Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By cthroop Date 2017-01-05 Time 11:56 Rev Time 0.00
Received By cthroop Date 2017-01-05 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By cthroop Date 2016-12-01 Time 12:44 Rev Time 0.00
Received By cthroop Date 2016-12-01 Time 12:44 Sent To  
Notes
2016-12-01 12:51:58 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE GENERATOR INSTALLATION INSTRUCTIONS. CANNOT
 VERIFY ATTACHMENT TO NEW SLAB. CANNOT VERIFY
 MANAUFACTURER'S BUILDING SETBACK REQUIREMENTS.
 2. PROVIDE STATEMENT OF GOVERNING CODES ON PLAN.
 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
 4. PROVIDE DEPTH OF SLAB DEMENSION ON PLAN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-05 Cont ID  
Sent By mvaldes Date 2017-01-05 Time 11:52 Rev Time 0.00
Received By mvaldes Date 2017-01-05 Time 11:52 Sent To  
Notes
2017-01-05 11:53:14CLIENT ADDRESSED ISSUES AT FRONT DESK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-30 Cont ID  
Sent By mvaldes Date 2016-11-30 Time 10:38 Rev Time 0.00
Received By mvaldes Date 2016-11-30 Time 10:02 Sent To B
Notes
2016-11-30 10:45:451ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] VERIFY GEC SIZE WITH TABLE NEC 250.66 BASED ON THE
 LARGEST SERVICE UNGROUNDED CONDUCTOR.
  
 2] CLARIFY IF ATS EQUIPMENT IS SERVICE RATED ? NEC
 230.66
  
 3] IS THE PROPOSED GENERATOR A SEPERATELY OR
 NON-SEPERATETLY DERIVED SYSTEM, IF CALLED OUT AS
 NON-SEPERATELY PLEASE SHOW AN EQUIPMENT GROUNDING
 CONDUCTOR TO THE GENERATOR ON THE RISER DIAGRAM. NEC
 250.35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-01 Cont ID  
Sent By cthroop Date 2016-12-01 Time 12:44 Rev Time 0.00
Received By cthroop Date 2016-11-15 Time 15:25 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-18 Cont ID  
Sent By cthroop Date 2016-12-01 Time 12:44 Rev Time 0.00
Received By njwira Date 2016-11-16 Time 14:31 Sent To E
Notes
2016-11-18 17:02:3111/18/16- PASSED
  
 NO TREES CAN BE MOVED WITHOUT A TREE ALTERATION PERMIT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  