Plan Review Details - Permit 16110067
Plan Review Stops For Permit 16110067
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-13 Cont ID  
Sent By shill Date 2017-02-13 Time 16:07 Rev Time 0.00
Received By shill Date 2017-02-13 Time 16:07 Sent To  
Notes
2017-02-13 16:08:45****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107. THE SURVEY SHOULD INCLUDE ALL GRADE LEVEL
 MECHANICAL EQUIPMENT LOCATED OUTSIDE OF THE BUILDING.
 (TWO SETS REQUIRED)
  
 FIRE SPRINKLER UNDERGROUND AND FIRE SPRINKLER PERMIT
 APPLICATIONS WITH PLANS ARE TO BE SUBMITTED PRIOR TO
 FIRST INSPECTION AS PLANS WERE NOT PROVIDED WITH THE
 BUILDING PERMIT AS REQUESTED.
  
 FIRE ALARM PERMIT IS REQUIRED
  
 A SEPARATE ROOF PERMIT REQUIRED. THE ASSEMBLY PROPOSED
 AND ENGINEERING IF REQUIRED ARE TO BE SUBMITTED PRIOR
 TO COMMENCEMENT OF ROOF WORK.
  
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING WHICH ARE
 REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR TO PERMIT
 ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH, THE STEEL
 EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS, MONUMENT SIGNS,
 DUMPSTER ENCLOSURE, FENCING, SITE LIGHTING, GENERATOR
  
 COMPLIANCE WITH FBC 1006 (MEANS OF EGRESS ILLUMINATION)
 REQUIRED FROM EXIT DISCHARGE TO THE PUBLIC WAY. THIS IS
 TO BE VERIFIED IN THE FIELD BUT IS THE RESPONSIBILITY
 OF THE CONTRACTOR AND OWNER.
  
 SHEET E4.0 INCLUDES A GENERATOR ANCHORING DETAIL.
 REVISE TO INCLUDE WIND DESIGN CRITERIA FBC 1604.3.1.
 THIS MAY BE DONE WITH A LETTER AND PROVIDED AT
 INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-02-10 Cont ID  
Sent By shill Date 2017-02-10 Time 12:47 Rev Time 0.00
Received By shill Date 2017-02-10 Time 09:52 Sent To  
Notes
2017-02-10 12:49:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN, FBC 109.
  
 20. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107. THE SURVEY SHOULD INCLUDE ALL GRADE LEVEL
 MECHANICAL EQUIPMENT LOCATED OUTSIDE OF THE BUILDING.
 (TWO SETS REQUIRED)
  
 PROVISO ITEMS:
  
 FIRE SPRINKLER UNDERGROUND AND FIRE SPRINKLER PERMIT
 APPLICATIONS WITH PLANS ARE TO BE SUBMITTED PRIOR TO
 FIRST INSPECTION AS PLANS WERE NOT PROVIDED WITH THE
 BUILDING PERMIT AS REQUESTED.
  
 FIRE ALARM PERMIT IS REQUIRED
  
 A SEPARATE ROOF PERMIT REQUIRED. THE ASSEMBLY PROPOSED
 AND ENGINEERING IF REQUIRED ARE TO BE SUBMITTED PRIOR
 TO COMMENCEMENT OF ROOF WORK.
  
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING WHICH ARE
 REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR TO PERMIT
 ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH, THE STEEL
 EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS, MONUMENT SIGNS,
 DUMPSTER ENCLOSURE, FENCING, SITE LIGHTING, GENERATOR
  
 COMPLIANCE WITH FBC 1006 (MEANS OF EGRESS ILLUMINATION)
 REQUIRED FROM EXIT DISCHARGE TO THE PUBLIC WAY. THIS IS
 TO BE VERIFIED IN THE FIELD BUT IS THE RESPONSIBILITY
 OF THE CONTRACTOR AND OWNER.
  
 SHEET E4.0 INCLUDES A GENERATOR ANCHORING DETAIL.
 REVISE TO INCLUDE WIND DESIGN CRITERIA FBC 1604.3.1.
 THIS MAY BE DONE WITH A LETTER AND PROVIDED AT
 INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-29 Cont ID  
Sent By shill Date 2016-12-29 Time 14:46 Rev Time 0.00
Received By shill Date 2016-12-29 Time 14:46 Sent To  
Notes
2016-12-29 14:46:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 IMMEDIATE ACTIONS RECOMMENDED FOR PRELIMINARY REVIEW AS
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED FOR A COMPLETE
 REVIEW:
 PROVIDE FIRE SPRINKLER INFORMATION (HYDRAULIC CALCS,
 SYSTEM DESIGN INFO) AND VALUE VIA EMAIL.
 PROVIDE ELEVATION CERTIFICATE VIA EMAIL.
  
 12/29 SPRINKLER INFORMATION, SURVEY, SOILS REPORT
 RECEIVED VIA EMAIL; A COURTESY REVIEW WILL BE DONE
 AFTER FFE INFORMATION IS RECEIVED
  
 1. OK
  
 2. FROM PREVIOUS LIST:
  
 IF SPRINKLERS ARE PROPOSED, PROVIDE FIRE SPRINKLER
 DESIGN DOCUMENTS AS REQUIRED BY FBC 107.3.5 (5). IS THE
 EXISTING WATER SERVICE ADEQUATE FOR A NEW SPRINKLER
 SYSTEM, OR WILL A NEW UNDERGROUND LINE BE REQUIRED?
  
 2ND REVIEW, THE PLAN HAS A NOTE: SEE FIRE SPRINKLER
 PERMIT DRAWINGS UNDER SEPARATE SUBMITTAL. THE FIRE
 SPRINKLER INFORMATION HAS NOT BEEN SUBMITTED AT THIS
 TIME.
  
 IF THE SUBMITTAL IS SEPARATE, IT WILL BE DIFFICULT FOR
 BUILDING TO REVIEW AND MAY CAUSE PERMIT DELAYS. IT IS
 RECOMMENDED TO INCLUDE THE REQUESTED INFORMATION IN THE
 RESUBMITTAL.
  
 FIRE SPRINKLER INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE FOR THE REQUIREMENTS OF CHANGE OF OCCUPANCY
 FROM BUSINESS TO INSTITUTIONAL. A NOTE DOES NOT APPEAR
 TO BE ADEQUATE WITHOUT ADDITIONAL INFORMATION. IS IT
 KNOWN AT THIS POINT WHAT IS INVOLVED TO INSTALL A NEW
 SYSTEM (SCOPE OF WORK AND COST)? ARE DESIGN DOCUMENTS
 CURRENTLY IN DEVELOPMENT, AND IF NOT, WHY NOT? I DO NOT
 HAVE ENOUGH INFORMATION TO DETERMINE WHETHER THIS ITEM
 IS KNOWN BY ALL PARTIES AND IS BEING WORKED ON BUT NOT
 AVAILABLE, OR IF THIS REQUIREMENT HAS NOT BEEN FULLY
 CONSIDERED. A PROVISO IS POSSIBLE WITH ADDITIONAL
 INFORMATION.
  
 THE SPRINKLER INFORMATION IS ALSO REQUIRED FOR
 SUBSTANTIAL IMPROVEMENT DETERMINATION. FOR A POST FIRM
 BUILDING, LATERAL ADDITION SUBSTANTIAL IMPROVEMENT IS
 REQUIRED TO COMPLY (FBC 1612). PLANS SHOW ELEVATION AT
 FINISHED FLOOR AS 0. NO INFORMATION REGARDING THE
 EXISTING ELEVATION. PROPOSED ADDITION ELEVATION APPEARS
 TO MATCH EXISTING, BUT THE EXISTING FFE HAS NOT BEEN
 PROVIDED. THIS APPEARS TO BE A SUBSTANTIAL IMPROVEMENT,
 POST FIRM, LATERAL ADDITION. THE FINISHED FLOOR
 ELEVATION IS REQUIRED TO DETERMINE WHAT, IF ANY,
 REQUIREMENTS APPLY.
  
 IT IS POSSIBLE (LIKELY) THAT AN ENGINEERING REVIEW IS
 ALSO REQUIRED. HAS A SEPARATE ENGINEERING PERMIT BEEN
 APPLIED FOR? AT THIS TIME NOT ENOUGH INFORMATION HAS
 BEEN PROVIDED TO DETERMINE THE REVIEWS REQUIRED. IS A
 NEW CONNECTION INTO THE CITY SYSTEM REQUIRED? IF YES,
 AN ENGINEERING REVIEW IS REQUIRED FOR THIS PERMIT. NO
 CIVIL SHEETS WERE SUBMITTED.
  
 AT A MINIMUM, PROVIDE HYDRAULIC CALCS (OR OTHER
 RELIABLE INFORMATION WHICH DEMONSTRATES HOW BASIC
 DESIGN INFORMATION WAS DETERMINED), BASIC INFORMATION
 REGARDING THE PROPOSED SYSTEM (IS A FIRE PUMP OR NEW
 UNDERGROUND LINE REQUIRED? NEW CONNECTION TO CITY
 SYSTEM?), AND THE VALUE OF THE PROPOSED SYSTEM.
 TYPICALLY A SPRINKLER HEAD LAYOUT IS ALSO REQUIRED. IT
 IS POSSIBLE THAT THE HEAD LAYOUT PLAN MAY BE DEFERRED
 UPON RECEIPT OF BASIC INFORMATION REGARDING THE
 PROPOSED FIRE SPRINKLER SYSTEM. FBC 107.3.5(5), FBC B
 1612.
  
 3. OK
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN, FBC 109.
  
 NOT ADDRESSED. ALSO REQUIRED FOR FBC B 1612, NFIP
 SUBSTANTIAL IMPROVEMENT DETERMINATION.
  
 5-16. OK
  
 17. SHEET LS1.1 INDICATES THAT A NEW FIRE ALARM SYSTEM
 IS PROPOSED. I WAS UNABLE TO LOCATE THIS ON THE
 ELECTRICAL SHEETS. PLEASE ADVISE AS TO WHERE THIS
 INFORMATION CAN BE LOCATED. AS THE VALUE IS PROVIDED
 WITH THE FIRE ALARM PERMIT, PROVIDE THE VALUE AT THIS
 TIME SO IT CAN BE INCLUDED IN THE PROJECT COST, FBC B
 1612.
  
 18-20. OK
  
 19. PROVIDE A GEOTECHNICAL REPORT, FBC 1803.2.
 STRUCTURAL ENGINEER IS TO REVIEW THE REPORT PRIOR TO
 RESUBMITTAL.
  
 THIS WAS REQUESTED TO BE A PROVISO. SINCE THE
 FOUNDATION DESIGN SHOULD BE CONFIRMED IS ADEQUATE, AND
 THIS PARCEL IS IN A KNOWN POOR SOILS AREA, THE REPORT
 IS REQUIRED.
  
 20. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107. THE SURVEY SHOULD INCLUDE ALL GRADE LEVEL
 MECHANICAL EQUIPMENT LOCATED OUTSIDE OF THE BUILDING.
  
 21. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (120229 0015B, FLOOD ZONE A8, BFE 16'). REVISE THE
 PLAN TO SHOW THE EXISTING FLOOR ELEVATION, PROPOSED
 FLOOR ELEVATION, AND ELEVATION OF ALL PROPOSED
 EQUIPMENT. THE MINIMUM DFE REQUIRED (BFE 16' + 1'
 FREEBOARD CITY OF WEST PALM BEACH MUNICIPAL CODE 94-541
 THROUGH 94-547). SEE ALSO NFIP REVIEW.
  
 22. INFORMATION REGARDING THE TOTAL VALUE OF THE
 PROJECT IS REQUIRED AT THIS TIME. IF IT IS AGREED THAT
 ITEMS SUCH AS FIRE SPRINKLER AND FIRE ALARM MAY BE
 SUBMITTED LATER, THE VALUE OF SUCH ITEMS IS REQUIRED AT
 THIS TIME SO THAT A SUBSTANTIAL IMPROVEMENT
 DETERMINATION CAN BE MADE, FBC 1612.
  
 2ND REVIEW, IT APPEARS THAT THIS IS A POST FIRM
 SUBSTANTIAL IMPROVEMENT LATERAL ADDITION. ADDITION IS
 REQUIRED TO COMPLY; BUILDING IS REQUIRED TO COMPLY.
 PROVIDE THE ELEVATIONS FOR THE EXISTING BUILDING. THIS
 MAY BE PROVIDED VIA EMAIL. A COURTESY REVIEW WILL BE
 PERFORMED AFTER RECEIVING THIS INFORMATION.
  
 23. A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME UNTIL
 THE INFORMATION REGARDING VALUE AND EXISTING BUILDING
 ELEVATION IS PROVIDED. PLEASE PROVIDE THIS INFORMATION
 VIA EMAIL. IF AN ELEVATION CERTIFICATE IS AVAILABLE,
 SEND VIA EMAIL.
  
 24. PROVISO ITEMS:
  
 A SEPARATE ROOF PERMIT REQUIRED. THE ASSEMBLY PROPOSED
 AND ENGINEERING IF REQUIRED ARE TO BE SUBMITTED PRIOR
 TO COMMENCEMENT OF ROOF WORK.
  
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING WHICH ARE
 REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR TO PERMIT
 ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH, THE STEEL
 EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
 SEPARATE PERMITS REQUIRED FOR SIGNS, MONUMENT SIGNS,
 DUMPSTER ENCLOSURE, FENCING, SITE LIGHTING, GENERATOR
  
 SITE LIGHTING IS REQUIRED TO COMPLY WITH FBC 1006
 (MEANS OF EGRESS ILLUMINATION).
  
 SHEET E4.0 INCLUDES A GENERATOR ANCHORING DETAIL.
 REVISE TO INCLUDE WIND DESIGN CRITERIA FBC 1604.3.1.
 THIS MAY BE DONE WITH A LETTER AND PROVIDED AT
 INSPECTION.
  
 FBC ACCESSIBILITY 805.3, A CLEAR FLOOR SPACE COMPLYING
 WITH 305 SHALL BE PROVIDED ON EACH SIDE OF THE BED. THE
 CLEAR FLOOR SPACE SHALL BE POSITIONED FOR PARALLEL
 APPROACH TO THE SIDE OF THE BED.
  
 ACCESSIBLE SHOWERS TO COMPLY WITH FBC ACCESSIBILITY
 607.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By shill Date 2016-11-17 Time 14:50 Rev Time 0.00
Received By shill Date 2016-11-14 Time 17:37 Sent To  
Notes
2016-11-17 14:51:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY (FROM B TO
 I2). REVISE PLAN TO INCLUDE THIS INFORMATION. SEE FBC
 EB CHAPTER 10. (SHEET LS1.1 STATES THIS IS A CHANGE OF
 USE. )
  
 2. LS1.1 INCLUDES A STATEMENT THAT BUILDING IS TO BE
 FULLY SPRINKLERED, SEE FIRE SPRINKLER DRAWINGS UNDER
 SEPARATE SUBMITTAL.
  
 IS THE BUILDING CURRENTLY SPRINKLERED? NOTES ON THE
 PLAN APPEAR TO INDICATE THAT SPRINKLERS ARE PROPOSED.
 IT APPEARS THAT THIS IS A LEVEL 3 ALTERATION, AND FIRE
 SPRINKLERS APPEAR TO BE REQUIRED FBC 5TH EDITION
 EXISTING BUILDING 804.2.4.
  
 IF SPRINKLERS ARE PROPOSED, PROVIDE FIRE SPRINKLER
 DESIGN DOCUMENTS AS REQUIRED BY FBC 107.3.5 (5). IS THE
 EXISTING WATER SERVICE ADEQUATE FOR A NEW SPRINKLER
 SYSTEM, OR WILL A NEW UNDERGROUND LINE BE REQUIRED?
  
 3. ENERGY CALC INPUT DATA LACKS DOORS, PLAN SHOWS A
 STEEL DOOR, PLEASE CORRELATE FBC 107.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN, FBC 109.
  
 5. SEE ROOF REVIEW. THE INFORMATION REQUIRED TO OBTAIN
 A ROOF SUB PERMIT MAY BE DEFERRED UPON REQUEST.
  
 6. SHEET A2.1 SPECS R19, 3.5 INCH INSULATION FOR THE
 ROOF. THE ENERGY CALCS SPEC 6 INCH INSULATION, R20.
 PLEASE CORRELATE.
  
 7. SHEET S4 SHOWS EXISTING ROOF TO REMAIN, LIGHTWEIGHT
 CONCRETE. THE ENERGY CALCS DO NOT INCLUDE TWO DIFFERENT
 ROOF ASSEMBLIES, CLARIFY. THE PERMIT WILL BE ISSUED
 WITH PROVISO THAT THE EXISTING ROOF IS NOT INCLUDED IN
 THE SCOPE OF THIS PERMIT.
  
 8. THE FOLLOWING PRODUCT APPROVALS WERE SUBMITTED AND
 FOUND ACCEPTABLE:
 JOHNS MANVILLE BUILT UP ROOF OVER CONCRETE DECK
 PGT SS 3500 ALUMINUM STOREFRONT SYSTEM
 PGT SE 3550 ALUMINUM STOREFRONT ENTRANCE DOOR
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO: PRODUCT
 APPROVALS FOR COMPONENTS AND CLADDING WHICH ARE
 REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR TO PERMIT
 ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH, THE STEEL
 EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
 9. THIS PERMIT WILL BE ISSUED WITH PROVISO, SEPARATE
 PERMITS REQUIRED FOR SIGNS, MONUMENT SIGNS, DUMPSTER
 ENCLOSURE, FENCING, SITE LIGHTING,
  
 10. THIS PERMIT WILL BE ISSUED WITH PROVISO, SITE
 LIGHTING IS REQUIRED TO COMPLY WITH FBC 1006 (MEANS OF
 EGRESS ILLUMINATION).
  
 11. FBC 1004.1.2, CLARIFY OCCUPANT LOAD FOR THE
 RESIDENTIAL AREA. THE OCCUPANT LOAD IS LESS THAN THE
 NUMBER OF BEDS SHOWN, AND SP1 STATES THERE ARE 46 BEDS.
 IT APPEARS THAT DESIGN OCCUPANT LOAD IS HIGHER THAN THE
 TABLE, CLARIFY OR REVISE.
  
 12. A1.1 NOTE 4 STATES THAT KITCHEN DESIGN AND
 EQUIPMENT ARE ATTACHED, UNABLE TO LOCATE INFORMATION.
 WHO WILL USE THE KITCHEN, RESIDENTS OR STAFF? IS THIS A
 WORK AREA, OR AN AMENITY? SEE ALSO FBC B 904.2.1, FBC
 ACCESSIBILITY. IT APPEARS THAT THIS WILL SERVE AS A
 COMMERCIAL KITCHEN (STAFF ONLY); REVISE PLAN TO
 CLARIFY.
  
 13. A7.3, DETAIL 5 IS FOR A SMOKE BARRIER, CLARIFY.
 OTHER SHEETS REFER TO A SMOKE PARTION WHICH IS REQUIRED
 BY FBC 407.3. IT IS ACCEPTABLE TO EXCEED CODE
 COMPLIANCE BUT, IF IT IS CALLED A SMOKE BARRIER, THE
 REQUIREMENTS OF A SMOKE BARRIER ARE APPLICABLE.
  
 14. DOOR SCHEDULE, A7.1, REVISE TO INCLUDE REQUIREMENTS
 FOR DOORS, FBC 407.3.1.
  
 15. A6.1, OR OTHER APPLICABLE SHEET, REVISE PLAN TO
 INCLUDE REQUIREMENT THAT THE CEILING IS TO BE INSTALLED
 IN A MANNER TO LIMIT THE TRANSFER OF SMOKE, FBC 7F10.4.
  
 16. THIS PERMIT WILL BE ISSUED WITH PROVISO, A SEPARATE
 PERMIT IS REQUIRED FOR THE GENERATOR REFERENCED ON
 E4.0.
  
 17. A NOTE ON SHEET LS1.1 STATES THAT THE FIRE ALARM IS
 EXISTING AND FULLY FUNCTIONAL. A FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC B 907.2.6 IS REQUIRED. SINCE THE
 ENTIRE SPACE IS BEING RECONFIGURED, IT APPEARS THAT AN
 ALTERATION OF THE FIRE ALARM SYSTEM IS REQUIRED.
 COMPLIANCE WITH OTHER REQUIREMENTS, SUCH AS OCCUPANT
 NOTIFICATION SYSTEM, IS NOT CLEAR AS THIS WAS NOT
 REQUIRED FOR THE BUSINESS OCCUPANCY. ARE OCCUPANT
 NOTIFICATION REQUIREMENTS THE SAME FOR BUSINESS AS
 SLEEPING AREAS? REVISE PLAN TO NOTE BASIC DESIGN
 REQUIREMENTS. A SEPARATE PERMIT IS REQUIRED FOR THE
 FIRE ALARM AND A COMPLETE REVIEW WILL BE DONE AT THAT
 TIME.
  
 18. A8.1, DETAILS 2, 5 GRAB BAR IS TOO HIGH, SEE FBC A
 609.9, TOP CANNOT EXCEED 36 IN.
  
 19. PROVIDE DETAILS FOR THE SHOWERS, FBC A 608.
  
 20. A8.1, THE BOTTOM OF THE REFLECTIVE SURFACE IS TO BE
 40IN ABOVE THE FINISHED FLOOR, FBC A 603.3.
  
 19. PROVIDE A GEOTECHNICAL REPORT, FBC 1803.2.
 STRUCTURAL ENGINEER IS TO REVIEW THE REPORT PRIOR TO
 RESUBMITTAL.
  
 20. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107. THE SURVEY SHOULD INCLUDE ALL GRADE LEVEL
 MECHANICAL EQUIPMENT LOCATED OUTSIDE OF THE BUILDING.
  
 21. THIS PARCEL IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (120229 0015B, FLOOD ZONE A8, BFE 16'). REVISE THE
 PLAN TO SHOW THE EXISTING FLOOR ELEVATION, PROPOSED
 FLOOR ELEVATION, AND ELEVATION OF ALL PROPOSED
 EQUIPMENT. THE MINIMUM DFE REQUIRED (BFE 16' + 1'
 FREEBOARD CITY OF WEST PALM BEACH MUNICIPAL CODE 94-541
 THROUGH 94-547). SEE ALSO NFIP REVIEW.
  
 22. INFORMATION REGARDING THE TOTAL VALUE OF THE
 PROJECT IS REQUIRED AT THIS TIME. IF IT IS AGREED THAT
 ITEMS SUCH AS FIRE SPRINKLER AND FIRE ALARM MAY BE
 SUBMITTED LATER, THE VALUE OF SUCH ITEMS IS REQUIRED AT
 THIS TIME SO THAT A SUBSTANTIAL IMPROVEMENT
 DETERMINATION CAN BE MADE, FBC 1612.
  
 23. A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME UNTIL
 THE INFORMATION REGARDING VALUE AND EXISTING BUILDING
 ELEVATION IS PROVIDED. PLEASE PROVIDE THIS INFORMATION
 VIA EMAIL. IF AN ELEVATION CERTIFICATE IS AVAILABLE,
 SEND VIA EMAIL.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-31 Cont ID  
Sent By rlecky Date 2017-01-31 Time 11:03 Rev Time 0.00
Received By rlecky Date 2017-01-31 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-13 Cont ID  
Sent By rlecky Date 2016-12-13 Time 12:15 Rev Time 0.00
Received By rlecky Date 2016-12-13 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By rlecky Date 2016-11-08 Time 12:48 Rev Time 0.00
Received By rlecky Date 2016-11-08 Time 10:59 Sent To  
Notes
2016-11-08 12:54:35NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 GENERATOR, ALARM SYSTEMS, SECURITY, SITE LIGHTING, AND
 DATA SYSTEMS

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2017-02-07 Cont ID  
Sent By mgonzale Date 2017-02-07 Time   Rev Time 1.00
Received By mgonzale Date 2017-02-07 Time   Sent To I
Notes
2017-02-07 11:31:59 
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-01-03 Cont ID  
Sent By mgonzale Date 2017-01-03 Time   Rev Time 1.00
Received By mgonzale Date 2017-01-03 Time   Sent To I
Notes
2017-01-03 17:26:01PLEASE SUBMIT DIRECTLY ENGINEERING SERVICES DEPARTMENT.
 HTTP://WPBFL.US/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
  
 CONTACT:
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 818-1322
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-02-01 Cont ID  
Sent By scaldero Date 2017-02-01 Time 12:47 Rev Time 0.00
Received By scaldero Date 2017-02-01 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-14 Cont ID  
Sent By scaldero Date 2016-12-14 Time 12:06 Rev Time 0.00
Received By scaldero Date 2016-12-14 Time 12:06 Sent To  
Notes
2016-12-28 13:14:25PERMIT #16110067
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
 1) FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PLEASE SUBMIT WITH RESUBMITTAL ADDRESSING COMMENTS BY
 ALL OTHER REVIEWERS.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-07 Cont ID  
Sent By scaldero Date 2016-11-07 Time 11:16 Rev Time 0.00
Received By scaldero Date 2016-11-07 Time 10:43 Sent To  
Notes
2016-11-07 11:16:50PERMIT #16110067
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PER NFPA 101: 32.3.3.4.7 SMOKE ALARMS. APPROVED
 SMOKE ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH
 9.6.2.10 INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-02-10 Cont ID  
Sent By tklarge Date 2017-02-10 Time 09:45 Rev Time 0.00
Received By tklarge Date 2017-02-10 Time 09:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-02-08 Cont ID  
Sent By tklarge Date 2017-02-08 Time 07:25 Rev Time 0.00
Received By tklarge Date 2017-02-08 Time 06:50 Sent To  
Notes
2017-02-08 07:09:121)PLEASE CALL TO SET UP A MEETING TO REVIEW THE GAS
 RISER. I CANNOT DO A PLAN REVIEW ON IT DUE TO THE
 DEFICIENCIES OBSERVED.
 2) SCREENS COVERING THE COMBUSTION AIR DUCTS SHALL HAVE
 A MESH SIZE NOT SMALLER THAN ONE-QUARTER INCH. 2014
 FBC-FUEL GAS SEC.304.10.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-01-04 Cont ID  
Sent By tklarge Date 2017-01-04 Time 12:43 Rev Time 0.00
Received By tklarge Date 2017-01-04 Time 06:15 Sent To  
Notes
2017-01-04 11:29:421) SHT.P4.1 - A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. A SHUTOFF VALVE
 SHALL BE LOCATED BETWEEN THE GAS METER AND THE NEW
 REGULATOR. 2ND REQUEST. FBC FUEL GAS SEC.409.4.
 2) SHT. P4.1 - SHOW THE CORRECT DISTANCE FROM THE NEW
 GAS REGULATOR TO THE MOST REMOTE OUTLET ON THE SYSTEM
 WHICH APPEARS TO BE THE GENERATOR. THE PLANS NOTE THE
 LONGEST RUN OF GAS PIPING FROM THE NEW GAS REGULATOR TO
 THE MOST REMOTE GAS OUTLET AS 195 FEET. THE FOLLOWING
 LENGTHS OF PIPE MEASUREMENTS SHOWN ON THE PLANS TO THE
 MOST REMOTE GAS OUTLET ARE AS FOLLOWS:
 3' + 5' + 15'- 6" + 56' +140' + 15'- 6" +3' . PLEASE
 EXPLAIN HOW THIS EQUALS 195 FEET WHEN I CALCULATE 238
 FEET. 2ND REQUEST.2014 FBC-FUEL GAS SEC.402.4.1. A
 COMPREHENSIVE GAS REVIEW CANNOT BE PERFORMED UNTIL THE
 CORRECT DISTANCE IS PROVIDED AND THE PLANS ARE
 CORRECTED. IF THE DISTANCE IS 238 FEET THE ENTIRE GAS
 SYSTEM IS UNDERSIZED FOR GALVANIZED PIPE. SIZE ALL
 SECTIONS OF THE GAS RISER IN ACCORDANCE WITH THE
 APPLICABLE SIZING TABLES IN THE FUEL GAS CODE.
 3) SHT. P4.1 - THE GAS RISER STILL SHOWS THE
 UNDERGROUND PIPE AS GALVANIZED ( LABELED "G") BUT THE
 TEXT STATES THE UNDERGROUND PIPE TO BE PE. CLEARLY
 IDENTIFY THE TYPE OF PIPING IN THE DIFFERENT AREAS ON
 THE GAS RISER. 2ND REQUEST. 2014 FBC-FUEL GAS
 SEC.404.11.
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 KITCHEN EQUIPMENT AND ALL OTHER GAS APPLIANCES /
 EQUIPMENT PER THE 2014 FBC-FUEL GAS SEC.304.1.WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2014 FBC-FUEL GAS SEC.
 304.9.3.THE CODE SECTION YOUR DESIGN IS BASED UPON
 REFERS TO THE SUPPLY OF COMBUSTION AIR BY MEANS OF A
 FAN/BLOWER THAT RUNS WHEN ANY OF THE SERVED APPLIANCES
 ARE IN A FIRING CYCLE. HOW ARE TRANSFER GRILLS AND
 DUCTS MEETING THIS REQUIREMENT?
 5) SUBMIT A DETAIL SHOWING THE TYPE, SIZE, LOCATION AND
 TERMINATION OF GAS VENTS PER 2014 FBC-FUEL GAS SECS.
 502 THRU 505. THIS HAS NOT BEEN DONE. 2ND REQUEST.
 6) SHOW THE EMERGENCY SHUT DOWN VALVE AND THE MANUAL
 SHUTOFF VALVE FOR THE GAS TO THE GAS COOKING APPLIANCES
 IN THE KITCHEN. THE LOCATION OF THE EMERGENCY SHUT DOWN
 AND THE MANUAL ACTIVATION VALVE SHALL BE LOCATED IN
 ACCORDANCE WITH NFPA 96-08 SECS. 10.4 & 10.5. 2ND
 REQUEST. THE EMERGENCY SHUT DOWN VALVE SHALL BE LOCATED
 BELOW THE CEILING AND THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM OF THE EMERGENCY SHUT DOWN VALVE WITH A UNION
 LOCATED DOWNSTREAM OF THE MANUAL VALVE. THESE ITEMS
 SHALL BE SHOWN ON THE GAS PLAN. 2ND REQUEST.
 7) APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND
 SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. SUBMIT WIND LOAD ANCHORING
 DETAILS FOR THE GENERATOR. 2ND REQUEST.
 8) SHOW THE GAS PIPING TO THE WATER HEATER ON SHT.
 P3.0.
 9) ARE THE DRYERS LOCATED IN ROOM #118 GAS OR ELECTRIC?
 IF GAS, SHOW THE DRYERS AND THE BTU LOAD OF EACH ONE ON
 THE GAS RISER, SUBMIT COMBUSTION AIR CALCULATIONS AND
 DETAILS ON THE VENTS.WPB AMEND. TO FBC SEC. 107.2.1.
 10) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN.
 CODE RULE 61G15-23.001. THE SUBMITTED PLANS ARE COPIES
 OF THE SEAL AND SIGNATURE. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By tklarge Date 2016-11-21 Time 06:43 Rev Time 0.00
Received By tklarge Date 2016-11-21 Time 05:35 Sent To  
Notes
2016-11-21 06:12:39GAS REVIEW
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON ALL GAS
 APPLIANCES / EQUIPMENT. EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2014 FBC- FUEL GAS SEC.301.3. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 2) A SHUTOFF VALVE IS REQUIRED ON THE SUPPLY SIDE OF
 THE METTER. FBC- FUEL GAS SEC.409.2.
 3) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF OF EACH MP REGULATOR. FBC- FGC
 SEC.409.4.
 4) SHT. P4.01 - NOTE #3 - THE GAS CODE IN EFFECT IS THE
 2014 FBC-FUEL GAS CODE, NOT THE 2010. REVISE THE NOTE.
 5) THE GRILLE AND FIRE PIT IS NOT LISTED IN THE GAS
 FIXTURE LOAD SUMMARY. CLARIFY.
 6) THE GAS RISER DOES NOT SHOW WHERE THE GRILLE AND THE
 FIRE PIT GAS PIPING CONNECT TO THE SYSTEM. SUBMIT A
 COMPLETE GAS RISER FOR ALL NEW AND EXISTING GAS
 APPLIANCES THAT WILL BE / ARE CONNECTED TO THIS SYSTEM.
 IF THE GRILLE AND FIRE PIT ARE CONNECTED TO A SEPARATE
 SYSTEM AND A SEPARATE METER, SUBMIT THE ENNTIRE GAS
 RISER FOR THAT SYSTEM FOR REVIEW.WPB AMEND. TO FBC
 107.2.1.
 7) SHT. P4.01 - THE PLANS NOTE THE LONGEST RUN IS 108.5
 FEET BUT I CALCULATED 214.5 FEET. IS THIS LOW PRESSURE
 OR HIGH PRESSURE? RECHECK YOUR DISTANCE. THIS WILL ALSO
 AFFECT THE SIZING.SHOW THE DISTANCE FOR THE LOW
 PRESSURE SSYSTEM FROM THE MP REGULATOR TO THE MOST
 REMOTE OUTLET ON THE SYSTEM.FGC SEC.402.4.1.
 8) SHOW THE DISTANCE FROM THE NEW REGULATOR TO THE
 FIRST TEE IN THE PIPING SYSTEM.
 9) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED
 UNDERGROUND AND ALL PIPE SIZES. GALVANIZED PIPING
 CANNOT BE INSTALLED UNDERGROUND.FGC SEC. 404.11.
 10) SHT. P4.01 REFERS TO 98UE TANKLESS WATER HEATER BUT
 THIS FIXTURE IS NOT SHOWN ON THE GAS RISER. CLARIFY.
 11) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 12) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 KITCHEN EQUIPMENT AND ALL OTHER GAS APPLIANCES /
 EQUIPMENT PER THE 2014 FBC-FUEL GAS CODE SEC.304.1 OR
 2014 FBC-RES. SEC. G 2407.
 13) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 14) THE GAS PLAN REFERS TO A 2 PSI SYSTEM AND ALSO A
 SYSTEM LESS THAN 2 PSI.THE GAS RISER DOES NOT SHOW THE
 DELINEATION OF THE TWO DIFFERENT SYSTEMS.SHOW THE
 LOCATION OF ALL MP REGULATORS, WHERE THE 2 PSI SYSTEM
 BEGINS AND ENDS AND WHERE THE LOWW PRESSURE SYSTEM
 BEGINS AND ENDS. 2014 FBC-FUEL GAS SEC.402.2 OR FBC
 RES. SEC. G2413.2.
 15) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 16) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS.10.4, 10.5 OF NFPA 96-08.
 17) CLEARLY INDICATE ON THE PLAN WHAT SIZING TABLES ARE
 BBEING USED IN THIS DESIGN AND FROM WHICH CODE
 STANDARD.WPB AMEND. TO FBC SEC. 107.2.1.
 18) APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND
 SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.SUBMIT WIND LOAD ANCHORING
 DETAILS FOR THE GENERATOR.
  
 NOTE: THE PLANS ARE SO VAGUE THAT A COMPREHENSIVE
 REVIEW COULD NOT BE DONE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-05-15 Cont ID  
Sent By shill Date 2017-02-13 Time 10:57 Rev Time 0.00
Received By shill Date 2017-02-13 Time 16:49 Sent To  
Notes
2017-02-13 16:49:52TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-10 Cont ID  
Sent By shill Date 2017-02-10 Time 12:55 Rev Time 0.00
Received By shill Date 2017-01-25 Time 11:43 Sent To  
Notes
2017-01-26 11:43:21C03

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-04 Cont ID  
Sent By tklarge Date 2017-01-04 Time 12:43 Rev Time 0.00
Received By tklarge Date 2016-12-07 Time 10:57 Sent To  
Notes
2016-12-08 10:57:52C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-21 Cont ID  
Sent By tklarge Date 2016-11-21 Time 06:44 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 09:59 Sent To  
Notes
2016-11-04 09:59:50C04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By shill Date 2017-02-13 Time 16:09 Rev Time 0.00
Received By shill Date 2017-02-13 Time 16:09 Sent To  
Notes
2017-02-13 16:09:24MU 2017 000664
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-14 Cont ID  
Sent By shill Date 2016-11-14 Time 17:33 Rev Time 0.00
Received By shill Date 2016-11-14 Time 17:33 Sent To  
Notes
2016-11-14 17:33:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 PLEASE CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-02-03 Cont ID  
Sent By ccole Date 2017-02-01 Time 16:29 Rev Time 0.00
Received By ccole Date 2017-02-03 Time 11:11 Sent To  
Notes
2017-02-01 16:33:03MECHANICAL PROVISO:
  
 1) MANUFACTURER'S SPECIFCATIONS FOR ALL AC SYSTEMS
 SHALL BE ONSITE AT TIME OF INSPECTION.
  
 2) ACCESS PANELS SHALL BE PROVIDED FOR ALL
 ABOVE-CEILING FCU'S.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-19 Cont ID  
Sent By ccole Date 2016-12-19 Time 15:30 Rev Time 0.00
Received By ccole Date 2016-12-19 Time 15:30 Sent To  
Notes
2016-12-19 16:08:192ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110067
 12/19/16
  
 1) 2ND REQUEST FOR COOLING AND HEATING CALCULATIONS FOR
 RTU-1.
  
 2) 2ND REQUEST FOR OWNER/AGENT SIGNATURE ON THE ENERGY
 CALCULATIONS
  
 3) SMOKE DAMPERS ARE REQUIRED FOR THE DUCTS PENETRATING
 THE CORRIDOR AND UTILITY ROOM SMOKE PARTITIONS.
  
 4) IN REFERENCE TO THE NARRATIVE RESPONSE FROM THE
 ARCHITECT TO COMMENT #4 FROM THE 1ST REVIEW, PLEASE
 PROVIDE A KEYED NOTE ON THE PLAN TO CLARIFY THE FAN
 SHUTDOWN PROCEDURE UPON DETECTION OF SMOKE.
  
 5) IN REFERENCE TO RESPONSE TO COMMENT #8 FROM THE 1ST
 REVIEW PLEASE INDICATE HOW COMBUSTION AIR IS BEING
 PROVIDED FOR THE COOKING APPLIANCES AND SHOW
 CALCULATIONS.
  
 6) IN REFERENCE TO COMMENT #7 FROM THE 1ST REVIEW
 PLEASE INDICATE HOW DRYER MAKEUP AIR IS BEING PROVIDED
 AND SHOW CALCULATIONS. PLEASE SUBMIT MANUFACTURER'S
 SPECS FOR THE DRYERS.
  
 7) THE REQUESTED WIND LOAD ENGINEERING WAS NOT
 PROVIDED- PLEASE COMPLY.
  
 8) THE MECHANICAL PLANS HAVE COPIED ENGINEER'S SEALS
 AND SIGNATURES. ORIGINALS ARE REQUIIRED PER SECTION
 61G15-23.002 FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 11:15 Rev Time 0.00
Received By ccole Date 2016-11-09 Time 07:21 Sent To  
Notes
2016-11-09 12:17:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110067
 11/9/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 RTU-1. IT APPEARS THAT HP-1 & 2 WERE SIZED USING ONLY
 THE SENSIBLE COOLING LOADS SHOWN IN THE SUMMARY
 CALCULATIONS, AND NO HEATING LOAD CALCS ARE SHOWN.
  
 2) ENERGYGAUGE COMPLIANCE FORM: A) PROVIDE COMPLIANCE
 DATA FOR RTU-1. B) THE OWNER/AGENT MUST SIGN THE FORM-
 SEE PAGE 3.
  
 3) SHEETS M1 & M1.1: PLACE THE #3 KEYED NOTE AT EACH
 FIRE DAMPER LOCATION. PLEASE CLARIFY WHY FIRE DAMPERS
 ARE BEING INSTALLED AT DUCT PENETRATIONS INTO THE
 CORRIDOR SMOKE PARTITIONS- SEE SHEET A1.1 AND SECTION
 607.5.7. WHERE REQUIRED SMOKE DAMPERS SHALL BE
 INSTALLED IN SMOKE PARTITIONS.
  
 4) REFER TO SECTION 606.2.1- 606.2.2 AND PROVIDE DUCT
 SMOKE DETECTORS IN ALL RETURN AIR SYSTEMS OR AREA SMOKE
 DETECTORS THAT ARE CONNECTED TO THE FIRE ALARM. PLEASE
 NOTE THAT FIRE ALARM PLANS MUST BE SUBMITTED UNDER
 SEPARATE PERMIT, HOWEVER THE SMOKE DETECTORS MUST BE
 SHOWN ON BOTH SETS OF PLANS.
  
 5) M1.& M1.1: PLACE THE KEYED NOTE #9 AT EACH FAN COIL
 LOCATION AND PROVIDE A CONDENSATE DISPOSAL PLAN PER
 SECTION 307. SHOW THE PIPING RUNS, TYPE AND SIZES OF
 PIPINGS, AND DISCHARGE LOCATIONS.
  
 6) M1 & M1.1: PLACE THE KEYED NOTE #11 AT EACH
 REFRIGERATION DISTRIBUTION BOX SHOWN ON THE PLAN AND
 INDICATE HOW ACCESS WILL BE PROVIDED TO THE BOX.
  
 7) M1.1: SHOW THE DRYER EXHAUST DUCT RUNS AND PROVIDE
 DETAILS INCLUDING TYPES AND SIZES OF DUCTS, THE DUCT
 RUN LENGTHS AND TERMINATION LOCATIONS- SEE SECTION 504.
 A) PROVIDE MAKEUP AIR AND CALCULATIONS. B) SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND PROVIDE AN EQUIPMENT
 SCHEDULE ON THE PLAN. C) INDICATE THE EXHAUST CFMS IN
 THE PRESSURIZATION CALCULATIONS ON M3.3.
  
 8) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE
 COOKING APPLIANCES AND PROVIDE CALCULATIONS- SECTION
 304 FBC-14 FUEL GAS.
  
 9) M4: REFER TO SECTION 403.2.4.4 FBC-14 ENERGY
 CONSERVATION: IT APPEARS THAT THE CONTROL SEQUENCE FOR
 RTU-1 O/A IS NOT IN COMPLIANCE BECAUSE THE DAMPERS WILL
 REMAIN OPEN WHEN THE BUILDING IS UNOCCUPIED.
  
 10) REFER TO SECTION 301.15 AND PROVIDE WIND LOAD
 ENGINEERING FOR ANCHORING THE RTU AND HP-1 & 2. PLEASE
 INCLDUE THE DESIGN CRITERIA AS OUTLINED IN SECTUION
 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2017-02-10 Cont ID  
Sent By shill Date 2017-02-10 Time 12:30 Rev Time 0.00
Received By shill Date 2017-02-10 Time 12:30 Sent To  
Notes
2017-02-10 12:32:56THIS IS A SUBSTANTIAL IMPROVEMENT AND A LATERAL
 ADDITION (VALUE $550,000; PAPA VALUATION 2016 $684,869)
 ELEVATION CERTIFICATE WAS PROVIDED; ALL ELEMENTS COMPLY
 WITH BFE + 1' FREEBOARD.
  
 PROVISO:
  
 PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY INCLUDING
 ELEVATIONS IS REQUIRED (OR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE)
  
 AFTER FINAL GRADE IS COMPLETE, A "FINISHED
 CONSTRUCTION" ELEVATION CERTIFICATE IS REQUIRED PRIOR
 TO FINAL INSPECTION
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-12-01 Cont ID  
Sent By shill Date 2016-12-01 Time 10:41 Rev Time 0.00
Received By shill Date 2016-12-01 Time 10:41 Sent To  
Notes
2016-12-01 10:44:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FLOOD RELATED REQUIREMENTS IN BUILDING PLAN
 REVIEW.
  
 2. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 PRIOR TO CONCRETE POUR, A "BUILDING UNDER CONSTRUCTION"
 ELEVATION CERTIFICATE IS REQUIRED. IT IS SUGGESTED THAT
 THIS EC BE SENT VIA EMAIL FOR PRELIMINARY REVIEW TO
 AVOID FIELD DELAYS.
  
 PRIOR TO FINAL INSPECTION, BUT AFTER FINAL FINISHED
 GRADE, A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE
 IS REQUIRED. IT IS SUGGESTED THAT THIS EC BE SENT VIA
 EMAIL TO AVOID DELAY OF C.O.
  
 """"
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-02-10 Cont ID  
Sent By tklarge Date 2017-02-10 Time 09:45 Rev Time 0.00
Received By tklarge Date 2017-02-10 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-02-08 Cont ID  
Sent By tklarge Date 2017-02-08 Time 06:42 Rev Time 0.00
Received By tklarge Date 2017-02-08 Time 05:04 Sent To  
Notes
2017-02-08 06:42:391) SHT. P3.1 - THE PLAN SHOWS A CONCRETE VAULT TYPE
 GREASE INTERCEPTOR AND ALSO AN ALL STEEL WATTS (
 HYDROMECHANICAL ?) GREASE INTERCEPTOR.WHICH TANK IS
 BEING USED? AT THIS POINT I HAVE NO IDEA AS TO HOW THE
 SIZE OF THE WATTS INTERCEPTOR WAS DETERMINED, HOW THE
 FLOW RATE WAS DETERMINED, THE GREASE CAPACITY,
 ETC.SUBMIT SIZING CALCULATIONS FOR THE WATTS
 INTERCEPTOR. 2014 FBC-PLUMBING SEC.1003.2, 1003.3.4,
 1003.3.4.1.
 2) THE CONCRETE INTERCEPTOR SHALL COMPLY WITH THE
 DESIGN REQUIREMENTS OF FL. ADMIN. CODE RULE 64E-6.013
 (7) (A). THE INLET INVERT SHALL DISCHARGE A MINIMUM 2
 1/2 INCHES ABOVE THE LIQUID LEVEL LINE AND THE OUTLET
 PIPE SHALL HAVE A TEE WITH A MINIMUM DIAMETER OF 4
 INCHES THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF
 THE TANK.
 3) THE MINIMUM CAPACITY OF A CONCRETE VAULT TYPE GREASE
 INTERCEPTOR SHALL BE 750 GALLONS. F.A.C. RULE 64E-6.013
 (7) (D).
 4) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF
 THE GREASE INTERCEPTOR.
 5) A LAUNDRY INTERCEPTOR IS REQUIRED FOR THE LAUNDRY
 AREA PERR 2014 FBC-PLUMBING SEC. 1003.6. THIS ITEM WAS
 OVERLOOKED DURING THE PREVIOUS REVIEWS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-01-03 Cont ID  
Sent By tklarge Date 2017-01-03 Time 06:47 Rev Time 0.00
Received By tklarge Date 2016-12-31 Time 09:15 Sent To  
Notes
2017-01-03 06:47:531) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE
 RULE 61G15-23.001. THE SUBMITTED PLANS ARE COPIES OF
 THE SEAL AND SIGNATURE. 2ND REQUEST.
 2) SUBMIT A KITCHEN EQUIPMENT SCHEDULE / LIST FOR
 REVIEW. THE LIST SHALL SHOW THE WATER, DRAIN AND GAS
 SUPPLY SIZES TO THE EQUIPMENT.
 3) SHT.P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY
 CLEANOUT BUT IT IS ALSO SHOWN AT THE GAS LINE. WHICH IS
 IT? CLARIFY. 2ND REQUEST.
 4) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK
 ON THE WATER HEATER DETAIL. 2ND. REQUEST.
 5) THE ICEMAKER AND JUICE MACHINE EACH SHALL BE
 EQUIPPED WITH BACKFLOW PREVENTERS, NOT ONE DEVICE FOR
 BOTH APPLIANCES.2014 FBC-PLUMBING SECS.608.3,
 608.16.10.
 6) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE
 GREASE INTERCEPTOR.2014 FBC-PLUMBING SEC.1003.2. IF THE
 UNIT IS A HYDROMECHANICAL TYPE INTERCEPTOR, SUBMIT
 SIZING CALCULATIONS DONE BY THE MANUFACTURER.
 HYDROMECHANICAL GREASE INTERCEPTORS SHALL COMPLY WITH
 2014 FBC-PLUMBING SEC.1003.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-21 Cont ID  
Sent By tklarge Date 2016-11-21 Time 06:28 Rev Time 0.00
Received By tklarge Date 2016-11-20 Time 04:27 Sent To  
Notes
2016-11-20 06:37:30PLUMBING PLAN REVIEW 11/20/16 TIM LARGE
  
 1) SHT. SP 1 SHOWS AN EMERGENCY GENERATOR. INDICATE ON
 THE PLAN IF IT IS NEW OR EXISTING. IF NEW, SUBMIT TWO
 COPIES OF FFULL DOCUMENTATION FOR THE GENERATOR (
 MANUFACTURER'S SPECIFICATIONS, MANUAL, ETC., ) OR PLACE
 A NOTE ON THE PLAN THAT THE GENERATOR WILL BE DDONE
 UNDER A SEPARATE PERMIT. WPB AMEND. TO 2014 FBC SEC.
 107.2.1.
 2) A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION
 SYSTEM AS NO IRRIGATION PLANS HAVE BEEN SUBMITTED.
 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY. INDICATE
 THIS ON THE PLANS AND LIST THE PREVIOUS OCCUPANCY ON
 THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. LS 1.1 NOTES 43 BEDS BUT THE PLAN SHOWS 44 BEDS
 AND SHT. SP 1 NOTES 46 BEDS. CLARIFY AND PLACE THE
 CORRECT NUMBER OF BEDS ON THE NOTED SHEETS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHT. A8.1 - ELEV. #1 - THE GRAB BAR ON THE SIDE WALL
 SHALL BE LOCATED PER 2014 FBC-ACCESS. SEC.604.5.1 AND
 FIGURE 604.5.1. THE GRAB BAR SHALL EXTEND A MINIMUM OF
 54 INCHES FROM THE REAR WALL.
 6) SHT. A8..1 - ELEV. #3 SHOWS 2'-5" MINIMUM TO THE
 BOTTOM OF THE LAVATORY APRON AND ELEVATION #2 SHOWS
 2'-3". CLARIFY.
 7) SHT.A8.1 - ELEV.#1 - THE LOCATION OF THE TOILET
 PAPER DISPENSER SHALL COMPLY WITH FBC-ACCESS.
 SEC.604.7.
 8) SHT. A8.1 - ELEV. #1 & #4 - THE HEIGHT OF THE WATER
 CLOSET SHALL COMPLY WITH FBC-ACCESS. SEC.604.4.
 9) A8.1 - ELEV.#1 & #5 - GRAB BARS SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE.FBC-ACCESS. SEC. 609.4.
 10) AT LEAST ONE WASHING MACHINE AND DRYER SHALL COMPLY
 WITH FBC-ACCESS. SECS.214 & 611.
 11) SUBMIT DETAILS / ELEVATIONS FOR THE ACCESSIBLE
 SHOWERS.COMPLY WITH 2014 FBC-ACCESS. SEC. 608.
 12) SUBMIT A ROOF SCUPPER DETAIL FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 13) PROVIDE DETAILS FOR OVERFLOW DRAINAGE IN ACCORDANCE
 WITH THE 2014 FBC SEC.1503.4.2.1.
 14) THE PLUMBING PLANS SHALL BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL IN ACCORDANCE WITH THE FL.
 ADMIN. CODE RULE 61G15-23.001.
 15) SUBMIT A KITCHEN EQUIPMENT LIST FOR REVIEW. THE
 LIST SHALL SHOW WATER, DRAIN ANDD GAS SUPPLY SIZES TO
 THE EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1.
 16) SHT. P4.0 - SHOW ALL INDIRECT WASTES DRAINS ON THE
 PLUMBING RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 17) SHT. P4.0 - THE SANITARY RISER REFERS TO CIVIL
 DRAWINGS FOR THE CONTINUATION OF THE SANITARY AND
 GREASE LINES. THERE ARE NO CIVIL DRAWINGS IN THE PLANS.
 CLARIFY.
 18) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF THE
 SHOWERS IN THE TYPICAL PATIENT ROOMS.
 19) SUBMIT AN ENLARGED FLOOR PLAN FOR THE ACCESSIBLE
 TOILET ROOMS FOR THE STAFF/COMMON AREA TOILETS AND ALSO
 THE PATIENT TOILET ROOM INCLUDING THE ACCESSIBLE AND
 NON-ACCESSIBLE TOILET ROOMS. SHOW ALL FIXTURE
 CLEARANCES, INSIDE CLEAR DIMENSIONS OF THE SHOWER (L X
 W), HEIGHT AND LOCATION OF CONTROLS, ETC. COMPLY WITH
 FBC-ACCESS. SEC. 608 & 2014 FPC.
 20) SHT. P2.0 - KEYED NOTE #6 REFERS TO A TWO WAY
 CLEANOUT BUT IT IS SHOWN AT THE GAS LINE. CLARIFY.
 21) SHT. P3.0 - INDICATE THE SIZE OF THE EXPANSION TANK
 ON THE WATER HEATER DETAIL.
 22) SHT. P3.0 - THE RELIEF LINE FOR THE WATER HEATER
 SHALL TERMINATE IN ACCORDANCE WITH 2014 FPC SEC.504.6
 (1-13).
 23) THE WASHING MACHINES SHALL DISCHARGE INTO A 3 INCH
 WASTE STACK PER 2014 FBC-PLUMBING SEC.406.2.
 24) SHT. P4.0 - THE INSTALLATION OF BACK TO BACK WATER
 CLOSETS SHALL COMPLY WITH FPC SEC.706.3.
 25) SHT. P4.0 - THE IDENTIFICATION ( LOCATION) OF THE
 WATER CLOSET AND THE LAVATORY ON THE SANITARY RISER IN
 ROOM #3 ( 119 ) DOES NOT CORRELATE WITH THE FLOOR PLAN
 ON SHT. P2.0. THEY ARE REVERSED. THE SAME SITUATION
 OCCURS ON THE WATER RISER AND ALSO FOR ROOM #12 (129 ).
 26) CLEARLY IDENTIFY THE SECTIONS OF THE WATER AND
 SANITARY RISERS TO CORRELATE WITH THE RISER TAGS SHOWN
 ON P1.0 & P2.0. WPB AMEND. TO FBC SEC. 107.2.1.
 27) THE ICEMAKER AND JUICE MACHINE SHALL BE EQUIPPED
 WITH BACKFLOW PREVENTERS PER THE FPC SEC.608.3,
 608.16.10.
 28) SHT. P4.1 - SIZE THE WATER SUPPLY LINE TO THE SINK,
 ICE MAKER AND JUICE DISPENSER AND ALSO THE INDIVIDUAL
 LINES TO EACH APPLIANCE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-12-29 Cont ID  
Sent By shill Date 2016-12-29 Time 08:11 Rev Time 0.00
Received By shill Date 2016-12-29 Time 08:11 Sent To  
Notes
2016-12-29 08:11:51ROOF PERMIT APPLICATION, ASSEMBLY PROPOSED, AND
 ENGINEERING (IF APPLICABLE) REQUIRED
  
 THE FOLLOWING PRODUCT APPROVALS HAVE BEEN SUBMITTED AND
 REVIEWED:
  
 JOHNS MANVILLE BUILT UP ROOF OVER CONCRETE DECK
 PGT SS 3500 ALUMINUM STOREFRONT SYSTEM
 PGT SE 3550 ALUMINUM STOREFRONT ENTRANCE DOOR
  
 PROVISO: PRODUCT APPROVALS FOR COMPONENTS AND CLADDING
 WHICH ARE REQUIRED BUT NOT SUBMITTED AND REVIEWED PRIOR
 TO PERMIT ISSUANCE (FOR INSTANCE, THE BILCO ROOF HATCH,
 THE STEEL EXTERIOR DOOR) ARE REQUIRED TO BE SUBMITTED
 AND REVIEWED AS A REVISION PRIOR TO INSTALLATION.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By shill Date 2016-11-17 Time 07:05 Rev Time 0.00
Received By shill Date 2016-11-17 Time 07:05 Sent To  
Notes
2016-11-17 07:41:44****CORRECTIONS****
 ROOF PLAN REVIEW
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
  
 1. NOA #16-0413.11, JOHNS MANVILLE BUILT-UP ROOFING
 SYSTEMS OVER CONCRETE DECKS, WAS REVIEWED BY DOR AND
 SUBMITTED. THIS PRODUCT IS ALSO REFERENCED BY ARCHITECT
 ON SHEET A2.1.
  
 IN ORDER TO OBTAIN A "PASSED" ROOFING REVIEW STOP,
 INDICATE THE APPROVED ASSEMBLY PROPOSED.
  
 OR, UPON REQUEST, APPLICANT MAY ELECT TO DEFER THIS
 SUBMITTAL, AND AN "N" WILL BE ENTERED FOR THE ROOF
 REVIEW. THE PERMIT WILL BE ISSUED WITH PROVISO THAT,
 PRIOR TO INSTALLATION, THE ASSEMBLY PROPOSED, ALONG
 WITH ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE,
 BE SUBMITTED AS A REVISION (WITH APPLICABLE REVISION
 FEES).
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-02-09 Cont ID  
Sent By   Date 2017-02-09 Time   Rev Time 0.00
Received By pgreilic Date 2017-02-09 Time 10:20 Sent To  
Notes
2017-02-09 13:49:31PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By   Date 2016-12-15 Time   Rev Time 0.00
Received By pgreilic Date 2016-12-15 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2016-11-18 Time   Rev Time 0.00
Received By pgreilic Date 2016-11-18 Time 16:04 Sent To  
Notes
2016-11-18 16:05:16PAUL GREILICH, SENIOR PLANNER
 (561)-822-1443
 [email protected]