| 2017-02-02 18:31:56 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER OR LEGALLY OWNER'S DESIGNATED AGENT NEEDS TO |
| | SIGN AND DATE BOTTOM OF FORM AS REQUIRED BY SEC. |
| | R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING NAME OF BUILDER (OWNER'S NAME IF IS AN |
| | OWNER/BUILDER). SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) THE SQUARE FOOTAGE ON ITEM #5 IS INCORRECT. THE |
| | TOTAL AREA O THE NEW PLAYROOM IS 442 S.F. NOT 373 S.F. |
| | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) THE WINDOW AREA ON ITEM #6(C) IS INCORRECT. NEED TO |
| | INCLUDE ALL WINDOWS IN THE NEW PLAYROOM AND NEED TO |
| | INCLUDE THE GLASS AREA OF THE SLIDING GLASS DOORS AS |
| | REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| | |
| | E) REVISE FLOOR AREA ON ITEM #8. COORDINATE WITH ITEM |
| | #1(C) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F) REVISE WALL INFORMATION ON ITEM #9. THERE IS NOT |
| | ADJACENT WALLL. ADJACENT IS IS THE WALL THAT SEPARATES |
| | CONDITIONED AREA WITH UNCONDITIONED AREA. THERE IS NOT |
| | UNCONDITIONED AREA BETWEEN THE EXISTING HOUSE AND THE |
| | NEW PLAYROOM. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | G) EXTERIOR MASONRY WALL REQUIRES MIN. R-4 INSULATION |
| | ON THE INTERIOR SIDE OF THE WALL AND MIN. R-3 |
| | INSULATION ON THE EXTERIOR SIDE OF THE WALL AS REQUIRED |
| | BY TABLE R402A OF THE PRESCRIPTIVE ENERGY CALCULATIONS |
| | SUBMITTED. SEE FOOTNOTE #4. THE WALL INFORMATION ON |
| | ITEM #9 NEEDS TO BE CHANGED ACCORDINGLY. |
| | |
| | H) HVAC SIZING CALCULATIONS IS REQUIRED. REVISE ITEM |
| | #14. IT IS NOT N/A. |
| | |
| | NOTE: |
| | LABEL FOR THE DOORS AND WINDOWS U-FACTOR AND SHGC |
| | FACTOR WILL BE REQUIRED TO VERIFY COMPLIANCE WITH THE |
| | ENERGY CALCULATIONS SUBMITTED. |
| | |
| | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXTERIOR WALL IS GOING TO HAVE R-6 INSULATION |
| | IN THE INTERIOR SIDE OF THE WALL AND R-4.1 INSULATION |
| | IN THE EXTERIOR SIDE OF THE WALL AS REQUIRED BY TABLE |
| | R402A OF PRESCRIPTIVE ENERGY CALCULATIONS SUBMITTED. |
| | SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | 3- PRESCRIPTIVE ENERGY CALCULATIONS SUBMITTED REQUIRE |
| | R-30 ROOF INSULATION. ROOF FRAMING PLAN AND TYPICAL |
| | WALL SECTION SPECIFY 2 X 10 ROOF JOISTS. R-30 BATT |
| | INSULATION IS ABOUT 9-1/2 INCHES THICK. THERE IS NO |
| | ROOM FOR THE REQUIRED 1 INCH MIN. SPACE REQUIRED BY |
| | SEC. R806.3 FBC-RESIDENTIAL FOR VENTILATION. REVISE AS |
| | REQUIRED TO COMPLY WITH THE ENERGY CALCULATIONS. |
| | |
| | 4- TYPICAL EXTERIOR WALL DETAIL ON SHEET S.2 AND ROOF |
| | FRAMING PLAN ON SHEET S.3 SPECIFY 2 X 10 ROOF JOISTS. |
| | THIS ROOF JOIST SIZE DOESN'T ALLOW ROOF CROSS |
| | VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). CROSS VENTILATION REQUIRES A LEAST |
| | 1 INCH SPACE BETWEEN THE INSULATION AND THE BOTTOM OF |
| | THE ROOF SHEATHING. R-30 INSULATION IS ABOUT 9-1/2" |
| | THICK, THEREFORE THE 1 INCH SPACE IS NOT PROVIDED. |
| | REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 5- FLAT ROOF NOA 14-0827.14 SUBMITTED: |
| | A) IT CAN NOT BE USED BECAUSE THIS NOA IS FOR |
| | "CEMENTITIOUS WOOD FIBER DECKS". THIS IS NOT THE TYPE |
| | OF DECK SPECIFIED ON PLANS. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR WOOD DECKS AS SPECIFIED ON PLANS. FAC |
| | 61G20-3.002(33). |
| | |
| | B) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | C) IF SELECTED ASSEMBLY DOESN'T MET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS WILL BE |
| | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. APPROVED ASSEMBLIES THAT ARE LIMITED BY |
| | GENERAL LIMITATION #9 MAY NOT BE USED IF THE DESIGN |
| | PRESSURES ARE TOO LOW. LIMITATION #9 DOESN'T ALLOW RAS |
| | 117 CALCULATIONS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR; |
| | A) WINDOW MULLIONS AS SPECIFIED ON PLANS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) PRE-CAST LINTELS AS SPECIFIED ON PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | |
| | 8- NORTH ARROW ORIENTATION SHOWN ON ALL PLANS IS |
| | INCORRECT. REVISE AS REQUIRED, INCLUDING THE CORRECT |
| | EXTERIOR ELEVATIONS ORIENTATION. SEE PALM BEACH COUNTY |
| | PROPERTY APPRAISER OR SURVEY. SEC. 107.2.1 CITY |
| | AMENDMENTS. THIS IS IMPORTANT FOR CORRECT ENERGY |
| | CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | NOTES: |
| | ****A) PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***B) PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | ONE. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS FOR |
| | REFERENCE. |
| | |