Plan Review Details - Permit 16110372
Plan Review Stops For Permit 16110372
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By cthroop Date 2016-11-17 Time 10:27 Rev Time 0.00
Received By cthroop Date 2016-11-17 Time 10:23 Sent To P
Notes
2016-11-17 10:31:49BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. INSUFFICIENT INFORMATION TO PERFORM REVIEW.
 2. PROVIDE MANUFACTURE'S INSTALLATION INSTRUCTIONS FOR
 NEW EQUIPTMENT.
 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN PER FBC
 107.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By mvaldes Date 2016-11-16 Time 15:17 Rev Time 0.00
Received By mvaldes Date 2016-11-16 Time 15:09 Sent To B
Notes
2016-11-16 15:19:001ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A ELECTRICAL PLAN TO INCLUDE A PANEL
 SCHEDULE SHOWING WIRE, BREAKER & CONDUIT SIZE, CICUIT
 DESIGNATION TO MATCH THE FLOOR PLAN. FBC 107
  
 2] PROVIDE MANUFACTURE SPECIFICATIONS OF NEW EQUIPMENT
 TO BE INSTALLED
  
 3] GFCI PROTECTION IS REQUIRED FOR VENDING MACHINES,
 PLUG RECEPTACLES IN COMMERCIAL KITCHENS, & OUTLETS
 INSTALLED WITHIN 6' OF THE OUTSIDE EDGE OF A SINK. NEC
 422.51 & 210.8(B)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-21 Cont ID  
Sent By cthroop Date 2016-11-21 Time 16:04 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 10:33 Sent To  
Notes
2016-11-09 10:33:14ROUTED TO ELECTRICAL INBOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By gjohnson Date 2016-11-21 Time 15:49 Rev Time 0.00
Received By gjohnson Date 2016-11-21 Time 15:49 Sent To  
Notes
2016-11-21 16:04:491ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLANS ARE TO SMALL AND UNCLEAR OF WHAT PLUMBING WORK
 IS BEING INSTALLED. PER. WPB AMEND TO BC 107.2.1.4
  
 2. PROVIDE PLUMBING RISER WITH EXISTING AND NEW WORK
 SANITARY AND WATER.PER. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. ICE MACHINES AND BEVERAGE DISPENSERS ARE REQUIRED TO
 HAVE BACKFLOW DEVICES ON WATER SUPPLY AND TO BE
 INDIRECTLY DRAINED. PER FBC PL 608.3 / 802.1.1
 /608.16.1