Plan Review Details - Permit 16110641
Plan Review Stops For Permit 16110641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-23 Cont ID  
Sent By mvaldes Date 2016-11-23 Time 09:36 Rev Time 0.00
Received By mvaldes Date 2016-11-23 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-17 Time 13:57 Rev Time 0.00
Received By mvaldes Date 2016-11-17 Time 13:06 Sent To  
Notes
2016-11-17 13:55:57REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] ALONG WITH THE RISER DIAGRAM PROVIDE COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC 107.3.5.3
  
 2] PLEASE ADD THE INTERSYSTEM BONDING TERMINAL TO THE
 GROUNDING DETAIL REQUIRED PER FBC-R SECTION E3609.3
  
 3] PROVIDE AN ELECTRICAL SITE SPECIFIC FLOOR PLAN WITH
 ALL POWER & LIGHTING OUTLETS AND INCLUDE THE FOLLOWING;
  
 A] 2 SMALL APPLIANCE DEDICATED 20 AMP CIRCUITS IN THE
 KITCHEN GFCI PROTECTED. FBC-R SECTION E3703.2 & E3902.6
 B] LOCATION OF SMOKE DETECTORS ON THE FLOOR PLAN. FBC-R
 SECTION 314 & 315
 C] MARK AFCI PROTECTED CIRCUITS ON THE FLOOR PLAN. .
 FBC-R SECTION E3902.12
 D] ADD A NOTE FOR TAMPER-RESISTANT RECEPTACLES. FBC-R
 SECTION E4002.14
 E] SHOW THE SERVICE RECEPTACLE BY THE MECHANICAL
 EQUIPMENT. FBC-R SECTION E3901.11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-17 Cont ID  
Sent By mvaldes Date 2016-11-17 Time 13:57 Rev Time 0.00
Received By mvaldes Date 2016-11-14 Time 11:36 Sent To  
Notes
2016-11-15 11:36:42ROUTED TO ELECTRICAL INBOX