Plan Review Details - Permit 16110654
Plan Review Stops For Permit 16110654
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By   Date 2016-12-22 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2016-12-22 Time 07:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By jwitmer Date 2016-12-05 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2016-12-05 Time 06:47 Sent To  
Notes
2016-12-05 08:30:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110654
 ADD: 1401NORTHPOINTPARKWAY
 CONT: SIERRA
 TEL: 305-557-2444
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 05/2016
 ACTION: DENIED
  
 1) SHEET A-2.2 INDICATES AN EMPLOYEE LOUNGE OF OVER
 1579 SQ. FT. IN AREA. HE PLANS DO NOT PROVIDE THE
 SQUARE FOOTAGE PER FLOOR TO BE ABLE TO DETERMINE IF
 THIS IS A MIXED USE OCCUPANCY. SECTION 508.2.1 OF THE
 2014 FBC-B DOES REQUIRE IF AN ACCESSORY OCCUPANCY IS
 OVER 10% OF THE FLOOR AREA, THEY SHALL BE INDIVIDUALLY
 CLASSIFIED IN ACCORDANCE WITH 302.1. PLEASE PROVIDE THE
 SQARE FOOTAGE OF THE 1ST FLOOR.
  
 2) BECAUSE OF THE USAGE OF THE EMPLOYEE LOUNGE WE USE
 THE 15 SQ. FT. PER OCCUPANT TO FIGURE THE OCCUPANT
 LOADS. 1579 SQ. FT/ 15= 106 OCCUPANTS. WHEN THE
 OCCUPANT LOADS ARE 50 OR MORE, SECTION 1008.1.2 DOOR
 SWING REQUIRES TO SWING IN THE DIRECTION OF EXIT
 TRAVEL.
  
 3) PLEASE ALSO REVIEW THE REQUIREMENTS FOR PANIC AND
 FIRE EXIT HARDWARE FOUND WITHIN SECTION 1008.1.10 OF
 THE FBC-B DOORS SERVING A GROUP A OCCUPANCY OR DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN A GROUP A OCCUPANCY SHALL NOT BE PROVIDED WITH
 A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE
 EXIT HARDWARE.
  
 4) THE COVERSHEET A-0.1DOES INDICATE THIS IS A FIRE
 SPRINKLERED BUILDING, SHEET A-2.2 DOES NOT INDICATE
 WHICH DOORS ARE GOING TO BE THE EXIT DOORS, PLEASE
 PROVIDE EXIT LIGHTS AND OR REQUIRED DIRECTIONAL LIGHTS
 FOR EXITING OF THE ASSEMBLY USAGE AREA PER SECTION
 1006.1 ILLUMINATION REQUIRED & 1006.3 EMERGENCY POWER
 FOR ILLUMINATION OF THE FBC-B.
  
 5) SHEET A-2.1 DETAIL # 4 SHOWS THE MENS RESTROOM WITH
 A TOTAL OF OVER 6 WATERCLOSETS AND URINALS. PLEASE
 PROVIDE COMPLIANCE WITH SECTION 213.3.1 OF THE 2014
 FBC-ACCESSIBILITY CODE. WHERE TOILET COMPARTMENTS ARE
 PROVIDED, AT LEAST ONE TOILET COMPARTMENT SHALL COMPLY
 WITH 604.8.1. IN ADDITION TO THE COMPARTMENT REQUIRED
 TO COMPLY WITH 604.8.1, AT LEAST ONE COMPARTMENT SHALL
 COMPLY WITH 604.8.2 WHERE SIX OR MORE TOILET
 COMPARTMENTS ARE PROVIDED, OR WHERE THE COMBINATION OF
 URINALS AND WATER CLOSETS TOTALS SIX OR MORE FIXTURES.
 PLEASE NOTE THE CONTRACTOR WOULD NEED TO SHOW
 COMPLIANCE WITH THIS SECTION OR PROVIDE DOCUMENTATION
 WHERE DISPROPORTIONATE COST ($44,708.00) HAVE BEEN MET,
 PROVIDE AN ITEMIZED WHERE THE FUNDS HAVE BEEN SPENT IN
 THIS ORDER.
  
 2014 ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-20 Cont ID  
Sent By rlecky Date 2016-12-20 Time 13:04 Rev Time 0.00
Received By rlecky Date 2016-12-20 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-29 Cont ID  
Sent By rlecky Date 2016-11-29 Time 14:06 Rev Time 0.00
Received By rlecky Date 2016-11-29 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By wjolin Date 2016-12-15 Time 14:33 Rev Time 0.00
Received By wjolin Date 2016-12-15 Time 14:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By wjolin Date 2016-11-16 Time 13:48 Rev Time 0.00
Received By wjolin Date 2016-11-16 Time 13:17 Sent To  
Notes
2016-11-16 13:48:531401 NORTHPOINT PARKWAY
 PERMIT #16110654
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY;
 HOWEVER, THIS APPEARS TO BE MIXED USE BUSINESS AND
 ASSEMBLY OCCUPANCY. PROVIDE A LIFE SAFETY PLAN BASED
 UPON AN ASSEMBLY OCCUPANCY. CURRENTLY TWO EXIT DOORS
 ARE SHOWN; HOWEVER, THEY ARE NOT SEPARATED BY A GREAT
 ENOUGH DISTANCE TO BE CONSIDERED TWO EXITS.
  
 DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 SHALL SWING IN THE DIRECTION OF EGRESS.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 COULD NOT LOCATE ANY EMERGENCY LIGHTING IN THE ASSEMBLY
 AREA. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-09 Cont ID  
Sent By ccole Date 2017-01-09 Time 08:47 Rev Time 0.00
Received By ccole Date 2017-01-09 Time 08:47 Sent To  
Notes
2017-01-05 11:33:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-30 Cont ID  
Sent By gjohnson Date 2016-12-30 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2016-12-13 Time 14:02 Sent To  
Notes
2016-12-14 14:02:23B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By jwitmer Date 2016-12-05 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2016-11-14 Time 14:07 Sent To  
Notes
2016-11-15 14:07:43B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By jwitmer Date 2016-12-05 Time 08:43 Rev Time  
Received By jwitmer Date 2016-12-05 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-09 Cont ID  
Sent By ccole Date 2017-01-09 Time 08:47 Rev Time 0.00
Received By ccole Date 2017-01-09 Time 08:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-28 Cont ID  
Sent By ccole Date 2016-12-28 Time 07:28 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 17:20 Sent To  
Notes
2016-12-28 07:35:472ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110654
 12/28/16
  
 1) SHEETS M-2.1 & M-3.1: EF-1 IN THE WOMEN'S TOILET
 ROOM HAS A CAPACITY OF 150 CFMS BUT THE EXHAUST RATE
 REQUIRED PER THE PLAN IS 200 CFMS. PLEASE NOTE THAT PER
 TABLE 403.3, 210 CFMS IS REQUIRED FOR INTERMITTENT
 OPERATION.
  
 2) M-2.1 & M-3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXHAUST FAN SERVING THE REMODELED MEN'S TOILET ROOM-
 MINIMUM 700 CFMS REQUIRED FOR INTERMITTENT OPERATION,
 AND 500 CFMS FOR CONTINUOUS- TABLE 403.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-22 Cont ID  
Sent By ccole Date 2016-11-22 Time 15:12 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 15:12 Sent To  
Notes
2016-11-22 15:27:241ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16110654
 11/22/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHOW THE LOCATION OF EF-1 ON THE PLAN AND INDICATE
 CONTROL OPERATION.
  
 3) REFER TOTABLE 6-4 ASHRAE 62.1-2010. KITCHENETTES
 REQUIRE EXHAUST VENTILATION AT A RATE OF 0.30 CFMS/SF.
 PLEASE REVISE THE PLAN TO SHOW COMPLIANCE.
  
 4) DIFFUSER SIZES AND SUPPLY CFMS NOT NOTED FOR TWO
 DROPS IN THE TECH. TOILETS ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-30 Cont ID  
Sent By gjohnson Date 2016-12-30 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2016-12-30 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-12-03 Cont ID  
Sent By tklarge Date 2016-12-03 Time 08:16 Rev Time 0.00
Received By tklarge Date 2016-12-03 Time 07:16 Sent To  
Notes
2016-12-03 08:16:191) A AT LEAST ONE LAVATORY OUTSIDE THE ACCESSIBLE
 TOILET COMPARTMENT SHALL COMPLY WITH FAC SEC.213.3.4.
 2) AN AMBULATORY ACCESSIBLE STALL IS REQUIRED IN THE
 MEN'S TOILET ROOM PER THE FAC SEC.604.8.2, 604.8.2.2.
 3) DRINKING FOUNTAINS ARE REQUIRED IN THIS SPACE PER
 2014 FBC - PLUMBING TABLE 403.1 FOOTNOTE (E) AND FAC
 SEC.211.2.
 4) IDENTIFY THE HANDICAPPED URINAL ON THE PLANS. THE
 URINAL SHALL COMPLY WITH FAC SEC. 605.
 5) THE VENDING MACHINES SHALL COMPLY WITH FAC
 SEC.228.1.
 6) THE ICE MACHINE SHALL BE EQUIPPED WITH A BACKFLOW
 PREVENTER ON THE WATER LINE PER FPC SEC.608.3.
 7) TEMPERED WATER IS REQUIRED FOR THE LAVATORIES IN THE
 TOILET ROOMS. FPC SEC.607.1.
 8) HOT WATER IS REQUIRED AT THE BREAKROOM SINK. FPC
 SEC. 607.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved