Plan Review Details - Permit 16110027
Plan Review Stops For Permit 16110027
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-02 Cont ID  
Sent By rmcdouga Date 2018-01-02 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2018-01-02 Time 11:34 Sent To  
Notes
2018-01-02 16:36:27APPROVED WITH EXCEPTIONS.
 TWO SETS OF PRODUCT APPROVALS FOR THE ASPHALT SHINGLE
 ROOF SHALL BE SUBMITTED AND APPROVED PRIOR TO ISSUANCE
 OF THE ROOF PERMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By rmcdouga Date 2017-11-16 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2017-11-15 Time 18:28 Sent To  
Notes
2017-11-16 10:54:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE ASPHALT
 ROOF SHINGLES AND THE WOOD FRONT DOOR SPECIFIED ON THE
 PLANS.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE 6'
 WIDE SLIDING GLASS DOOR ARE NON-IMPACT RATED AND
 REQUIRES THE DOORS TO HAVE IMPACT PROTECTION DEVICES
 INSTALLED. SUBMIT TWO SETS OF PRODUCT APPROVALS AND AN
 INSTALLATION SCHEDULE FOR THE IMPACT PROTECTION
 DEVICES. FBC 107.3.4
  
 3) THE ENERGY FORMS R405-2014 THAT WERE SUBMITTED ARE
 MISSING INFORMATION AND CONTAIN ERRORS. PLEASE CORRECT.
 FBC ENERGY CONSERVATION SECTION R405.4
 - THE FORMS ARE REQUIRED TO BE SIGNED BY THE
 OWNER/AGENT.
 - THE OWNER'S NAME SHOULD BE DANNY JONES.
 - BUILDER'S NAME IS MISSING.
 - JURISDICTION IS MISSING (604700).
 - THE ORIENTATION IS WRONG THE FRONT DOOR FACES EAST,
 NOT NORTH.
 - THE WINDOW AREA AND ORIENTATIONS DO NOT MATCH THE
 PLANS.
 - THE GLAZED AREA OF THE 6' WIDE SLIDING GLASS DOOR IS
 NOT SHOWN WITH THE WINDOWS.
 - IN ORDER TO USE THE 1:300 VENT RATIO THE PLANS MUST
 COMPLY WITH EXCEPTION NUMBER (2) OF FBC-R806.2. PROVIDE
 CALCULATIONS AND SHOW THE REQUIRED 40 PERCENT BUT NOT
 MORE THAN 50 PERCENT OF THE REQUIRED VENTILATING AREA
 PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF
 THE ATTIC ON THE PLANS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By rmcdouga Date 2016-12-05 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2016-12-02 Time 17:11 Sent To  
Notes
2016-12-02 19:07:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 2) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION. FOR EXAMPLE THE GENERAL NOTE ON SHEET
 S-4.
  
 3) THE FOOTING NOTES ON S-3 FOR WALL SECTION 2 ARE NOT
 CONSITENT WITH THE FOUNDATION SCHEDULE ON S-1. PLEASE
 CORRECT. FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE. FOOTINGS AT EXTERIOR WALLS ARE REQUIRED TO
 BE 12 INCHES BELOW GRADE PER FBC R403.1.4.
  
 4) FBC R301.2.1 WIND DESIGN CRITERIA. SPECIFY THE
 EXPOSURE CATEGORY AND THE COMPONENT AND CLADDING
 PRESSURES ON THE PLANS.
  
 5) THE KITCHEN WINDOW IS NOT SHOWN ON THE SOUTH
 ELEVATION ON SHEET A-2 OR ON SHEETS S-1, S-2, M-1, E-1
 OR WP-1. FBC 107.2.1
  
 6) THE WINDOW AND DOOR ID TAG LETTERS AND NUMBERS ON
 THE ELEVATIONS DO NOT MATCH THE SCHEDULES ON SHEETS A-1
 AND A-2. FBC 107.2.1
  
 7) THE WOOD BEAM FOR THE FRONT PORCH IS SPECIFIED AS
 (3) 2 X 8S ON S-2 AND (2) 2 X 8S ON S-3. FBC 107.2.1
  
 8) THE ROOF FASTENING SPECIFIED ON S-2 IS NOT
 CONSISTENT WITH THE NOTE ON WALL SECTION 2 ON S-3. FBC
 107.2.1
  
 9) ON SHEET S-2 THE LINTEL ID TAGS PC 1, PC 2, ETC. DO
 NOT HAVE A CORRESPONDING LINTEL SCHEDULE. FBC 107.2.1
  
 10) SOME OF THE OPENINGS ARE MISSING THE LINTEL ID
 TAGS. FBC 107.2.1
  
 11) THE DOOR SCHEDULE SPECIFIES THE EXTERIOR DOORS AS
 WOOD AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 FOR METAL DOORS. DCA RULE 9N-3
  
 12) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ASPHALT ROOF SHINGLES AND THE SLIDING GLASS DOORS.
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-12 Cont ID  
Sent By jpearson Date 2017-11-12 Time 12:13 Rev Time 0.00
Received By jpearson Date 2017-11-12 Time 12:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 14:38 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 13:13 Sent To  
Notes
2016-11-09 14:39:24REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO"S
  
 1] ADD AN INTERSYSTEM BONDING TERMINAL TO THE RISER
 DIAGRAM GROUNDING DETAIL. NEC 250.94
  
 2] FBC-R SECTION 315.1 CO/ALARM REQUIRED BECAUSE OF AN
 ATTACHED GARAGE WITHIN 10? OF A SLEEPING ROOM.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-02 Cont ID  
Sent By rmcdouga Date 2018-01-02 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2017-12-27 Time 11:39 Sent To I
Notes
2017-12-27 11:40:54RMCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-01 Cont ID  
Sent By ajones Date 2017-12-01 Time 15:50 Rev Time 0.00
Received By ajones Date 2017-11-03 Time 12:56 Sent To PC
Notes
2017-11-06 12:56:35R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-05 Cont ID  
Sent By rmcdouga Date 2016-12-05 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2016-11-01 Time 16:03 Sent To  
Notes
2016-11-02 16:04:08R29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-01-02 Cont ID  
Sent By rmcdouga Date 2018-01-02 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2018-01-02 Time 11:34 Sent To  
Notes
2018-01-02 11:35:43MU-2017-35520, PAID $2516.60

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-02 Cont ID  
Sent By rmcdouga Date 2016-12-02 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2016-12-02 Time 12:51 Sent To  
Notes
2016-12-02 12:56:59BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. NEEDED
 TO VERIFY THAT IMPACT FEES WERE PAID.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-02 Cont ID  
Sent By rmcdouga Date 2018-01-02 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2018-01-02 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By rmcdouga Date 2017-11-16 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2017-11-15 Time 18:32 Sent To I
Notes
2017-11-16 15:52:43PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE
 ON THE MECHANICAL PLANS ARE REQUIRED TO MATCH THE
 EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION
 - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL
 S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING
 CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR
 THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. (ONLY ONE SET WAS SUBMITTED. SUBMIT AN
 ADDITIONAL SET OF SIZING CALCULATIONS.)
  
 2) THE EQUIPMENT SIZING CALCULATIONS, INDICATE 10
 PEOPLE. THIS IS TOO MANY PEOPLE FOR A THREE BEDROOM
 RESIDENCE. PLEASE CORRECT.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-02 Cont ID  
Sent By rmcdouga Date 2016-12-02 Time 16:33 Rev Time 0.00
Received By rmcdouga Date 2016-12-02 Time 16:33 Sent To  
Notes
2016-12-02 17:11:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS WITH
 CALCULATION DATA. THERE WERE THREE OF THESE SUBMITTED
 AND THE ONLY ONE THAT WAS SIGNED BY THE PREPARER AND
 THE OWNER/AGENT WAS DIFFERENT FROM THE OTHER TWO. THE
 ORIENTATION OF THE DWELLING IS INCORRECT ON ALL OF THEM
 ( THE FRONT DOOR FACES EAST ). IN ORDER TO TAKE THE
 CEILING FAN CREDIT THE FANS ARE REQUIRED TO BE SIZED
 ACCORDING TO TABLE R405.7.6 AND THE SIZES SPECIFIED ON
 THE PLANS. ALL OF THE ENERGY FORM INFORMATION IS
 REQUIRED TO MATCH THE PLANS. FBC ENERGY CONSERVATION -
 SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION. THE
 BUILDING?S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE
 ON THE MECHANICAL PLANS ARE REQUIRES TO MATCH THE
 EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION
 - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL
 S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE
 WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING
 CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR
 THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-15 Cont ID  
Sent By gjohnson Date 2017-11-15 Time 17:59 Rev Time 0.00
Received By gjohnson Date 2017-11-15 Time 16:55 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-20 Cont ID  
Sent By tklarge Date 2016-11-20 Time 04:26 Rev Time 0.00
Received By tklarge Date 2016-11-20 Time 04:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-01-02 Cont ID  
Sent By rmcdouga Date 2018-01-02 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2018-01-02 Time 16:32 Sent To  
Notes
2018-01-02 16:34:04NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ASPHALT
 SHINGLE ROOF. THE PRODUCT APPROVALS SHALL BE SUBMITTED
 AND APPROVED PRIOR TO ISSUANCE OF THE ROOFING PERMIT.

Review Stop Z ZONING
Rev No 2 Status P Date 2017-12-01 Cont ID  
Sent By LL Date 2017-12-01 Time 15:48 Rev Time 0.00
Received By ajones Date 2017-11-27 Time 16:07 Sent To  
Notes
2017-12-01 15:50:2712-1-17- APPROVED WITH THE PROVISION THAT A SEPERATE
 PERMIT IS REQUIRED FOR LANDSCAPING, FENCE/WALLS AND
 DRIVEWAY/CURB CUTS
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By njwira Date 2016-11-09 Time 18:00 Rev Time 0.00
Received By njwira Date 2016-11-09 Time 15:57 Sent To  
Notes
2016-11-09 17:56:0711/9/16- FAILED
  
 SF-14 SINGLE FAMILY HIGH DENSITY RESIDENTIAL
  
 FAILED
 1. TREE ALTERATION PERMIT REQUIRED
 2. LANDSCAPE PERMIT REQUIRED
 3. DRIVEWAY PERMIT REQUIRED SEPORATELY.
  
 PASSED
 1. ONE KITCHEN MAKES THIS ONE(1)UNIT
 2. 14FT. HIGH HOUSE MEETS THE 30FT. HEIGHT LIMIT
 3. A/C UNIT IS NOT IN A REQUIRED SETBACK
 4. ROOF DOESN'T PROJECT INTO A REQUIRED SETBACK
 5. FRONT SETBACK IS 25FT. MEETING 25FT. SETBACK
 REQUIREMENT.
 6. REAR SETBACK IS 9.03FT. MEETING THE 10% OF 90FT.
 SETBACK OF 9FT.
 7. HOUSE MEETS 5FT. MINIMUM 15FT. TOTAL SIDE SETBACK.
  
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  