Plan Review Details - Permit 16110614
| Plan Review Stops For Permit 16110614 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-04 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-04 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-11-28 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-11-28 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2016-11-28 09:49:34 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] LABEL EACH AREA ON THE FLOOR PLAN WITH THE | | | OCCUPATION IT PROPERLY SERVES. FBC 107 | | | | | | 2] ADD FA DEVICES PER FIRE MARSHALL REQUEST IN | | | ACCORDANCE WITH NFPA 101 & NFPA 72 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-12-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-12-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-12-30 |
Time |
12:49 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-11-17 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-11-28 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-11-16 |
Time |
16:16 |
Sent To |
E |
|
| Notes |
| 2016-11-17 14:00:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE APPEARS TO BE LIMITED DETAIL IN EACH OF THE | | | SEPARATED OCCUPANCIES INDICATED WALL SECTIONS, | | | BATHROOMS, OFFICES, ETC, THAT MAY BE REQUIRED TO HAVE | | | ALARM NOTIFICATIONS. | | | | | | PLEASE PROVIDE FOR GREATER DETAIL IN EACH OF THE AREAS | | | AND NOTIFICATIONS DEVICES AS REQUIRED PER NFPA 101, | | | CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION | | | EQUIPMENT, 9.6 FIRE DETECTION, ALARM, AND | | | COMMUNICATIONS SYSTEMS AND NFPA 72. | | | | | | PROVIDE CODE AND NARATIVE JUSTIFICATION IF YOU BELIEVE | | | THEY MAY NOT BE REQUIRED. | | | | | | | | | | | | 2) THERE APPEARS TO BE DIFFERENCT OCCUPANCIES OR SPACES | | | THAT MAY BE VACANT. | | | | | | PLEASE PROVIDE THE OCCUPANCIES CLASSIFICATION OF EACH | | | SPACE AND THE DETAILED PROPOSED ALARM DEVICES OF THE | | | SPACE AS THERE MAY BE SEPARATE/DIFFERENT REQUIRMENTS | | | THAT NEED TO BE MET. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-04 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-04 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2016-12-29 10:01:44 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-11-28 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-11-14 |
Time |
13:36 |
Sent To |
FIRE |
|
| Notes |
|
|
|