Plan Review Details - Permit 16110470
Plan Review Stops For Permit 16110470
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By shill Date 2016-12-13 Time 15:04 Rev Time 0.00
Received By shill Date 2016-12-13 Time 15:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 15:04 Rev Time 0.00
Received By shill Date 2016-11-29 Time 15:04 Sent To  
Notes
2016-11-29 15:07:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A 202.3, 404.2.4, RESTROOM 105DOOR LACKS THE
 18IN MANEUVERING CLEARANCE (PULL SIDE) REQUIRED, PLEASE
 REVISE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By mvaldes Date 2016-12-21 Time 17:04 Rev Time 0.00
Received By mvaldes Date 2016-12-21 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By mvaldes Date 2016-11-21 Time 10:45 Rev Time 0.00
Received By mvaldes Date 2016-11-21 Time 09:12 Sent To  
Notes
2016-11-21 10:46:02JOB PERMIT NUMBER: 16110470
 JOB ADDRESS: 5500 VILLAGE BLVD
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 21, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT
 FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW
 SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM
 PROVISIONS ASTM 635C & 636C.
  
 2] PLEASE ADD EXIT SIGNS IN THE COPY MAIL AREA FOR THE
 DOOR LEADING TO THE EGRESS STAIRS & ADD AN EXIT SIGN
 FOR THE EXIT DISCHARGE WITHIN THE BREAKROOM. FBC-1011
  
 3] AT LEAST 50 % OF ALL 125 V 15 & 20 AMP RECEPTACLES
 INSTALLED IN PRIVATE OR OPEN OFFICES INCLUDING MODULAR
 PARTITIONS SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL
 DEVICE PER FBC-E SECTION C405.7.1 CONFORMANCE WITH
 ASHREA 90.1, 8.4.2. THIS APPLIES TO THE POWER POLE
 FEEDS FOR THE MODULAR OFFICES.
  
 4] GFCI PROTECTION IS REQUIRED WHERE RECEPTACLES ARE
 INSTALLED WITHIN 6' OF THE SINK & INSIDE BATHROOMS. NEC
 210.8(B) PLEASE VERIFY BREAKROOM & RESTROOM.
  
 5] ACCESS CONTROL & FIRE ALARM PLANS SHALL BE SUBMITTED
 UNDER A SEPARATE PERMIT. A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-16 Cont ID  
Sent By pleduc Date 2016-11-16 Time   Rev Time 0.00
Received By pleduc Date 2016-11-15 Time 17:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-21 Cont ID  
Sent By mvaldes Date 2016-12-21 Time 17:04 Rev Time 0.00
Received By mvaldes Date 2016-12-06 Time 09:16 Sent To  
Notes
2016-12-07 09:16:44C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 15:07 Rev Time 0.00
Received By shill Date 2016-11-09 Time 12:14 Sent To  
Notes
2016-11-09 12:14:35C11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-19 Cont ID  
Sent By ccole Date 2016-12-19 Time 10:03 Rev Time 0.00
Received By ccole Date 2016-12-19 Time 17:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 12:30 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 12:24 Sent To  
Notes
2016-11-14 12:54:221ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110470
 11/14/16
  
 1) SHEET M1: PROVIDE SPECIFIC NOTE #13 SHOWN AT AHU-2,
 AND IT APPEARS NOTE #3 DOES NOT APPLY TO THE ERV.
  
 2) CLARIFY THE LOCATIONS OF THE NEW CONDENSERS AND
 PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING- SEE
 SECTIONS 301.15 AND 1609 FBC-14 BUILDING. IF USING THE
 BMP CLIPS, AS SHOWN ON M2, PLEASE SUBMIT THE PRODUCT
 APPROVAL WITH ALL APPLICABLE INSTALLATION DETAILS,
 NOTES, DESIGN PRESSURES ETC. CIRCLED, HIGHLIGHTED, OR
 OTHERWISE MARKED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-12-13 Cont ID  
Sent By shill Date 2016-12-13 Time 12:53 Rev Time 0.00
Received By shill Date 2016-12-13 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-21 Cont ID  
Sent By gjohnson Date 2016-12-21 Time 13:03 Rev Time 0.00
Received By gjohnson Date 2016-12-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-28 Cont ID  
Sent By tklarge Date 2016-11-28 Time 05:01 Rev Time 0.00
Received By tklarge Date 2016-11-28 Time 04:17 Sent To  
Notes
***NONE***