| 2016-11-15 13:24:37 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ENGINEER "FASTENER SPACING CALCULATIONS" SUBMITTED |
| | VIA-MAIL: |
| | A) CALCULATIONS SUBMITTED ARE NOT THE RAS 117 |
| | CALCULATIONS. PROVIDE THE ACTUAL RAS 117 CALCULATIONS |
| | AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA 15-0921.05 SUBMITTED. |
| | NEED CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC. |
| | R301.1 FBC-RESIDENTIAL, TTH EDITION (2014). |
| | |
| | B) ENGINEER TO CLARIFY WHY USING 12 FASTENERS FOR THE |
| | FIELD AND PERIMETER AREAS AND 16 FASTENERS FOR THE |
| | CORNER AREAS. WHERE IN THE PRODUCT APPROVAL SUBMITTED |
| | SPECIFIES THAT FASTENER DENSITY. SEE PAGE 16 OF 29 OF |
| | NOA SUBMITTED. |
| | SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | C) ENGINEER TO PROVIDE ILLUSTRATION SHOWING THE |
| | LOCATION OF THE NUMBER OF FASTENERS SPECIFIED ON THE |
| | PREVIOUS COMMENT AS REQUIRED BY FIGURE 2 OR FIGURE 3 OF |
| | RAS 117. |
| | SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | D) ENGINEER TO CLARIFY WHY PROVIDING A "FASTENER |
| | SPACING REDUCTION FACTOR CALCULATIONS". THE PURPOSE OF |
| | RAS 117 CALCULATIONS IS TO PROVIDE NAIL ENHANCEMENT NOT |
| | NAIL REDUCTION. |
| | SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | E) ENGINEER TO REVISE THE "GIVEN DATA". THE SYSTEM |
| | MANUFACTURER FOR THE ROOF SYSTEM TO BE INSTALLED IS NOT |
| | GAF. SEE PRODUCT APPROVAL SUBMITTED AND REVISE AS |
| | REQUIRED. |
| | SEC. 1074.2.1 CITY AMENDMENTS. |
| | |
| | F) ENGINEER TO REVISE THE "DESIGN CRITERIA". WHY THE |
| | LINE FOR INSULATION IS N/A IF THE SELECTED ASSEMBLY ON |
| | PAGE 16 IS FOR AN INSULATED ASSEMBLY. REVISE AS |
| | REQUIRED. |
| | SEC. 1074.2.1 CITY AMENDMENTS. |
| | |
| | G) ENGINEER TO CLARIFY SECOND PARAGRAPH OF THE |
| | CONCLUSION. IS THIS A 4" X 4" ISO-INSULATION PANEL OR |
| | 4' X 4' ISO-INSULATION PANEL?. |
| | SEC. 1074.2.1 CITY AMENDMENTS. |
| | |
| | |