| 2016-12-06 07:38:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16110574 |
| | ADD: 3200 N. CONGRESS |
| | CONT: HEDRICK BROTHERS |
| | TEL: 561-308-2954 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 06/2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 002_A001 THE SITE PLAN UNDER THE HEADING OF |
| | BUILDING DATA LIST THIS BUILDING OCCUPANCY AS A UTILITY |
| | CLASSIFICATION. |
| | SECTION 312 OF THE 2014 FBC-B LIST SHEDS, CARPORTS, |
| | PRIVATE GARQAGES AND BARNS AS EXAMPLES OF A UTILITY |
| | OCCUPANCY, NONE OF THESE TYPE STRUCTURES HAVE |
| | OCCUPIABLE SPACE. THIS SPACE RESEMBLES MORE A BUSINESS |
| | TYPE OF OCCUPANCY WHERE ONE OR MORE PERSONS MONITORS |
| | THE SECURITY OF THE DEVELOPMENT BY WHO ENTERS THE |
| | PROJECT. PLEASE ALSO NOTE UNDER TABLE 1004.1.2. THERE |
| | ARE NO CLASSIFICATIONS FOR OCCUPANT LOADS FOR THE |
| | UTILITY USAGE. WITH A BUSINESS OCCUPANCY A OCCUPANCY |
| | LOAD OF 3 WOULD BE ASSIGNED TO THE BUILDING. |
| | |
| | 2) SHEET 006_A102 THE KITCHENETTE DETAIL SHOWS A |
| | MICROWAVE ABOVE THE REACH RANGES AND RANGE FOR OPERABLE |
| | PARTS. SEE THE 2014 FBC-ACCESSIBILITY CODE SECTIONS 308 |
| | & 309 FOR CODE COMPLIANCE. |
| | |
| | 3) SHEET 014-A501 THE WATER CLOSET GRAB BARS THE |
| | HEIGHTS ARE LISTED FROM FINISH FLOOR TO THE CENTERLINE |
| | OF THE GRAB BARS. PLEASE REVIEW THE 2014 |
| | FBC-ACCESSIBILITY CODE. THIS CODE MEASURES THE GRAB BAR |
| | TO THE TOP OF THE GRASABLE SURFACE SEE SECTION 609.4. |
| | |
| | 4) SHEET 016_A602 DETAIL FOR SLIDING DOOR HEAD DETAIL |
| | INDICATES THE USE OF BLOCKING/ BUCK. THE NOTE INDICATES |
| | FASTENERING PER MANUFACTURERS RECOMMENDATIONS. PLEASE |
| | NOTE PRODUCT APPROVALS DO NOT INDICATE HOW TO FASTEN |
| | BUCKS, THAT IS UP TO THE DESIGN PROFESSIONAL TO PROVIDE |
| | THE THICKNESS OF THE BUCKS AND ANCHORS. PLEASE ALSO SEE |
| | THE REQUIREMENTS IN THE 2014 FBC-B 1710.10 MASONRY, |
| | CONCRETE OR OTHER STRUCTURAL SUBSTRATE. |
| | WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 |
| | 1/2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE |
| | ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR |
| | SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S |
| | PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE |
| | SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE |
| | OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS |
| | OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| | MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| | LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| | TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE |
| | ROUGH OPENING SUBSTRATE. |
| | |
| | WHERE THE WOOD BUCK THICKNESS IS 1 1/2 INCHES (38 MM) |
| | OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO |
| | TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE AND THE BUCK SHALL EXTEND BEYOND |
| | THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW |
| | AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN |
| | FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE |
| | FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE |
| | MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS. |
| | UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| | MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| | LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| | TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY |
| | TO THE SECURED WOOD BUCK. |
| | |
| | 5) NOTED: BUILDING PROVISO: DEFERRED SUBMITTALS |
| | 107.3.4.2 REQUEST. |
| | 5.1) EXTERIOR WINDOWS AND DOORS |
| | 5.2) WOOD TRUSSES |
| | 5.3) ALUMINUM LOUVER PANELS |
| | 5.4) ROOFING ASSEMBLIES |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |