETAILS, VELOCITY CALCULATIONS, EXHAUST OUTLET | | | AND AIR INLET LOCATIONS AND CLEARANCES. | | | | | | PLEASE SEE SECTION 506. | | | | | | ADDITIONALLY, IT WOULD BE VERY HELPFUL IF INDIVIDUAL | | | HOODS SHOWN ON THE CAPTIVEAIRE PLAN SHEET NO. 1 WERE | | | IDENTIFIED AS ASTROS OR NATIONALS. THIS SHEET HAS BEEN | | | SUBMITTED FOR BOTH THE ASTROS AND NATIONALS PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL ME. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-13 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-13 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2016-12-13 14:07:58 | 12/13/16 | | | DIGITAL SIGNATURES VERIFIED ON UPDATED PLANS. | | | PLANS LABELED FOR REFERENCE ONLY, AND HOOD SHOP | | | DRAWINGS WERE NOT DIGITALLY SIGNED. | | | CCOLE | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2016-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-01 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-01 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2016-12-01 16:12:34 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110863 | | | 12/1/16 | | | | | | 1) THE ARCHITECT'S APPROVAL STAMP ON THE CAPTIVEAIRE | | | PLAN IS INDICATING APPROVAL FOR ARCHITECTURAL ISSUES | | | ONLY. PLEASE PROVIDE AN APPROVAL STAMP AND SIGNATURE | | | FROM THE MECHANICAL ENGINEER OF RECORD. ALL OTHER | | | ARCHITECTURAL OR ENGINEERED PLANS MUST BEAR THE | | | ELECTRONIC SEALS AND SIGNATURES OF THE DESIGNERS OF | | | RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
|