Plan Review Details - Permit 16110554
Plan Review Stops For Permit 16110554
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 07:30 Rev Time  
Received By jwitmer Date 2016-11-29 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 11:07 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 10:55 Sent To M
Notes
2016-12-08 11:08:09ROUTED TO CC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By mvaldes Date 2016-11-21 Time 11:44 Rev Time 0.00
Received By mvaldes Date 2016-11-21 Time 10:53 Sent To  
Notes
2016-11-21 11:45:34JOB PERMIT NUMBER: 16110554
 JOB ADDRESS: 500 AUSTRALIAN AVE
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 21, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A PANEL SCHEDULE WITH MATCHING DESIGNATED
 CIRCUITS ON THE FLOOR PLAN. FBC-107
  
 2] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4)
  
 3] SHOW A FIRE PENETRATION DETAIL IN COMPLIANCE WITH
 FBC 714 & NEC 300.21.
  
 4] FIRE ALARM SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT. A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-16 Cont ID  
Sent By wjolin Date 2016-11-16 Time 10:33 Rev Time 0.00
Received By wjolin Date 2016-11-16 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By ccole Date 2016-12-08 Time 12:22 Rev Time 0.00
Received By ccole Date 2016-12-01 Time 14:58 Sent To  
Notes
2016-12-01 14:58:42RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By ccole Date 2016-11-29 Time 15:08 Rev Time 0.00
Received By ccole Date 2016-11-10 Time 09:56 Sent To  
Notes
2016-11-14 09:56:36B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 07:31 Rev Time  
Received By jwitmer Date 2016-11-29 Time 07:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By ccole Date 2016-12-08 Time 12:22 Rev Time 0.00
Received By ccole Date 2016-12-08 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By ccole Date 2016-11-29 Time 14:59 Rev Time 0.00
Received By ccole Date 2016-11-29 Time 14:59 Sent To  
Notes
2016-11-29 15:08:371ST REVIEW FBC-2014 MECHANICAL, EXISTNG BUILDING CODES
 PERMIT #16110554
 11/29/16
  
 1) SHEET 2: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET 2: INDICATE THE DUCT, DIFFUSER, AND GRILL
 SIZES IN THE CONF RM, AND OFFICES 4 AND 5. SHOW THE
 SUPPLY AND RETURN CFMS AT EACH DIFFUSER AND GRILL.
  
 3) SHEET 2: PROVIDE AN AIR DEVICE SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  