Plan Review Details - Permit 16110448
Plan Review Stops For Permit 16110448
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-13 Cont ID  
Sent By jwitmer Date 2017-02-13 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2017-02-13 Time 13:57 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-26 Cont ID  
Sent By jwitmer Date 2017-01-26 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2017-01-26 Time 09:07 Sent To  
Notes
2017-01-26 09:29:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110448
 ADD: 7130 OKEECHOBEE BLVD.
 CONT: LAGASSE' POOL
 TEL: 954-587-1000
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. JAN. 26/ 2017
 ACTION: DENIED
  
 IMPORTANT NOTICE!!!!!!!WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1) 2ND REQUEST. SHEET 1 OF 7 SHOW SECTIONS OF FENCING
 BY OTHERS BETWEEN BUILDINGS. THIS PLAN DEPICTS THE
 OUTLINE OF THE APARTMENT BUILDINGS AND RECREATION/
 LEASING CENTER WHICH SURROUND THE POOL AND POOL DECK.
 THE BUILDING ELEVATION PLANS OF THESE BUILDINGS DOES
 NOT INDICATE HOW SEPARATION FROM THE APARTMENT PATIO
 DECKS (FIRST FLOOR) AND THE POOL AND POOL DECK AREAS
 AND COMPLIANCE WITH 2014 FBC-B 454.1.3.1.9. ACCESS
 THROUGH THE BARRIER OR FENCE FROM DWELLING UNITS, SUCH
 AS HOMES, APARTMENTS, MOTEL ROOMS AND HOTEL ROOMS,
 SHALL BE THROUGH SELF-CLOSING, SELF-LATCHING LOCKABLE
 GATES OF 48 INCH (1219 MM) MINIMAL HEIGHT FROM THE
 FLOOR OR GROUND WITH THE LATCH LOCATED A MINIMUM OF 54
 INCHES (1372 MM) FROM THE BOTTOM OF THE GATE OR AT
 LEAST 3 INCHES (76 MM) BELOW THE TOP OF THE GATE ON THE
 POOL SIDE.
  
 2) 2ND REQUEST. SHEET 1 OF 7 THE SAME POOL SEPARATION
 ISSUE OCCURS WITHIN THE RECREATION/ LEASING BUILDING
 AND POOL/ POOL DECK AREA PLEASE SHOW COMPLIANCE WITH:
 2014 FBC-B 454.1.3.1.9. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. DOORED ACCESS POINTS FROM PUBLIC ROOMS
 SUCH AS LOBBIES OR CLUB HOUSES NEED NOT BE THROUGH
 GATES IF THE DOOR(S) MEET THE SAME SELF-CLOSING,
 SELF-LATCHING REQUIREMENTS AS A GATE. GATES SHALL OPEN
 OUTWARD AWAY FROM THE POOL AREA.
  
 3) COMPLIED. POOL HEATERS/ 2014 ENERGY CODE C404.7.3
 COVERS
  
 4)COMPLIED. POOL FOR RESIDENCE USE ONLY, UNDER FAIR
 HOUSING REQUIREMENTS.
  
 5) NEW COMMENT: SHEETS CH P-1, CH-P2 & CHE-4. THE PLANS
 ARE COPIED, REDUCED AND WITH A PRINTED DIGITAL
 SIGNATURE. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED ON ELECTRONICALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 IF THESE SHEETS ARE FOR REFERENCE USE ONLY, MARK AS
 SUCH. REFERENCE USE ONLY!!!
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By jwitmer Date 2017-01-03 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2017-01-03 Time 14:06 Sent To  
Notes
2017-01-03 16:00:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110448
 ADD: 7130 OKEECHOBEE BLVD.
 CONT: LAGASSE' POOL
 TEL: 954-587-1000
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JAN. 03/ 2017
 ACTION: DENIED
  
 1) SHEET 1 OF 7 SHOW SECTIONS OF FENCING BY OTHERS
 BETWEEN BUILDINGS. THIS PLAN DEPICTS THE OUTLINE OF THE
 APARTMENT BUILDINGS AND RECREATION/ LEASING CENTER
 WHICH SURROUND THE POOL AND POOL DECK. THE BUILDING
 ELEVATION PLANS OF THESE BUILDINGS DOES NOT INDICATE
 HOW SEPERATION FROM THE APARTMENT PATIO DECKS (FIRST
 FLOOR) AND THE POOL AND POOL DECK AREAS AND COMPLIANCE
 WITH 2014 FBC-B 454.1.3.1.9. ACCESS THROUGH THE BARRIER
 OR FENCE FROM DWELLING UNITS, SUCH AS HOMES,
 APARTMENTS, MOTEL ROOMS AND HOTEL ROOMS, SHALL BE
 THROUGH SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF
 48 INCH (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR
 GROUND WITH THE LATCH LOCATED A MINIMUM OF 54 INCHES
 (1372 MM) FROM THE BOTTOM OF THE GATE OR AT LEAST 3
 INCHES (76 MM) BELOW THE TOP OF THE GATE ON THE POOL
 SIDE.
  
 2) SHEET 1 OF 7 THE SAME POOL SEPARTION ISSUE OCCURS
 WITHIN THE RECREATION/ LEASING BUILDING AND POOL/ POOL
 DECK AREA PLEASE SHOW COMPLIANCE WITH:
 2014 FBC-B 454.1.3.1.9. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. DOORED ACCESS POINTS FROM PUBLIC ROOMS
 SUCH AS LOBBIES OR CLUB HOUSES NEED NOT BE THROUGH
 GATES IF THE DOOR(S) MEET THE SAME SELF-CLOSING,
 SELF-LATCHING REQUIREMENTS AS A GATE. GATES SHALL OPEN
 OUTWARD AWAY FROM THE POOL AREA.
  
 3) BOTH SHEETS 2 & 4 SHOW (2) POOL HEATERS, PLEASE SHOW
 COMPLIANCE WITH 2014 ENERGY CODE C404.7.3 COVERS.
 HEATED SWIMMING POOLS AND INGROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
 EXCEPTION: OUTDOOR POOLS DERIVING OVER 70 PERCENT OF
 THE ENERGY FOR HEATING FROM SITE-RECOVERED ENERGY, SUCH
 AS A HEAT PUMP OR SOLAR ENERGY SOURCE COMPUTED OVER AN
 OPERATING SEASON.
  
 4) THE PLANS DO NOT SHOW ANY MEANS OF AN ACCESSIBLE
 ENTRANCE, NOR DOES THE PLANS INDICATE THAT THE
 APARTMENTS DO NOT RECEIVE GOVERNMENT FINANIAL
 ASSISTANCE OR SPONSORSHIP AND WHOSE FACILITIES ARE
 INTENDED SOLEY FOR THE USE OF RESIDENTS AND THEIR
 GUESTS, ARE NOT SUBJECT TO THE ACCESSIBILITY CODE AND
 SECTION1009.2.1 POOL LIFTS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-23 Cont ID  
Sent By vperez Date 2017-01-23 Time 06:57 Rev Time 0.00
Received By vperez Date 2017-01-23 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-05 Cont ID  
Sent By vperez Date 2017-01-05 Time 08:24 Rev Time 0.00
Received By vperez Date 2017-01-05 Time 08:24 Sent To  
Notes
2017-01-05 08:29:32PLEASE SHOW ALL MOTOR PROVIDED WITH GFCI PROTECTION PER
 NEC 680.21C
  
 SHOW A GENERAL PURPOSE RECEPTACLE AT THE VAKPAK FOR
 SERVICE, TO BE GFCI PROTECTED. REFLECT ON PANEL
 SCHEDULE
  
 ADDRESS PLUMBING, BUILDING AND ZONING COMMENTS FOR A
 COMPLETE ELECTRICAL APPROVAL.
  
 V. PEREZ
 *6717

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By mgonzale Date 2017-02-06 Time   Rev Time 1.00
Received By mgonzale Date 2017-02-06 Time   Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-11-26 Cont ID  
Sent By tklarge Date 2016-11-26 Time 07:24 Rev Time 0.00
Received By tklarge Date 2016-11-26 Time 07:24 Sent To  
Notes
2016-11-26 07:25:30THERE IS NO GAS WORK ASSOCIATED WITH THIS SWIMMING
 POOL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-15 Cont ID  
Sent By lmarchan Date 2017-02-15 Time 13:41 Rev Time 0.00
Received By lmarchan Date 2017-02-06 Time 11:20 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-26 Cont ID  
Sent By jwitmer Date 2017-01-26 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2017-01-13 Time 14:01 Sent To  
Notes
2017-01-17 14:01:45RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-05 Cont ID  
Sent By vperez Date 2017-01-05 Time 08:29 Rev Time 0.00
Received By vperez Date 2017-01-05 Time 08:29 Sent To  
Notes
2016-11-09 10:54:19ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-09 Cont ID  
Sent By lmarchan Date 2017-02-15 Time 13:41 Rev Time 0.00
Received By tklarge Date 2017-02-07 Time 05:38 Sent To  
Notes
2017-02-07 13:28:521)

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-01-23 Cont ID  
Sent By tklarge Date 2017-01-23 Time 06:27 Rev Time 0.00
Received By tklarge Date 2017-01-23 Time 05:51 Sent To  
Notes
2017-01-23 06:03:491) SHT. 2 OF 7 - THE DRAIN FROM THE VAK-PAK IS NOT
 PERMITTED TO DISCHARGE TO THE STORM DRAINAGE SYSTEM PER
 CITY CODE OF ORDINANCES CHAPT.90, ART. V, SEC. 90-203
 (A).
 2) PROVIDE VERIFICATION THAT THE FILTRATION RATE HAS
 BEEN DESIGNED TO INCLUDE A FLOW RATE OF 3/4 GPM FOR
 EACH NON - TRANSIENT LIVING UNIT PER 2014 FBC
 SEC.454.1.1.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-26 Cont ID  
Sent By tklarge Date 2016-11-26 Time 07:25 Rev Time 0.00
Received By tklarge Date 2016-11-26 Time 04:55 Sent To  
Notes
2016-11-26 07:23:381) SHT. 2 OF 7 - THE DRAIN FROM THE VAK-PAK IS NOT
 PERMITTED TO DISCHARGE TO THE STORM DRAINAGE SYSTEM PER
 CITY CODE OF ORDINANCES CHAPT.90, ART. V, SEC. 90-203
 (A).
 2) SUBMIT MANUF. SPECCIFICATIONS FOR THE HEAT PUMPS.
 HEAT PUMPS SHALL COMPLY WITH THE 2014 FBC-ENERGY,
 SEC.C404.7.1 AND TABLE C404.2 FOR THE REQUIRED MINIMUM
 EFFICIENCIES.
 3) TIME SWITCHES OR OTHER CONTROL METHODS THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS TO A PRESET
 SCHEDULE SHALL BE INSTALLED ON ALL HEATERS AND HEAT
 PUMPS. FBC-ENERGY SEC.C404.7.2.
 4)PLEASE CLARIFY WHY THE CLUBHOUSE PLANS HAVE BEEN
 SUBMITTED. IF THEY ARE FOR REFERENCE ONLY, MARK THE
 PLANS AS SUCH. OTERWISE THE PLANS NEED TO BEAR THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL OF
 RECORD. FAC RULE 61G15-23.001.
 5) PROVIDE VERIFICATION THAT THE FILTRATION RATE HAS
 BEEN DESIGNED TO INCLUDE A FLOW RATE OF 3/4 GPM FOR
 EACH NON - TRANSIENT LIVING UNIT PER 2014 FBC
 SEC.454.1.1.1.
 6) PROVIDE VERIFICATION THAT THE MAXIMUM FILTRATION
 RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER
 AREA FOR THE CARTRIDGE FILTERS DOES NOT EXCEED 0.375
 PER 2014 FBC SEC.454.1.6.5.5.1.
 7) SHOW THE DISTANCE OF THE HOSE BIBB AND RIINSE SHOWER
 FROM THE POOL. WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT. 7 OF 7 - NOTES #6, 7, & 8 REFER TO FBC CODE
 SECTIONS 802 ( NOTE #6), 424.2.9 (NOTE #7), & FBC
 605.21 (NOTE #8). THESE CCODE SECTIONS HAVE NOTHING TO
 DO WITH SWIMMING POOL CONSTRUCTION. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-02-15 Cont ID  
Sent By llouie Date 2017-02-15 Time   Rev Time 0.00
Received By llouie Date 2017-02-13 Time 15:48 Sent To I
Notes
2017-02-15 09:59:53MINOR DSI AMENDMENT REQUIRED PRIOR TO FINAL C.O. FOR
 THE AS-BUILT.
  
  
  
  
2017-02-13 17:10:58ROUTED TO LINDA LOUIE

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-19 Cont ID  
Sent By llouie Date 2017-01-19 Time 08:48 Rev Time 0.00
Received By llouie Date 2017-01-17 Time 15:11 Sent To  
Notes
2017-01-19 08:50:20SEPARATE PERMIT APPLICATIONS REQUIRED FOR POOL
 LANDSCAPING AND FENCE.
  
  
  
  
  
  
  
2017-01-18 11:04:30ROUTED TO LINDA LOUIE

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-15 Cont ID  
Sent By njwira Date 2016-11-15 Time 17:53 Rev Time 0.00
Received By njwira Date 2016-11-09 Time 17:12 Sent To  
Notes
2016-11-15 17:54:0411/15/16- FAILED
  
 LANDSCAPE PLAN REQUIRED
  
 MEETS REQUIRED SETBACKS
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  