Plan Review Details - Permit 16110673
Plan Review Stops For Permit 16110673
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-12-02 Cont ID  
Sent By cthroop Date 2016-12-02 Time 10:49 Rev Time 0.00
Received By cthroop Date 2016-12-02 Time 10:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-19 Cont ID  
Sent By mvaldes Date 2016-12-19 Time 11:20 Rev Time 0.00
Received By mvaldes Date 2016-12-19 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-30 Cont ID  
Sent By mvaldes Date 2016-11-30 Time 11:12 Rev Time 0.00
Received By mvaldes Date 2016-11-30 Time 10:52 Sent To G
Notes
2016-11-30 11:17:461ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 1] PLEASE CLARIFY THE SCOPE OF THE WORK? THE PERMIT
 APPLICATION CALLS OUT A SERVICE CHANGE AND THE PLANS
 PROVIDED ARE GENERIC. PROVIDE A SITE SPECIFIC RISER
 DIAGRAM WITH WIRE & CONDUIT SIZES, COMPLETE LOAD
 CALCULATION, & GROUNDING DETAIL. FBC 107, NEC 215.5
  
 2] SHOW OVERCURRENT PROTECTION WITHIN SIGHT OR
 INTERGRATED AT THE GENERATOR PER NEC 445 & 702.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-12-02 Cont ID  
Sent By gjohnson Date 2016-12-02 Time 09:35 Rev Time 0.00
Received By gjohnson Date 2016-12-02 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-19 Cont ID  
Sent By mvaldes Date 2016-12-19 Time 11:20 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 10:52 Sent To  
Notes
2016-12-09 10:53:09RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-02 Cont ID  
Sent By gjohnson Date 2016-12-02 Time 10:38 Rev Time 0.00
Received By cthroop Date 2016-11-15 Time 11:10 Sent To  
Notes
2016-11-16 11:10:42ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By njwira Date 2016-12-12 Time 17:29 Rev Time 0.00
Received By njwira Date 2016-12-09 Time 16:45 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By njwira Date 2016-11-21 Time 10:49 Rev Time 0.00
Received By njwira Date 2016-11-17 Time 10:31 Sent To E
Notes
2016-11-21 10:50:1311/21/16- FAILED
  
 SOUTH FLAGLER IS THE FRONT SETBACK
 GENERATOR IS 9FT. FROM THE REAR SETBACK AND DOESN'T
 MEET THE 11FT. REQUIREMENT 94-74(3)D
 TREE ALTERATION PERMIT REQUIRED TO REMOVE TREES
 94-448(D)1
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  