| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] THE LOAD CALCULATIONS PROVIDED USING THE STANDARD |
| | METHOD PER YOUR NUMBERS IS UNDERSIZED, PLEASE ADJUST OR |
| | PROVIDE OPTIONAL METHOD FOR VERIFICATION. |
| | |
| | NEC 220.12, 7200 SQFT X 3VA = 21,600 - 3000VA = 18,600 |
| | X 35% = 6510 + 3000VA = 9510 |
| | NEC 220.53, W/H 3000VA X 3 = 9000 |
| | NEC 220.54, DRYER 5000VA X 3 = 15000 |
| | NEC 220.55, RANGE 8000VA X 3 = 14000 |
| | NEC 220.50 & 51, AC VS HEAT 5000VA X 3 = 15000 |
| | TOTAL DEMAND LOAD, 62510VA / 240V = 260.5 AMPS |
| | |
| | 2] PROVIDE INTERSYSTEM BONDING TERMINAL IN THE |
| | GROUNDING DETAIL. NEC 250.94 |
| | |
| | 3] SHOW PROPER IDENTIFICATION ON EACH DISCONNECT, LABEL |
| | UNIT # EACH SERVE. NEC 225.37 |
| | |
| | 4] CLARIFY WHY THERE IS ANOTHER PERMIT APPLICATION OPEN |
| | FOR THE SAME SCOPE OF WORK ON THIS PROPERTY, ANY |
| | QUESTIONS PLEASE CONTACT ME DIRECTLY. |
| | |
| | REVIEW FBC 2014 5TH ED. NEC 2011 |