Plan Review Details - Permit 16110422
Plan Review Stops For Permit 16110422
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2017-02-01 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2017-01-11 Time 16:43 Sent To  
Notes
2017-01-11 16:43:39BUILDING PLAN REVIEW
 W. P. B. REVISION: 16110422
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDLING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: POOLE & KENT
 CONTACT
 TEL:
 E-MAIL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. DEC. 29/ 2016
 ACTION: DENIED
  
 1) SHEET 0382-A-ADF-04 FOR REFERENCE ONLY NO CHANGES.
  
 2) SHEET 0383-A-ADF-05 FOR REFERENCE ONLY NO CHANGES.
  
 3) SHEET 0390-A-ADF-12 FOR REFERENCE ONLY NO CHANGES.
 4) SHEET 0391-A-ADF-13 FOR REFERENCE ONLY NO CHANGES.
  
 FEES NOT PAID!!!!!!! NO REVIEW.
  
  
 5A) SHEET 0393-A-ADF-15 THE ORIGINAL PERMITTED SET OF
 PLANS ONLY SHOWS REVISION # 1. PLEASE SEE ON THE NEW
 SHEET SUBMITTED REVISION # 2 IS NEW, THIS IS CONSIDERED
 A REVISION TO THIS PERMIT. REUSE THE SUBMITTAL NUMBER
 OF 16110422 RECLASSIFY THIS IS A REVISION, AND PAY THE
 ADDITIONAL $150.00 REVISION FEE.
 5B) SINCE SHEET 0393-A-ADF-15 IS A REVISION THE
 ENGINEER OF RECORD WILL NEED TO COMPLY WITH:
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-29 Cont ID  
Sent By jwitmer Date 2016-12-29 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2016-12-29 Time   Sent To  
Notes
2016-12-29 16:21:10BUILDING PLAN REVIEW
 W. P. B. REVISION: 16110422
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDLING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: POOLE & KENT
 CONTACT
 TEL:
 E-MAIL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. DEC. 29/ 2016
 ACTION: DENIED
  
 1) SHEET 0382-A-ADF-04 FOR REFERENCE ONLY NO CHANGES.
  
 2) SHEET 0383-A-ADF-05 FOR REFERENCE ONLY NO CHANGES.
  
 3) SHEET 0390-A-ADF-12 FOR REFERENCE ONLY NO CHANGES.
 4) SHEET 0391-A-ADF-13 FOR REFERENCE ONLY NO CHANGES.
 5A) SHEET 0393-A-ADF-15 THE ORIGINAL PERMITTED SET OF
 PLANS ONLY SHOWS REVISION # 1. PLEASE SEE ON THE NEW
 SHEET SUBMITTED REVISION # 2 IS NEW, THIS IS CONSIDERED
 A REVISION TO THIS PERMIT. REUSE THE SUBMITTAL NUMBER
 OF 16110422 RECLASSIFY THIS IS A REVISION, AND PAY THE
 ADDITIONAL $150.00 REVISION FEE.
 5B) SINCE SHEET 0393-A-ADF-15 IS A REVISION THE
 ENGINEER OF RECORD WILL NEED TO COMPLY WITH:
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By jwitmer Date 2016-11-28 Time 16:01 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2016-11-28 16:01:07BUILDING PLAN REVIEW
 W. P. B. REVISION: 16110422 M1/M4 SLUDGE PUMPING/
 BOILER GAS BUILDING
 W. P. B. PERMIT: 15060551
 ADD: 4395 EASLEY ST.
 CONT: POOLE & KENT
 CONTACT: ??????
 TEL: ???????
 E-MAIL: ?????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. NOV. 28/ 2016
 ACTION: DENIED
  
 1) SHEETS BOILER-GAS HANDLING BLDG. ELEV. -A-ADF -12,
 BOILER GAS HANDLING PLAN-A-ADF-04 & M1-M4 SLUDGE
 PUMPING BLDG. ELEV. A-ADF-13, M1-M4 SLUDGE PUMPING BLDG
 PLAN A-ADF-05 & WALL SECTION ?A-ADF-15 NONE HAVE AN
 ELECTRONIC SIGNATURE NOR ANY DOCUMENTS UNDER THE
 SIGNATURE FOLDER.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS).
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2017-01-27 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2017-01-04 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-29 Cont ID  
Sent By jwitmer Date 2016-12-29 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-20 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-28 Cont ID  
Sent By jwitmer Date 2016-11-28 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2016-11-14 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 11:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-02-01 11:36:02SIGNATURES: SUBMITTED NO REVISION NO SIGNATURE
 REQUIRED. J. W.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 16:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-01-11 16:45:30FEES NOT PAID NO REVIEW.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-12-29 Cont ID  
Sent By jwitmer Date 2016-12-29 Time 16:21 Rev Time 0.00
Received By jwitmer Date 2016-12-29 Time 16:21 Sent To  
Notes
2016-12-29 16:21:551) SINCE SHEET 0393-A-ADF-15 IS A REVISION THE ENGINEER
 OF RECORD WILL NEED TO COMPLY WITH: 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.