Plan Review Details - Permit 16110862
Plan Review Stops For Permit 16110862
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-01 Cont ID  
Sent By wjolin Date 2016-12-01 Time 08:17 Rev Time 0.00
Received By wjolin Date 2016-12-01 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 13:13 Rev Time 0.00
Received By ccole Date 2016-12-12 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 15:51 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 13:16 Rev Time 0.00
Received By ccole Date 2016-12-13 Time 13:14 Sent To  
Notes
2016-12-13 13:33:48MECHANICAL PROVISOS
  
 IN AN EFFORT TO HELP EXPEDITE THE FIELD INSPECTIONS,
 THE PROPOSED PLANS ARE APPROVED, HOWEVER A REVISION
 WILL BE REQUIRED TO ORGANIZE THE PLANS, AND CORRECT
 DEFICIENCIES AND CONFLICTS BETWEEN THE SUBMITTED
 CAPTIVEAIRE SCHEDULES AND PLANS, AND THE MAIN BALL PARK
 MECHANICAL PLANS.
  
 AN EXAMPLE IS LISTED BELOW:
 1) HOOD #1 (TAG-33)
 THE CAPTIVEAIRE SCHEDULE IS LISTING THE SUPPLY AIR AT
 2005 CFMS, HOWEVER THE PLAN IS SPECIFYING MUA-S-3-3 AT
 3600 CFMS.
  
 PLEASE PROVIDE AT TIME OF INSPECTION:
  
 1) THE CORRECTED PLANS AND SCHEDULES.
 2) A HOOD SUMMARY SHEET LISTING THE HOOD NUMBER, HOOD
 LOCATION, AND THE CORRELATING PLAN SHEETS THAT SHOW THE
 DUCT LAYOUTS AND DETAILS, THE FAN SCHEDULES, AND THE
 FAN LOCATIONS.
 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE SELKIRK GREASE DUCT.
 4) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP FANS, CURBS, AND MUA'S.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 15:51 Rev Time 0.00
Received By ccole Date 2016-12-01 Time 15:51 Sent To  
Notes
2016-12-01 15:53:581ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110862
 12/1/16
  
 1) BECAUSE OF THE LACK OF GREASE DUCT AND FAN
 INFORMATION I AM NOT ABLE TO PERFORM A COMPLETE REVIEW
 ON THE SYSTEMS AS REQUIRED BY THE FLORIDA MECHANICAL
 CODE.
  
 THE LACK OF THESE DETAILS AND SPECIFICATIONS WILL ALSO
 RESULT IN FAILED INSPECTIONS IN THE FIELD.
  
 THEREFORE, IN ORDER TO APPROVE EACH PERMIT FOR THE
 HOODS (#16110858- ASTROS, & 16110861- NATIONALS) PLEASE
 ADD THE THE GREASE DUCT DETAILS AND THE MUA AND EXHAUST
 FAN INFORMATION AND SCHEDULES FOR EACH HOOD. IF THIS
 MEANS SUBMITTING THE CORRELATING PLAN SHEETS FROM THE
 MAIN
  
 PLANS THAT WOULD BE ACCEPTABLE, BUT PLEASE HIGHLIGHT
 THE ALL CORRELATING DETAILS AND EQUIPMENT SCHEDULES.
  
 TYPICAL PLAN DETAILS INCLUDE DUCT SPECIFICATIONS- TYPE
 AND GAUGE OF DUCTS, DUCT SIZES, DUCT RUNS, CLEAN-OUT
 LOCATIONS, CLEARANCES TO COMBUSTIBLES, CONNECTION AND
 SUPPORT DETAILS, VELOCITY CALCULATIONS, EXHAUST OUTLET
 AND AIR INLET LOCATIONS AND CLEARANCES.
  
 PLEASE SEE SECTION 506.
  
 ADDITIONALLY, IT WOULD BE VERY HELPFUL IF INDIVIDUAL
 HOODS SHOWN ON THE CAPTIVEAIRE PLAN SHEET NO. 1 WERE
 IDENTIFIED AS ASTROS OR NATIONALS. THIS SHEET HAS BEEN
 SUBMITTED FOR BOTH THE ASTROS AND NATIONALS PERMITS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 13:14 Rev Time 0.00
Received By ccole Date 2016-12-13 Time 13:14 Sent To  
Notes
2016-12-13 13:16:4912/13/16
 DIGITAL SIGNATURES VERIFIED ON UPDATED PLANS.
 PLANS LABELED FOR REFERENCE ONLY, AND HOOD SHOP
 DRAWINGS WERE NOT DIGITALLY SIGNED.
 CCOLE
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 16:01 Rev Time 0.00
Received By ccole Date 2016-12-01 Time 16:01 Sent To  
Notes
2016-12-01 16:11:471ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110862
 12/1/16
  
 1) THE ARCHITECT'S APPROVAL STAMP ON THE CAPTIVEAIRE
 PLAN IS INDICATING APPROVAL FOR ARCHITECTURAL ISSUES
 ONLY. PLEASE PROVIDE AN APPROVAL STAMP AND SIGNATURE
 FROM THE MECHANICAL ENGINEER OF RECORD. ALL OTHER
 ARCHITECTURAL OR ENGINEERED PLANS MUST BEAR THE
 ELECTRONIC SEALS AND SIGNATURES OF THE DESIGNERS OF
 RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  