Plan Review Details - Permit 16110549
Plan Review Stops For Permit 16110549
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By jwitmer Date 2017-01-09 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2017-01-09 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 07:36 Sent To  
Notes
2016-11-29 08:17:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110549
 ADD: 1555 PALM BEACH LAKES BLVD. SUITE # ???????
 CONT: URBIK BUILDING GROUP
 TEL: 561-727-8343
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 29/2016
 ACTION: DENIED
  
 1) NEITHER THE PLANS NOR THE PERMIT APPLICATION PROVIDE
 THE SUITE NUMBER IDENTIFYING WHERE THE WORK UNDER THIS
 PERMIT WILL BE ACCOMPLISHED. THE INSPECTORS NEED THIS
 INFORMATION TO LOCATE THE PROJECT AS WELL FOR RECORD
 RETENTION.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION OF THE PROJECT.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS
 ADDRESS, MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2) SHEET A-1 THE DOORWAY BETWEEN THE WAITING ROOM AND
 HALLWAY 115 DOES NOT HAVE THE REQUIRED 18 INCHES ON THE
 LATCH SIDE OF THE DOORWAY IN COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 404.2.4.1.
  
 3) SHEET A-1 THE 2ND EXITING DOORWAY FROM THE SPACE IS
 CENTERED IN THE WALL BUT DOES NOT PROVIDE COMPLIANCE
 WITH ACCESS. CODE 404.2.4.1.
  
 3A) THE PLANS DO NOT INDICATE ID THE MENTIONED DOOR
 ABOVE IS NEW OR EXISTING, IF EXISTING COMPLIANCE WITH
 202.4.1 DISPROPORTIONATE COST. PLEASE SHOW IN AN
 ITEMIZED LIST WHERE UP TO 20 % OF THE CONTRACT VALUE
 WOULD BE USED IN MAKING THIS OFFICE COMPLIANT WITH THE
 EXISITNG BUILDING CODE AND ACCESSIBILITY CODES.
 2014 FBC-ACCESS. CODE 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-12-13 Cont ID  
Sent By rlecky Date 2016-12-13 Time 14:11 Rev Time 0.00
Received By rlecky Date 2016-12-13 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-19 Cont ID  
Sent By pleduc Date 2017-01-19 Time   Rev Time 0.00
Received By pleduc Date 2017-01-19 Time 13:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-16 Cont ID  
Sent By wjolin Date 2016-11-16 Time 11:31 Rev Time 0.00
Received By wjolin Date 2016-11-16 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 17:54 Rev Time 0.00
Received By ccole Date 2017-01-04 Time 14:31 Sent To  
Notes
2017-01-05 14:31:59B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-13 Cont ID  
Sent By rlecky Date 2016-12-13 Time 14:31 Rev Time 0.00
Received By rlecky Date 2016-11-10 Time 13:28 Sent To  
Notes
2016-11-14 13:28:28B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-01-24 Cont ID  
Sent By ccole Date 2017-01-24 Time 17:54 Rev Time 0.00
Received By ccole Date 2017-01-24 Time 17:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By ccole Date 2016-11-21 Time 08:47 Rev Time 0.00
Received By ccole Date 2016-11-21 Time 08:47 Sent To  
Notes
2016-11-21 08:58:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110549
 11/21/16
  
 1) CLARIFY HOW HEAT IS BEING PROVIDED TO THE NEW
 OFFICES. THE VAV BOX SCHEDULE DOES NOT INDICATE ANY
 HEATER CAPACITIES.
  
 2) THE DESIGN INSTALLATION AC CONTRACTOR- ALTMAN
 BROTHERS MUST SUBMIT A SUB-PERMIT APPLICATION FOR THE
 PROPOSED PROJECT- SECTION 105.3.1.2 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-24 Cont ID  
Sent By gjohnson Date 2017-01-24 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2017-01-24 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By gjohnson Date 2016-11-28 Time 18:17 Rev Time 0.00
Received By gjohnson Date 2016-11-28 Time 12:54 Sent To  
Notes
2016-11-28 18:17:211ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 3. SHOW COMPLIANCE IN TRANSFER TYPE COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ACROSS THE CONTROL WALL AND BACK
 WALL TO A POINT 18 INCHES (455 MM) FROM THE CONTROL
 WALL. GRAB BARS SHALL COMPLY WITH 609 AND SHALL BE
 PROVIDED IN ACCORDANCE WITH 608.3. WHERE MULTIPLE GRAB
 BARS ARE USED, REQUIRED HORIZONTAL GRAB BARS SHALL BE
 INSTALLED AT THE SAME HEIGHT ABOVE THE FINISH FLOOR.
 PER FBC ACC 608.3.1
  
 4. SHOW COMPLIANCE FBC ACC 608.5.1 TRANSFER TYPE SHOWER
 COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 5. SHOW COMPLIANCE FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 (64 MM) MAXIMUM AND THE FRONT EDGE 15 INCHES (380 MM)
 MINIMUM AND 16 INCHES (405 MM) MAXIMUM FROM THE SEAT
 WALL. THE REAR EDGE OF THE ?L? PORTION OF THE SEAT
 SHALL BE 11/2 INCHES (38 MM) MAXIMUM FROM THE WALL AND
 THE FRONT EDGE SHALL BE 14 INCHES (355 MM) MINIMUM AND
 15 INCHES (380 MM) MAXIMUM FROM THE WALL. THE END OF
 THE ?L? SHALL BE 22 INCHES (560 MM) MINIMUM AND 23
 INCHES MAXIMUM (585 MM) FROM THE MAIN SEAT WALL.
  