Plan Review Details - Permit 16110180
Plan Review Stops For Permit 16110180
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By shill Date 2017-02-15 Time 09:11 Rev Time 0.00
Received By shill Date 2017-02-15 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-01-26 Cont ID  
Sent By shill Date 2017-01-26 Time 17:51 Rev Time 0.00
Received By shill Date 2017-01-26 Time 17:51 Sent To  
Notes
2017-01-26 17:58:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TWO COMMENTS REMAINING FROM PREVIOUS LIST (NOTE THAT A
 PROVISO WILL BE CONSIDERED; CONTACT S.KENNEDY IF I AM
 UNAVAILABLE):
  
 3. INCORRECT OCCUPANT LOAD FOR MERCANTILE, SEE FBC B
 TABLE 1004.1.2.
  
 THIS WAS CHANGED FROM 100 TO 60. SEE THE TABLE - GRADE
 FLOOR REQUIRES 30 SF PER PERSON. REVISE PLAN
 ACCORDINGLY.
  
 14. OFFICE DOOR LACKS MANEUVERING CLEARANCE, PULL SIDE,
 FBC ACCESSIBILITY 404.2.4.1.
  
 THIS WAS ADDRESSED BY SHOWING CLEAR FLOOR SPACE ON THE
 OPPOSITE SIDE. PLEASE REFER TO DIAGRAMS, 18" PULL SIDE
 REQUIRED, REVISE PLAN ACCORDINGLY.
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS:
  
 A. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED
 IN THE EXIT DISCHARGE; TO BE VERIFIED AT INSPECTION.
  
 B. PRODUCT APPROVALS TO BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-04 Cont ID  
Sent By shill Date 2017-01-04 Time 18:00 Rev Time 0.00
Received By shill Date 2017-01-04 Time 17:32 Sent To  
Notes
2017-01-04 18:00:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC EXISTING
 BUILDING CHAPTER 10.
  
 2ND REVIEW, PLAN REVISED TO STATE THAT THE PREVIOUS
 OCCUPANCY WAS "INDUSTRIAL". SEE FBC B CHAPTER
 10 AND REVISE PLAN TO DECLARE AN OCCUPANCY FROM THE
 BUILDING CODE FOR . DO YOU MEAN FACTORY
 INDUSTRIAL (F)? F1 OR F2?
  
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
 NO INFORMATION PROVIDED. IT APPEARS THAT
 YOU PROPOSE TO GO TO A HIGHER RISK IN SOME OR ALL OF
 THE TABLES. WHILE I AM ABLE TO DETERMINE
 COMPLIANCE IN SOME INSTANCES, NO SURVEY WAS PROVIDED SO
 COMPLIANCE WITH FBC EB TABLE 1012.6 CANNOT
 BE DETERMINED. WITHOUT A SURVEY AND OCCUPANCY
 CLASSIFICATION, COMPLIANCE CANNOT BE DETERMINED.
  
 2. SEE COMMENT 3.
  
 3. OCCUPANT LOAD WAS PROVIDED USING 100 SF PER PERSON,
 BUT IT APPEARS THAT A PORTION OF THIS AREA
 SHOULD USE MERCANTILE, SEE FBC TABLE 1004.1.2.
  
 2ND REVIEW, INCORRECT OCCUPANT LOAD FOR MERCANTILE, SEE
 FBC B TABLE 1004.1.2.
  
 3. 2ND REVIEW, REVISE PLAN TO CLARIFY:
  
 BUILDING CLASSIFICATION IIIB; CLARIFY
  
 2ND REVIEW, DO YOU MEAN CONSTRUCTION TYPE? REVISE PLAN
 TO TERMINOLOGY CONSISTENT WITH THE BUILDING
 CODE OR PROVIDE CLARIFICATION.
  
 4. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED
 IN THE EXIT DISCHARGE. NO LIGHTING IS SHOWN
 IN THE OUTDOOR AREA WHICH IS A PART OF THE EXIT
 DISCHARGE.
  
 2ND REVIEW, RESPONSE LETTER STATES TO SEE A2. THIS IS
 THE DEMO PAGE. SHEET E2 HAS SOME LIGHTING
 ADDED BUT NOT IN ALL OUTDOOR AREAS.
  
 5. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FOR COMPONENTS AND CLADDING, FBC 1609.
  
 2ND REVIEW, DRAWING SHEETS ARE ILLEGIBLE. LOOSE SHEETS
 WERE ALSO PROVIDED. IT APPEARS THAT THE
 NOAS WERE NOT PROPERLY BOUND. ONLY ONE PRODUCT APPROVAL
 WAS PROVIDED (GLAZED DOOR). ANY PRODUCT
 APPROVALS NOT SUBMITTED PRIOR TO PERMIT ISSUANCE WILL
 BE REQUIRED TO BE SUBMITTED AS A REVISION,
 WITH FEES.
  
 6. FBC 1011.1, THE EXIT DISCHARGE WHICH GOES THROUGH
 THE OUTDOOR FENCED PLAY AREAS IS NOT READILY
 APPARENT. IT APPEARS THAT EXIT SIGNS ARE REQUIRED IN
 THIS AREA, REVISE PLAN.
  
 2ND REVIEW, NOT ADDRESSED. PLAY AREAS 1, 2, 3 DO NOT
 PROVIDE A CLEAR PATH TO EXIT. IF THE
 OCCUPANT LEAVES THE BUILDING AND TURNS LEFT, THEY DEAD
 END. IF THEY TAKE GATE INTO PLAY AREA 3,
 THEY ARE ALSO REQUIRED TO BACKTRACK. IT IS NOT CLEAR
 HOW AN OCCUPANT SHOULD KNOW THAT THEY NEED TO
 EGRESS THROUGH DOG PLAY AREAS 1 OR 2 TO GET TO THE
 PUBLIC WAY. A CLEAR PATH TO THE PUBLIC WAY IS
 NOT PROVIDED, REVISE.
  
 EXPLAIN RATIONALE OF FORCING OCCUPANTS TO TRAVEL
 THROUGH ANIMAL AREAS TO EXIT. IT APPEARS THAT A
 SAFER MEANS OF EGRESS SHOULD BE PROVIDED.
  
 7. REVISE PLAN TO SHOW EXIT DISCHARGE (PATH OF EXIT TO
 THE PUBLIC WAY), FOR THE REAR EXIT,
 INCLUDING THE MEANS OF EGRESS ILLUMINATION FBC 1008.
  
 2ND REVIEW, NOT ADDRESSED.
  
 8. OK
  
 9-10. OK
  
 11. PROVIDE A DETAIL FOR THE CHECK OUT COUNTER, FBC
 ACCESSIBILITY 904.
  
 2ND REVIEW, THE DETAIL SHOWS THE COUNTER TOP AT 3', A
 SECOND COUNTER AT 3'6. SEE FBC A 904.
  
 12. REVISE PLAN TO SHOW COMPLIANCE WITH ACCESSIBLE
 ROUTE, FBC ACCESSIBILITY 202.4, 206.2.
 INFORMATION REGARDING THE ENTRY DOOR AND PARKING
 LOCATION WAS NOT PROVIDED; DOES THE ROUTE COMPLY
 WITH FBC A 303?
  
 13. SEE IMPACT FEE REVIEW.
  
 NEW COMMENT:
  
 14. OFFICE DOOR LACKS MANEUVERING CLEARANCE, PULL SIDE,
 FBC ACCESSIBILITY 404.2.4.1.
  
 15. PLAN PAGES ARE NUMBERED
  
 CVR OF 10
 A-0 OF 9
 ETC
  
 IT IS NOT CLEAR WHETHER THERE SHOULD BE 9 OR 10 PAGES.
 REVISE TO BE CONSISTENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 12:43 Rev Time 0.00
Received By shill Date 2016-11-29 Time 12:43 Sent To  
Notes
2016-11-29 12:43:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC EXISTING BUILDING
 CHAPTER 10.
  
 2. OCCUPANT LOAD FOR A SMALL PORTION OF THE BUILDING
 HAS BEEN DETERMINED. PROVIDE OCCUPANT LOAD FOR THE
 REMAINDER OF THE BUILDING (6,885 SF). SEE FBC 1004.1.2,
 PROPOSE AN OCCUPANT LOAD WHICH MOST CLOSELY RESEMBLES
 THE USE OF THE SPACE.
  
 3. OCCUPANT LOAD WAS PROVIDED USING 100 SF PER PERSON,
 BUT IT APPEARS THAT A PORTION OF THIS AREA SHOULD USE
 MERCANTILE, SEE FBC TABLE 1004.1.2.
  
 3. REVISE PLAN TO CLARIFY:
 IN THE TABLE ASCE7 10:
 OCCUPANCY TYPE IIIB, CLARIFY
 BUILDING CLASSIFICATION IIIB; CLARIFY
  
 TYPE OF CONSTRUCTION; SEE FBC CHAPTER 6. PLAN STATES
 UNPROTECTED (NOT SPRNKLERED). THIS IS NOT A BUILDING
 TYPE.
  
 4. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED
 IN THE EXIT DISCHARGE. NO LIGHTING IS SHOWN IN THE
 OUTDOOR AREA WHICH IS A PART OF THE EXIT DISCHARGE.
  
 5. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FOR COMPONENTS AND CLADDING, FBC 1609.
  
 6. FBC 1011.1, THE EXIT DISCHARGE WHICH GOES THROUGH
 THE OUTDOOR FENCED PLAY AREAS IS NOT READILY APPARENT.
 IT APPEARS THAT EXIT SIGNS ARE REQUIRED IN THIS AREA,
 REVISE PLAN.
  
 7. REVISE PLAN TO SHOW EXIT DISCHARGE (PATH OF EXIT TO
 THE PUBLIC WAY), FOR THE REAR EXIT, INCLUDING THE MEANS
 OF EGRESS ILLUMINATION FBC 1008.
  
 8. A2 HAS CONFLICATING NOTES REGARDING DOOR HARDWARE.
 ONE STATES THAT DOORS SHOULD HAVE PANIC DEVICES,
 ANOTHER SPECS LEVERS, FBC 107.
  
 9. SEE PLUMBING COMMENTS REGARDING ACCESSIBLITY; ALL
 ARE APPLICABLE FOR BUILDING REVIEW.
  
 10. A4 HAS A FIRE ALARM LEGEND, FIRE ALARM FIXTURES NOT
 SHOWN, FBC 107.
  
 11. PROVIDE A DETAIL FOR THE CHECK OUT COUNTER, FBC
 ACCESSIBILITY 904.
  
 12. REVISE PLAN TO SHOW COMPLIANCE WITH ACCESSIBLE
 ROUTE, FBC ACCESSIBILITY 202.4, 206.2. INFORMATION
 REGARDING THE ENTRY DOOR AND PARKING LOCATION WAS NOT
 PROVIDED; DOES THE ROUTE COMPLY WITH FBC A 303?
  
 13. SEE IMPACT FEE REVIEW.
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2017-04-05 Cont ID  
Sent By vperez Date 2017-04-05 Time 12:09 Rev Time 0.00
Received By vperez Date 2017-04-05 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2017-03-06 Cont ID  
Sent By vperez Date 2017-03-06 Time 09:19 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 09:19 Sent To Z
Notes
2017-03-06 09:19:55ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL APPROVAL
  
 V PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 13:30 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 13:30 Sent To  
Notes
2017-02-27 13:30:59ADDRESS MECHANICAL COMMENTS FOR AN ELECTRICAL APPROVAL
  
 V PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-26 Cont ID  
Sent By vperez Date 2017-01-26 Time 06:37 Rev Time 0.00
Received By vperez Date 2017-01-26 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-01-06 Cont ID  
Sent By vperez Date 2017-01-06 Time 09:50 Rev Time 0.00
Received By vperez Date 2017-01-06 Time 09:41 Sent To  
Notes
2017-01-06 09:52:522ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS NOT ADDRESSED FROM INITIAL REVIEW:
  
 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND
 POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY
 ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT
 EXCEEDED AMPS PER SIZE OF MAINS.
 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION
 CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF
 AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR
 AREAS.
  
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-12 Cont ID  
Sent By vperez Date 2016-11-12 Time 16:20 Rev Time 0.00
Received By vperez Date 2016-11-12 Time 16:20 Sent To  
Notes
2016-11-12 16:21:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
 1. PLEASE PROVIDE AN ACCURATE ONE-LINE RISER THAT
 EXISTING AS CONDUCTORS SIZE AT 1/0 IS UNDERSIZED FOR A
 200A MAIN. FBC 107.3.5
 2. DELETE RESIDENTIAL CODE NOTES FROM THE ELECTRICAL
 NOTES, ONLY PROVIDE WHAT IS APPLICABLE FOR THIS
 PROJECT. FBC 107.3.5
 3. CLARIFY HEX NOTES TO FLOOR PLAN. NOT SHOWN.
 4. SHOW A COMPLETE PANEL BOARD SCHEDULE NOT JUST
 ADDITIONAL AS SHOWN. THERE ARE NEW POWER AND LIGHTING
 OUTLETS SHOWN. NEW EXHAUST FANS, NEW A/H AND A/C MUST
 BE ACCOUNTED FOR.
 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND
 POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY
 ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT
 EXCEEDED AMPS PER SIZE OF MAINS.
 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION
 CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF
 AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR
 AREAS.
 7. NEW A/C EQUIPMENT MUST PROVIDE A W/P GFCI RECEPTACLE
 WITHIN 25FT OF UNIT FOR SERVICE. NEC 210.63. SHOW A
 DISCONNECT FOR A/C UNIT AND A/H UNIT INSIDE.
 8. LABEL ON FLOOR PLAN WHAT IS NEW OR EXISTING FOR A
 COMPLETE REVIEW.
 9. EM LIGHTING TO BE PROVIDED TO NEW BATHROOM AREA.
 10. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM
 TO INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; SEE VERBIAGE IN CODE.
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 17:09 Rev Time 0.00
Received By shill Date 2016-11-29 Time 17:09 Sent To  
Notes
2016-11-29 17:09:32CONFIRMED W/MG THAT REVIEW IS NOT REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-02-24 Cont ID  
Sent By scaldero Date 2017-02-24 Time 13:00 Rev Time 0.00
Received By scaldero Date 2017-02-24 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By pleduc Date 2017-01-19 Time   Rev Time 0.00
Received By pleduc Date 2017-01-19 Time 12:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-01-03 Cont ID  
Sent By pleduc Date 2017-01-03 Time   Rev Time 0.00
Received By pleduc Date 2016-12-30 Time 09:38 Sent To  
Notes
2016-12-30 10:32:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) PREVIOUS COMMNET 1) - NOT COMPLIED - SHEET A 4 -
 EXIT SIGNS ARE INDICATED AT DOORS LEADING TO THE
 OUTSIDE PLAY AREA; HOWEVER, THERE ARE SEVERAL GATES AND
 PLAY AREAS THAT MUST BE NAVIGATED UNTIL THE EXIT
 DISCHAGE IS REACHED. THE EXIT IS NOT REACHED UNTIL THE
 POINT OF PUBLIC WAY.
  
 8.1.2.4* EXIT TRAVEL DISTANCES.
 8.1.2.4.1 IN ANIMAL HOUSING FACILITIES NOT SPRINKLERED
 IN ACCORDANCE WITH SECTION 9.2, EXIT TRAVEL DISTANCE
 SHALL NOT EXCEED 75 FT (23 M) FROM ANY POINT IN THE
 FACILITY.
  
 8.1.2.1 NUMBER OF MEANS OF EGRESS.
 8.1.2.1.1 TWO MEANS OF EGRESS FOR HUMAN AND ANIMAL
 OCCUPANTS, AS A MINIMUM, SHALL BE PROVIDED IN EVERY
 FACILITY, SECTION,AND AREA WHERE SIZE, OCCUPANCY, AND
 ARRANGEMENT ENDANGER OCCUPANTS ATTEMPTING TO USE A
 SINGLE MEANS OF EGRESS
 THAT IS BLOCKED BY FIRE OR SMOKE.
 8.1.2.1.2 WHERE TWO MEANS OF EGRESS ARE REQUIRED, THEY
 SHALL BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT BOTH
 MIGHT BE RENDERED IMPASSABLE BY THE SAME EMERGENCY
 CONDITION.
  
 11.2 MEANS OF EGRESS REQUIREMENTS.
 11.2.1 GENERAL. EACH REQUIRED MEANS OF EGRESS SHALL BE
 IN ACCORDANCE WITH THE APPLICABLE PORTIONS OF CHAPTER
 8.
 11.2.2 MEANS OF EGRESS COMPONENTS.
 11.2.2.1 GENERAL. COMPONENTS OF MEANS OF EGRESS SHALL
 BE LIMITED TO THE TYPES DESCRIBED IN NFPA 101, LIFE
 SAFETY CODE, CHAPTER 7; OR NFPA 5000, BUILDING
 CONSTRUCTION AND SAFETY CODE, CHAPTER 11; CHAPTER 8 OF
 THIS STANDARD; AND AS MODIFIED IN THIS SUBSECTION.
  
 NFPA 101, CHAPTER 3, DEFINITIONS.
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
  
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 3.3.218 PUBLIC WAY. A STREET, ALLEY, OR OTHER SIMILAR
 PARCEL OF LAND ESSENTIALLY OPEN TO THE OUTSIDE AIR
 DEEDED, DEDICATED, OR OTHERWISE PERMANENTLY
 APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND HAVING A
 CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FT (3050
 MM).
  
  
 THE PROPOSED TRAVEL DISTANCES INDICATED ON A 4 ARE
 NONCOMPLIANT AND NOT APPROVED. YOUR PROPOSED EXITS ARE
 EXIT ACCESSES WITH YOUR EXIT ACTUALLY BEING AT THE END
 OF YOUR OCUTDOOR PALY AREA. PLEASE CORRECT.
  
  
 2) PREVIOUS COMMENT 2) - COMPLIED.
  
  
 3) PREVIOUS COMMENT 3) - COMPLIED.
  
  
 4) PREVIOUS COMMENT 4) - NOT COMPLIED - SHEET A 4 -
 THERE IS ONE EXIT INDICATED FROM THE MERCANTILE AREA;
 HOWEVER, PER NFPA 150, 8.1.2.1 NUMBER OF MEANS OF
 EGRESS.
 8.1.2.1.1 TWO MEANS OF EGRESS FOR HUMAN AND ANIMAL
 OCCUPANTS, AS A MINIMUM, SHALL BE PROVIDED IN EVERY
 FACILITY, SECTION, AND AREA WHERE SIZE, OCCUPANCY, AND
 ARRANGEMENT ENDANGER OCCUPANTS ATTEMPTING TO USE A
 SINGLE MEANS OF EGRESS
 THAT IS BLOCKED BY FIRE OR SMOKE.
  
 SHOULD A FIRE OCCUR IN THE AREA OF THE GROOMING THE
 MAIN EXIT COULD BE INACCESSIBLE. A SECOND EXIT SHALL BE
 IDENTIFIED AND PROVIDED FROM THIS AREA.
  
  
  
 ADDITIONAL COMMENTS:
  
  
  
 5) SHEET A 2 & A 4 - AN EXIT ACCESS IS INDICATED
 PASSING THROUGH A DOOR LEADING INTO INDOOR INDOOR PLAY
 AREA # 1 THAT THEN LEADS TO THE EXIT IN THE CORNER.
  
 THE DOOR LEADING TO INDOOR PLAY AREA # 1 IS NOT
 INDICATED ON THE DOOR SCHEDULE AND DOES NOT SHOW
 COMPLIANT EXIT HARDWARE.
  
 PLEASE CORRECT.
  
  
  
 6) SHEET A 2 - DOORS INDICATED AS E ARE EXIT DOORS AND
 ARE NOT SHOWING COMPLIANT EXIT HARDWARE ON THE DOOR
 SCHEDULE, INCLUDING LOCKING AND LATCHING DEVICES.
  
 PLEASE CORRECT.
  
  
  
 7) SHEET A 4 - ONE EXIT IS INDICATED FROM THE OVERNIGHT
 DOG PLAY AREA.
  
 8.1.2.1.1 TWO MEANS OF EGRESS FOR HUMAN AND ANIMAL
 OCCUPANTS, AS A MINIMUM, SHALL BE PROVIDED IN EVERY
 FACILITY, SECTION, AND AREA WHERE SIZE, OCCUPANCY, AND
 ARRANGEMENT ENDANGER OCCUPANTS ATTEMPTING TO USE A
 SINGLE MEANS OF EGRESS
 THAT IS BLOCKED BY FIRE OR SMOKE.
  
 PLEASE CORRECT.
  
  
  
 8) SHEET A 2 & A 4 - EXIT ACCESS IS BEING SHOWN FROM 2
 DOORS LEADING TO THE OUTDOOR PLAY AREA AND GATE
 SYSTEMS. THESE ARE EXIT ACCESS AND NOT EXITS. ONCE INTO
 THE AREA THERE IS NO INDICATIONS SHOWING THE WAY
 LEADING TO AN EXIT. HOW WILL SOMEONE KNOW WHERE TO GO
 ONCE THEY LEAVE THE DOORS.
  
 PLEASE PROVIDE CODE COMPLIANT EXIT SIGNAGE.
  
  
  
 9) SHEET A 2 & A 4 - THE GATES WITHIN THE OUTDOOR PLAY
 AREA ARE NOT INDICATED BY DETAIL ON THE DOOR SCHEDULE
 OR ANY PLAN SHEET. THESE GATES ARE PART OF THE EXIT
 ACCESS AND SHALL COMPLY WITH CODE.
  
 PLEASE PROVIDE THE SEPCIFIC DETAIL REGARDING THE GATES,
 INCLUDING LOCKING AND LATCHING DEVICES.
  
  
  
 10) SHEET E 1 - THERE ARE NO EXIT PATH ILLUMINATION AT
 THE OUTDOOR AREAS.
  
 NFPA 101, CHAPTER 7, MEANS OF EGRESS
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
  
 PLEASE PROVIDE ILLUMINATION AS REQUIRED.
  
  
  
 11) SHEET CVR - A BUNESS & MERCANTILE OCCUPANCY CLASS
 IS INDICATED. ON SHEET A 4 AN ASSEMBLY OCCUPANCY IS
 INDICATED.FOR THE MEANS OF EGRESS.
  
 THIS IS CONFUSING AND SHALL BE EXPLAINED AND/OR
 CORRECTED.
  
  
  
 12) SHEET CVR - UNDER THE SCOPE OF WORK # 2. - FENCE
 NEW PLAY AREA WITH 6' CHAIN LINK AND WOOD FENCE AS
 INDICATED ON PLAN. THERE IS NO INDICATION AND/OR DETAIL
 REGARDING THIS NOTE.
  
 PLEASE PROVIDE SPECIFIC DETAIL FOR THIS COMMENT
 INCLUDING EITHER AT EACH LOCATION. ENSURE THAT
 CONSIDERATION IS GIVEN TO THE WALL FINISH RATING ALONG
 THE EXIT PATH OF TRAVEL.
  
  
  
 13) THIS COMMENT IS FOR INFORMATIONAL PURPOSES.
  
 SHEET A 4 - A FIRE ALARM IS INDICATED WITH 24/7
 MONOTORING. PLEASE BE ADVISED THAT MONITORING IS NOT
 REQURED PER NFPA 105 REQUIRMENTS FOR THE SIZE OF THIS
 OCCUPANCY
  
 CHAPTER 11, CLASS 1 ANIMAL HOUSING FACILITIES
  
 11.3.1 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 11.3.1.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE
 WITH SECTION 9.3 SHALL BE REQUIRED IN ACCORDANCE WITH
 THIS SUBSECTION.
 11.3.1.1.1 IN ANIMAL HOUSING FACILITIES GREATER THAN
 3000 FT2 (280 M2) BUT NO MORE THAN 20,000 FT2 (1860
 M2), A LOCAL FIRE ALARM SYSTEM SHALL BE PROVIDED.
 11.3.1.1.2 IN ANIMAL HOUSING FACILITIES GREATER THAN
 20,000 FT2 (1860 M2), A MONITORED FIRE ALARM SYSTEM
 SHALL BE PROVIDED.
  
 9.3 FIRE ALARM SYSTEMS.
 9.3.1 WHERE FIRE ALARM SYSTEMS ARE REQUIRED BY THIS
 STANDARD THROUGHOUT THE ANIMAL HOUSING FACILITY, ALARM
 SYSTEMS SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM CODE, AND THE REQUIREMENTS OF THIS SECTION.
 9.3.2 THE ALARM SYSTEM SHALL SOUND AN AUDIBLE AND
 VISUAL EXTERIOR ALARM FOR PURPOSES OF INITIATING
 EMERGENCY ACTION.
 9.3.2.1 MODIFICATIONS TO 9.3.2 SHALL BE PERMITTED TO
 ACCOMMODATE THE NEEDS OF THE ANIMAL OCCUPANTS WITH
 APPROVAL OF THE AHJ.
  
 YOU HAVE THE OPTION OF PROVIDING A LOCAL FIRE ALARM
 SYSTEM.
  
  
  
 14) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 15) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By scaldero Date 2016-11-07 Time 11:57 Rev Time 0.00
Received By scaldero Date 2016-11-07 Time 11:27 Sent To  
Notes
2016-11-07 11:57:46PERMIT #16110180
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SHEET A-4: YOU SHOW A TRAVEL DISTANCE OF 94 FEET.
 THIS IS A NON-SPRINKLERED BUILDING. PER NFPA 150:
 8.1.2.4* EXIT TRAVEL DISTANCES.
 8.1.2.4.1 IN ANIMAL HOUSING FACILITIES NOT SPRINKLERED
 IN ACCORDANCE WITH SECTION 9.2, EXIT TRAVEL DISTANCE
 SHALL NOT EXCEED 75 FT (23 M) FROM ANY POINT IN THE
 FACILITY.
  
 2) PLEASE INDICATE WHAT CATEGORY OF ANIMALS WILL BE
 HOUSED IN THIS FACILITY. (CATEGORY A, CATEGORY B, OR
 BOTH).
 PLEASE SEE NFPA 150: 9.8 SPECIAL REQUIREMENTS FOR
 CATEGORY A ANIMALS.
  
 3) SHEET A-4: NOTE INDICATES THAT ONLY ONE (1) FIRE
 EXTINGUISHER WILL BE PROVIDED. FIRE EXTINGUISHERS WILL
 NEED TO BE PROVIDED PER NFPA 1, NFPA 101, AND NFPA 150.
  
 4) SHEET A-4: LIFE SAFETY GENERAL NOTES INDICATE THAT
 EGRESS REQUIREMENTS ARE IN COMPLIANCE WITH NFPA 101,
 CHAPTERS 7 AND 12. PLEASE REVIEW NFPA 150 FOR
 ADDITIONAL EGRESS REQUIREMENTS, IF ANY, AS NEEDED FOR
 ANIMAL CATEGORY (A AND/OR B) AND ANIMAL HOUSING CLASS
 (CLASS 1, 2, OR 3).
  
 5) ADDITIONAL COMMENTS MAY BE NEEDED UPON REVIEW OF
 RESUBMITTAL.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 16:10 Rev Time 0.00
Received By ccole Date 2017-04-05 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 16:10 Rev Time 0.00
Received By ccole Date 2017-02-28 Time 08:17 Sent To  
Notes
2017-03-01 08:20:48RESUBMITTAL GIVEN TO CCOLE PER SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 13:31 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 13:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-30 Cont ID  
Sent By lmarchan Date 2017-01-30 Time 10:34 Rev Time 0.00
Received By lmarchan Date 2017-01-17 Time 14:24 Sent To  
Notes
2017-01-17 14:25:25C09

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2016-12-20 Time 14:46 Sent To  
Notes
2016-12-21 14:47:02C07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 17:21 Rev Time 0.00
Received By shill Date 2016-12-14 Time 11:02 Sent To  
Notes
2016-12-15 11:02:50IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 17:09 Rev Time 0.00
Received By shill Date 2016-11-03 Time 10:11 Sent To  
Notes
2016-11-04 10:14:45C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 17:20 Rev Time 0.00
Received By shill Date 2016-12-15 Time 17:20 Sent To  
Notes
2016-12-15 17:21:42NO NUMBER ASSIGNED, PLANS STAMPED

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-29 Cont ID  
Sent By shill Date 2016-11-29 Time 12:43 Rev Time 0.00
Received By shill Date 2016-11-29 Time 12:43 Sent To  
Notes
2016-11-29 12:44:01IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 16:10 Rev Time 0.00
Received By ccole Date 2017-04-05 Time 16:10 Sent To  
Notes
2017-04-05 16:19:30MECHANICAL PROVISO
 4/5/2017
  
 THE PLANS HAVE BEEN APPROVED WITH EXCEPTION.
 FAILURE TO CORRECT THE LISTED DEFICIENCY IN THE PLAN
 PRIOR TO MECHANICAL INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF REINSPECTION FEES.
  
 1) THE EXHAUST FAN CAPACITIES AND EXHAUST VENTILATION
 CALCULATIONS FOR THE OVERNIGHT DOG AREA AND THE DOG
 AREA NEED TO BE CORRECTED TO MEET THE REQUIREMENTS OF
 TABLE 403.3 FBC-14 MECHANICAL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2017-03-01 Cont ID  
Sent By ccole Date 2017-03-01 Time 12:04 Rev Time 0.00
Received By ccole Date 2017-03-01 Time 10:37 Sent To  
Notes
2017-03-01 12:28:376TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 3/1/17
  
 1) THE REVISED EXHAUST VENTILATION AND AIR BALANCE
 CALCULATIONS INDICATE ERV'S ARE REQUIRED FOR AHU'S #1,
 3, 4, & 5 BECAUSE THE THE AMOUNT OF O/A REQUIRED IS
 EXCEEDING 50% OF THE DESIGN SUPPLY FAN AIRFLOW RATE-
 SEE TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE
 NOTE THAT A PRODUCT DATA SHEET HAS BEEN SUBMITTED FOR A
 LIGHT COMMERCIAL ERV HOWEVER THE UNIT(S) ARE NOT SHOWN
 ON THE PLAN. IT ALSO APPEARS THAT THE O/A REQUIRED FOR
 THE OVERNIGHT DOG AREA AT 1397 CFMS WILL FAR EXCEED THE
 COOLING CAPACITY OF THE 5-TON AHU-1 SYSTEM.
  
 2) M-2: AC SYSTEMS #1, 4 & 5 ARE NOT FUNCTIONING IN THE
 RETAIL AREA- PLEASE DESIGNATE THEIR LOCATIONS TO
 CORRELATE WITH THE PLAN.
  
 3) ADVISORY: TO AVOID ANY FURTHER PLAN REJECTIONS,
 PLEASE CONSULT WITH A LICENSED MECHANICAL ENGINEER.
 PLEASE NOTE THAT ALL OCCUPIED SPACES MUST BE PROVIDED
 WITH EITHER NATURAL OR MECHANICAL VENTILATION (SECTION
 401.2), AND ACTIVE OR SPACE HEATING SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2017-02-22 Cont ID  
Sent By ccole Date 2017-02-22 Time 11:59 Rev Time 0.00
Received By ccole Date 2017-02-22 Time 10:17 Sent To  
Notes
2017-02-22 12:36:195TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 1/22/17
  
 1) 4TH REQUEST FOR EXHAUST VENTILATION CALCULATIONS:
 THE REQUESTED EXHAUST VENTILATION CALCULATIONS FOR THE
 DOG AREA AND THE OVERNIGHT DOG PLAY AREA HAVE NOT BEEN
 PROVIDED AS REQUIRED BY TABLE 403.3. CALCULATIONS BASED
 ON THE SCALE SHOWN ON THE PLAN INDICATE 666 CFMS OF
 EXHAUST REQUIRED FOR THE DOG AREA AND 683 CFMS FOR THE
 OVERNIGHT DOG PLAY AREA. THE EF-1 FANS AT 110 CFMS
 CAPACITY ARE ONLY PROVIDING 220 CFMS OF EXHAUST AT EACH
 OF THESE ROOMS INDICATING INCREASED VENTILATION MUST BE
 PROVIDED- SEE TABLE 403.3.
  
 2) 4TH REQUEST FOR COMPLETE EXHAUST SYSTEM DRAWINGS:
 THE REQUESTED DETAILS FOR THE EXHAUST SYSTEMS IN THE
 DOG AREA AND OVERNIGHT DOG PLAY AREA HAVE NOT BEEN
 PROVIDED.
  
 2) PLEASE LABEL THE NEW EXHAUST AND SUPPLY FANS IN THE
 INDOOR DOG PLAY AREA AND PROVIDE EQUIPMENT SCHEDULES.
  
 3) REFER TO TABLE 403.3 AND PROVIDE AN O/A CALCULATION
 FOR THE INDOOR PLAY AREA AND SHOW HOW O/A WILL BE
 PROVIDED TO THE AREAS. CORRECT THE NOTE IN THE AIR
 BALANCE CALCULATION THAT STATES "NO FRESH AIR THRU
 AHU'S".
  
 4) INDICATE THE SIZES OF THE MAIN DUCT TRUNKS
 DISTRIBUTING AIR FROM AHU'S 3, 4 & 5.
  
 5) THE PLAN APPEARS TO SHOW INADEQUATE AIR DISTRIBUTION
 WILL BE PROVIDED TO THE BREATHING ZONES IN THE INDOOR
 DOG PLAY AREA BASED ON THE DUCT LAYOUT PLAN PROVIDED.
  
 6) A PRODUCT DATA SHEET FOR BROAN EXHAUST FANS HAS BEEN
 SUBMITTED WITH MODEL NUMBERS THAT DON'T MATCH THE MODEL
 NUMBERS ON THE EQUIPMENT SCHEDULES SHOWN ON THE PLANS-
 PLEASE CORRECT ONE OR THE OTHER.
  
 7) A PRODUCT DATA SHEET HAS BEEN SUBMITTED FOR A
 SHUTTER FAN BUT NO LOCATION, DETAILS, OR SCHEDULE FOR
 THE FAN ARE PROVIDED ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-02-17 Cont ID  
Sent By ccole Date 2017-02-17 Time 07:40 Rev Time 0.00
Received By ccole Date 2017-02-17 Time 07:34 Sent To  
Notes
2017-02-17 07:43:494TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 2/17/17
  
 NO CORRECTIONS TO THE PLANS OR RESPONSES TO THE 3RD
 REVIEW COMMENTS HAVE BEEN PROVIDED. I HAVE COPIED THE
 COMMENTS BELOW FOR REVIEW- PLEASE COMPLY.
  
 1) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR
 ALL SYSTEMS- TABLE 403.3
  
 2) 3RD REQUEST TO PROVIDE COMPLETE EXHAUST SYSTEM
 DRAWINGS INCLUDING THE INDOOR DOG PLAY ROOMS. THE
 DRAWINGS AND DETAILS SHALL INCLUDE THE EXHAUST DUCT
 TYPES AND SIZES, DUCT RUNS AND TERMINATION LOCATIONS.
 PLEASE NOTE THAT ENGINEERING DETAILS FOR INSTALLATION
 OF ANY ROOFTOP FANS OR TERMINATION CAPS WILL BE
 REQUIRED.
  
 3) 2ND REQUEST FOR THE ARCHITECT OF RECORD TO PROVIDE
 SHOP DRAWING APPROVAL OF THE AC CALCULATIONS.
  
 4) 2ND REQUEST FOR THE ENERGY COMPLIANCE CHECKLIST TO
 BE FILLED OUT.
  
 5) 3RD REQUEST FOR COMPLETE AIR BALANCE CALCULATIONS.
 PLEASE NOTE THE CALCULATION M-1 DOES NOT INCLUDE THE
 O/A AIR SUPPLIED BY AHU-3 AND THE REQUIRED EXHAUST
 SYSTEMS IN THE INDOOR DOG AREAS.
  
 6) PROVIDE THE DUCT LAYOUT PLAN FOR AHU-3.
  
 7) THE CU TIE DOWN DETAIL IS INCOMPLETE. PLEASE PROVIDE
 THE GAUGE OF THE STEEL STRAP OR MANUFACTURER'S
 SPECIFICATIONS, AND HOW THE CLIP WILL BE FASTENED TO
 THE CONDENSER JACKET.
  
 8) 2ND REQUEST TO SHOW THE LOCATION OF THE DS DETECTORS
 IN THE RETURN AIR SYSTEMS OF THE AHU'S.
  
 9) PLEASE CLARFY WHAT TYPE OF AUTOMATIC O/A DAMPERS ARE
 PROPOSED FOR AHU'S 1 & 2. ARE THESE MOTORIZED DAMPERS?
 IF SO, PLEASE SEE SECTION C402.4.5.2 FBC-14 ENERGY
 CONSERVSATION AND PROVIDE MANUFACTURER'S
 SPECIFICATIONS.
  
 10) REFER TO SECTION 401.4 AND PROVIDE THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO
 EXHAUST OUTLETS OR OTHER CONTAMINANT SOURCES, AND
 VEHICULAR DRIVE AREAS SUCH AS DRIVEWAYS AND PARKING
 LOTS
  
 11) INDICATE HOW THE O/A OPENINGS WILL BE PROTECTED IN
 COMPLIANCE WITH SECTION 401.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-01-27 Cont ID  
Sent By ccole Date 2017-01-27 Time 11:11 Rev Time 0.00
Received By ccole Date 2017-01-27 Time 09:58 Sent To  
Notes
2017-01-27 11:16:343RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 1/27/17
  
 1) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR
 ALL SYSTEMS- TABLE 403.3
  
 2) 3RD REQUEST TO PROVIDE COMPLETE EXHAUST SYSTEM
 DRAWINGS INCLUDING THE INDOOR DOG PLAY ROOMS. THE
 DRAWINGS AND DETAILS SHALL INCLUDE THE EXHAUST DUCT
 TYPES AND SIZES, DUCT RUNS AND TERMINATION LOCATIONS.
 PLEASE NOTE THAT ENGINEERING DETAILS FOR INSTALLATION
 OF ANY ROOFTOP FANS OR TERMINATION CAPS WILL BE
 REQUIRED.
  
 3) 2ND REQUEST FOR THE ARCHITECT OF RECORD TO PROVIDE
 SHOP DRAWING APPROVAL OF THE AC CALCULATIONS.
  
 4) 2ND REQUEST FOR THE ENERGY COMPLIANCE CHECKLIST TO
 BE FILLED OUT.
  
 5) 3RD REQUEST FOR COMPLETE AIR BALANCE CALCULATIONS.
 PLEASE NOTE THE CALCULATION M-1 DOES NOT INCLUDE THE
 O/A AIR SUPPLIED BY AHU-3 AND THE REQUIRED EXHAUST
 SYSTEMS IN THE INDOOR DOG AREAS.
  
 6) PROVIDE THE DUCT LAYOUT PLAN FOR AHU-3.
  
 7) THE CU TIE DOWN DETAIL IS INCOMPLETE. PLEASE PROVIDE
 THE GAUGE OF THE STEEL STRAP OR MANUFACTURER'S
 SPECIFICATIONS, AND HOW THE CLIP WILL BE FASTENED TO
 THE CONDENSER JACKET.
  
 8) 2ND REQUEST TO SHOW THE LOCATION OF THE DS DETECTORS
 IN THE RETURN AIR SYSTEMS OF THE AHU'S.
  
 9) PLEASE CLARFY WHAT TYPE OF AUTOMATIC O/A DAMPERS ARE
 PROPOSED FOR AHU'S 1 & 2. ARE THESE MOTORIZED DAMPERS?
 IF SO, PLEASE SEE SECTION C402.4.5.2 FBC-14 ENERGY
 CONSERVSATION AND PROVIDE MANUFACTURER'S
 SPECIFICATIONS.
  
 10) REFER TO SECTION 401.4 AND PROVIDE THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO
 EXHAUST OUTLETS OR OTHER CONTAMINANT SOURCES, AND
 VEHICULAR DRIVE AREAS SUCH AS DRIVEWAYS AND PARKING
 LOTS
  
 11) INDICATE HOW THE O/A OPENINGS WILL BE PROTECTED IN
 COMPLIANCE WITH SECTION 401.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-27 Cont ID  
Sent By ccole Date 2016-12-27 Time 08:00 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 07:09 Sent To  
Notes
2016-12-27 08:49:022ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 12/27/16
  
 1) THE REQUESTED EXHAUST FAN SCHEDULES AND EXHAUST
 VENTILATION CALCULATIONS WERE NOT PROVIDED.
  
 2) THE REQUESTED EXHAUST DUCT DETAILS- TYPES AND SIZES
 OF DUCTS AND TERMINATION LOCATIONS WERE NOT PROVIDED.
  
 3) THE REQUESTED AC CALCULATIONS MUST BEAR TRHE SHOP
 DRAWING APPROVAL STAMP AND SIGNATURE OF THE DESIGN
 PROFESSIONAL OF RECORD.
  
 4) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS
 SUBMITTED WITHOUT THE PRINTED OR SIGNED NAMES OF THE
 DESIGN PROFESSIONALS OR THE OWNER/AGENT- SEE PAGE 3.
  
 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS
 SUBMITTED WITHOUT THE MANDATORY REQUIREMENTS CHECKLIST
 COMPLETED- SEE PAGE 8.
  
 6) THE ENERGY COMPLIANCE SUBMITTAL INCORRECTLY LISTS
 TWO 5-TON AC SYSTEMS AT 16 SEER, HOWEVER ONLY THE NEW
 SYSTEM IS 16 SEER.
  
 7) THE REQUESTED AIR BALANCE CALCULATION WAS NOT
 PROVIDED.
  
 8) THE REQUESTED WIND LOAD ENGINEERING AND STRUCTURAL
 DETAILS FOR THE CU AND CU PAD WERE NOT PROVIDED.
  
 9) THE EQUIPMENT SCHEDULE FOR THE NEW 5-TON AC
 INCORRECTLY LISTS THE WEIGHT AT 9.7 LBS.
  
 10) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF THE NEW AND EXISTING 5-TON AC SYSTEMS,
 UNLESS MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS
 ARE INCAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR- SECTION 606.2.1.
  
 11) PROVIDE AN AIR DEVICE SCHEDULE.
  
 12) NEW DRYER: REFER TO SECTION 504 AND PROVIDE A)
 MANFACTURER'S SPECIFICATIONS FOR THE DRYER. B) EXHAUST
 DUCT DETAILS INCLUDING THE DUCT RUN AND DUCT
 TERMINATION. C) MAKEUP AIR DETAILS- SEE SECTION 504.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 07:33 Rev Time 0.00
Received By ccole Date 2016-11-10 Time 17:02 Sent To  
Notes
2016-11-14 08:51:351ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16110180
 11/14/16
  
 THE MECHANICAL PLANS DESIGNED BY SANDRA PUERTA
 ARCHITECT ARE DEFICIENT AND NOT IN COMPLIANCE WITH
 CURRENT CODES AND STANDARDS.
  
 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR THE NEW
 AND EXISTING AC SYSTEMS, AND THE VARIOUS EXHAUST FANS
 SHOWN IN THE DRAWINGS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR, AND THE REQUIRED AND
 PROVIDED CFM'S OF EXHAUST AIR.
  
 4) PROVIDE AN AIR BALANCE CALCULATION.
  
 5) THE PROJECT IS DEFINED AS A CHANGE OF OCCUPANCY PER
 SECTION 202 FBC-14 EXISTING BUILDING CODE. REFER TO
 SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND SUBMIT
 DOCUMENTATION OF COMPLIANCE. SEE SECTION 401.2 FOR
 COMPLIANCE PATH OPTIONS.
  
 6) PROVIDE AN AIR DEVICE SCHEDULE ON THE PLAN,.
  
 7) INDICATE THE SIZES OF THE SUPPLY AND RETURN DUCTS,
 DIFFUSERS, DISTRIBUTION BOXES, AND RETURN GRILLS SHOWN
 ON THE LAYOUT DRAWING, AND SHOW CFM AMOUNTS AT EACH
 SUPPLY DIFFUSER AND RETURN GRILL.
  
 8) PROVIDE A COMPLETE DUCT LAYOUT FOR AHU-2 & AHU-3
  
 9) INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO THE
 ROOMS AND SPACES, AND REFER TO SECTION C403.2.4.4 FOR
 SHUTOFF DAMPER REQUIREMENTS.
  
 10) REFER TO TABLE 403.3 FOOTNOTE B: AIR FROM THE DOG
 GROOMING ROOM IS NOT PERMITTED TO RECIRCULATE INTO THE
 ADJACENT RETAIL AREA.
  
 11) REFER TO TABLE 403.3 FOOTNOTE B: HOW IS AIR BEING
 RETURNED TO AHU-3? NO RETURN DUCTS OR GRILLS ARE SHOWN.
 PLEASE NOTE THAT AHU-1 MUST BE A COMPLETELY SEALED UNIT
 WITH A DUCTED RETURN BECAUSE IT SHARES THE SAME
 MECHANICAL CLOSET WITH AHU-2. THE AIR FROM THESE TWO
 SYSTEMS CANNOT COMMUNICATE.
  
 12) PROVIDE EXHAUST VENTILATION DETAILS: SHOW THE TYPES
 AND SIZES OF EXHAUST DUCTS, THE DUCT RUNS, AND THE
 TERMINATION LOCATIONS- SEE SECTION 501.2- 501.3.1.1.
  
 13) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ACCU #3- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2017-02-15 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-01-28 Cont ID  
Sent By tklarge Date 2017-01-28 Time 07:30 Rev Time 0.00
Received By tklarge Date 2017-01-28 Time 07:04 Sent To  
Notes
2017-01-28 06:09:501) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014
 FBC-ACCESS. SECS.212, 606 AND 305. SHOW THE HEIGHT OF
 THE TOP OF THE COUNTERTOP/SINK FROM THE FINISH FLOOR.
 2) THE WALL FINISH IN THE NEW TOILET ROMM SHALL COMPLY
 WITH 2014 FBC SEC. 1210. SHT.THE FINISH SCHEDULE ON
 SHT.A-2 SHOWS THE WALLS AS PAINT. CLARIFY.
 3) THE SANITARY RISER DOES NOT COMPLY WITH THE
 FBC-PLUMBING CODE.
 A) THE WASHING MACHINE SHALL BE INSTALLED ON A MINIMUM
 3 INCH STACK. FPC SEC.406.2.
 B) THE DOG TUBS ARE NOT VENTED. FPC 901.2.1.
 C) THE DISHWASHER SHALL DRAIN INDIRECTLY PER FPC
 SEC.802.1.6.
 D) THE DRINKING FOUNTAIN IS NOT VENTED. FPC 901.2.1.
 4) SHT. A-1 ( DEMO PLAN) IS MISSING. IT IS LISTED ON
 THE COVER PAGE. CLARIFY.
 5) HOT WATER IS REQUIRED TO THE WASHING MACHINE. FPC
 SEC.607.1.
 6) THE ENTIRE WATER SYSTEM ( HOT & COLD ) IS SIZED IN
 1/2 INCH PIPE. REFER TO FPC SEC.604.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 13:37 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 13:37 Sent To  
Notes
2017-01-12 14:25:162ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW HEIGHT OF ACCESSIBLE SINK IN BREAK ROOM TO
 COMPLY WITH FBC ACC 606.3 - 306
  
 2. SANITARY RISER DIAGRAM DOES NOT COMPLY WITH THE
 CODE. PER WPB AMEND TO FBC 107.2.1
  
 A) THE MOP SINK IS NOT VENTED. FBC PL 901.2.1
 B) ACCESSIBLE SINK IN BREAK ROOM IS NOT VENTED. FBC PL
 901.2.1
 C) DOG TUBS NOT VENTED. FBC PL 901.2.1
 D) WASHING MACHINE IS NOT VENTED. FBC PL 901.2.1
 E) THE WATER FOUNTAIN IS NOT SHOWN ON RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.2.1
 F)DRAIN LINE FOR WASHING MACHINE SHALL BE A MIN OF 3".
 PER FBC PL 406.2
 G) EXISTING WASHER IS NOT SHOWN ON DEMO PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 H) THE BUILDING DRAIN SERVING THE WASHING MACHINE, DOG
 TUBS, BREAKROOM SINKS AND MOP SINK SHALL CONNECT DOWN
 STREAM OF BATHROOM GROUP IT CAN'T CONNECT BETWEEN THE
 TOILET AND LAV. FBC PL 912.1
  
 3. THE WATER RISER DIAGRAM IS UNCLEAR PLEASE ENLARGE
 AND MAKE IT CLEAR TO READ. PER WPB AMEND TO FBC 107
 107.2.1.4
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-27 Cont ID  
Sent By tklarge Date 2016-11-27 Time 05:05 Rev Time 0.00
Received By tklarge Date 2016-11-27 Time 03:24 Sent To  
Notes
2016-11-27 04:50:321) SHT. CVR OF 10 - THE OCCUPANCY CLASSIFICATION IS
 LISTED AS "IIIB". THIS IS A MIXED OCCUPANCY. LIST ALL
 APPLICABLE OCCUPANCY TYPES AND THE CORRESPONDING
 OCCUPANT LOAD FOR EACH AREA IN ACCORDANCE WITH 2014 FBC
 CHAPTER 3 AND SEC.1004.
 2) THIS IS A CHANGE OF OCCUPANCY AND SHALL COMPLY WITH
 THE PLUMBING FIXTURE REQUIREMENTS OF THE 2014
 FBC-PLUMBING, LIST THE PREVIOUS OCCUPANCY ON THE PLANS.
 TABLE 403.1.
 3) DRINKING FOUNTAINS ARE REQUIRED PER 2014
 FBC-PLUMBING TABLE 403.1. A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED PER TABLE 403.1 FOOTNOTE (E) AND
 2014 FBC-ACCESS. SEC.211.2. SUBMIT ELEVATION DETAILS.
 4) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014
 FBC-ACCESS. SECS.212, 606 AND 305. SHOW THE HEIGHT OF
 THE TOP OF THE COUNTERTOP FROM THE FINISH FLOOR AND THE
 REQUIRED CLEAR FLOOR SPACE FOR THE SINK.
 5) A SERVICE SINK IS REQUIRED PER 2014 FBC-PLUMBING
 TABLE 403.2.
 6) SEPARATE FACILITIES ARE REQUIRED FOR MALES AND
 FEMALES PER TABLE 403.1 OF 2014 FBC-PLUMBING.
 7) SHT. A-3 DETAIL 4 (A) - THE PLACEMENT OF THE GRAB
 BAR ON THE REAR WALL SHALL COMPLY WITH 2014 FBC-
 ACCESS. SEC. 604.5.2 & FIGURE 504.5.2.
 8) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE2014 FBC-ACCESS. SEC. 609.4.
 9) SHT.A-3 - DETAIL 5 - SHOWS THE TOP OF THE LAVATORY
 AT 40 INCHES ABOVE THE FINISH FLOOR AND 34 INCHES IS
 SHOWN TO THE BACKSPLAS. THE MAXIMUM HEIGHT OF THE
 LAVATORY SHALL COMPLY WITH 2014 FBC- ACCESS. SEC.606.3.
 10) THE FLUSH HANDLE FOR THE WATER CLOSET SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET.
 FBC-ACCESS. SEC.604.6.
 11) SHT.A-3 DETAIL 6 REFERENCES THE 2010 FBC. THIS
 SCOPE OF WORK SHALL COMPLY WITH 2014 FBC.
 12) THE WALL FINISH IN THE NEW TOILET ROMM SHALL COMPLY
 WITH 2014 FBC SEC. 1210.
 13) SUBMIT A SANITARY AND WATER RISER FOR REVIEW THAT
 SHOWS ALL PLUMBING FIXTURES (DRINKING FOUNTAIS, MOP
 SINK, BREAK ROOM SINK, WASHER, DOG WASH TUBS, WATER
 HEATER).
 14) WILL THERE BE ANY HOSE BIBBS INSTALLED FOR WASHING
 DOWN THE DOG AREAS? IF SO, SHOW THEM ON THE WATER
 RISER. EACH HOSE BIBB SHALL BE EQUIPPED WITH SEPARATE
 SHUTOFF VALVE. FPC SEC.606.2.
 15) HOT WATER IS REQUIRED TO THE NEW MOP SINK. 2014 FPC
 SEC.607.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2017-03-07 Time   Rev Time 0.00
Received By   Date 2017-03-07 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-01-30 Time   Rev Time 0.00
Received By awooten Date 2017-01-30 Time 10:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-01-04 Time   Rev Time 0.00
Received By awooten Date 2017-01-04 Time 14:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-22 Cont ID  
Sent By AW Date 2016-11-22 Time 08:39 Rev Time 0.00
Received By awooten Date 2016-11-22 Time 08:38 Sent To  
Notes
2016-11-22 08:39:01******ZONING********
  
 BUSINESS TAX LICENSE NEEDED.