| Plan Review Stops For Permit 16110027 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-02 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-02 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-01-02 16:36:27 | APPROVED WITH EXCEPTIONS. | | | TWO SETS OF PRODUCT APPROVALS FOR THE ASPHALT SHINGLE | | | ROOF SHALL BE SUBMITTED AND APPROVED PRIOR TO ISSUANCE | | | OF THE ROOF PERMIT. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-11-16 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-11-15 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2017-11-16 10:54:27 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE ASPHALT | | | ROOF SHINGLES AND THE WOOD FRONT DOOR SPECIFIED ON THE | | | PLANS. | | | | | | 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE 6' | | | WIDE SLIDING GLASS DOOR ARE NON-IMPACT RATED AND | | | REQUIRES THE DOORS TO HAVE IMPACT PROTECTION DEVICES | | | INSTALLED. SUBMIT TWO SETS OF PRODUCT APPROVALS AND AN | | | INSTALLATION SCHEDULE FOR THE IMPACT PROTECTION | | | DEVICES. FBC 107.3.4 | | | | | | 3) THE ENERGY FORMS R405-2014 THAT WERE SUBMITTED ARE | | | MISSING INFORMATION AND CONTAIN ERRORS. PLEASE CORRECT. | | | FBC ENERGY CONSERVATION SECTION R405.4 | | | - THE FORMS ARE REQUIRED TO BE SIGNED BY THE | | | OWNER/AGENT. | | | - THE OWNER'S NAME SHOULD BE DANNY JONES. | | | - BUILDER'S NAME IS MISSING. | | | - JURISDICTION IS MISSING (604700). | | | - THE ORIENTATION IS WRONG THE FRONT DOOR FACES EAST, | | | NOT NORTH. | | | - THE WINDOW AREA AND ORIENTATIONS DO NOT MATCH THE | | | PLANS. | | | - THE GLAZED AREA OF THE 6' WIDE SLIDING GLASS DOOR IS | | | NOT SHOWN WITH THE WINDOWS. | | | - IN ORDER TO USE THE 1:300 VENT RATIO THE PLANS MUST | | | COMPLY WITH EXCEPTION NUMBER (2) OF FBC-R806.2. PROVIDE | | | CALCULATIONS AND SHOW THE REQUIRED 40 PERCENT BUT NOT | | | MORE THAN 50 PERCENT OF THE REQUIRED VENTILATING AREA | | | PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF | | | THE ATTIC ON THE PLANS. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-05 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-02 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2016-12-02 19:07:22 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY | | | SEPARATE BUILDING OR AN ADDITION TO AN EXISTING | | | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS | | | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR | | | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER | | | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE | | | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL | | | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH | | | ROOM USED FOR SLEEPING PURPOSES. | | | | | | 2) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. | | | THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE | | | 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT | | | DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC | | | FIFTH EDITION. FOR EXAMPLE THE GENERAL NOTE ON SHEET | | | S-4. | | | | | | 3) THE FOOTING NOTES ON S-3 FOR WALL SECTION 2 ARE NOT | | | CONSITENT WITH THE FOUNDATION SCHEDULE ON S-1. PLEASE | | | CORRECT. FBC-R404.1.6 HEIGHT ABOVE FINISHED GRADE. | | | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND | | | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT | | | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY | | | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) | | | ELSEWHERE. FOOTINGS AT EXTERIOR WALLS ARE REQUIRED TO | | | BE 12 INCHES BELOW GRADE PER FBC R403.1.4. | | | | | | 4) FBC R301.2.1 WIND DESIGN CRITERIA. SPECIFY THE | | | EXPOSURE CATEGORY AND THE COMPONENT AND CLADDING | | | PRESSURES ON THE PLANS. | | | | | | 5) THE KITCHEN WINDOW IS NOT SHOWN ON THE SOUTH | | | ELEVATION ON SHEET A-2 OR ON SHEETS S-1, S-2, M-1, E-1 | | | OR WP-1. FBC 107.2.1 | | | | | | 6) THE WINDOW AND DOOR ID TAG LETTERS AND NUMBERS ON | | | THE ELEVATIONS DO NOT MATCH THE SCHEDULES ON SHEETS A-1 | | | AND A-2. FBC 107.2.1 | | | | | | 7) THE WOOD BEAM FOR THE FRONT PORCH IS SPECIFIED AS | | | (3) 2 X 8S ON S-2 AND (2) 2 X 8S ON S-3. FBC 107.2.1 | | | | | | 8) THE ROOF FASTENING SPECIFIED ON S-2 IS NOT | | | CONSISTENT WITH THE NOTE ON WALL SECTION 2 ON S-3. FBC | | | 107.2.1 | | | | | | 9) ON SHEET S-2 THE LINTEL ID TAGS PC 1, PC 2, ETC. DO | | | NOT HAVE A CORRESPONDING LINTEL SCHEDULE. FBC 107.2.1 | | | | | | 10) SOME OF THE OPENINGS ARE MISSING THE LINTEL ID | | | TAGS. FBC 107.2.1 | | | | | | 11) THE DOOR SCHEDULE SPECIFIES THE EXTERIOR DOORS AS | | | WOOD AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE | | | FOR METAL DOORS. DCA RULE 9N-3 | | | | | | 12) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE ASPHALT ROOF SHINGLES AND THE SLIDING GLASS DOORS. | | | | | | 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-11-12 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2017-11-12 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2017-11-12 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-11-09 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-11-09 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2016-11-09 14:39:24 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO"S | | | | | | 1] ADD AN INTERSYSTEM BONDING TERMINAL TO THE RISER | | | DIAGRAM GROUNDING DETAIL. NEC 250.94 | | | | | | 2] FBC-R SECTION 315.1 CO/ALARM REQUIRED BECAUSE OF AN | | | ATTACHED GARAGE WITHIN 10? OF A SLEEPING ROOM. | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-02 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-12-27 |
Time |
11:39 |
Sent To |
I |
|
| Notes |
| 2017-12-27 11:40:54 | RMCDOUGAL'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2017-12-01 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2017-11-03 |
Time |
12:56 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-12-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-05 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-11-01 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-02 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-02 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-01-02 11:35:43 | MU-2017-35520, PAID $2516.60 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-12-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-02 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-02 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2016-12-02 12:56:59 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. NEEDED | | | TO VERIFY THAT IMPACT FEES WERE PAID. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-02 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-02 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2017-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2017-11-16 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2017-11-15 |
Time |
18:32 |
Sent To |
I |
|
| Notes |
| 2017-11-16 15:52:43 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS. | | | THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE | | | ON THE MECHANICAL PLANS ARE REQUIRED TO MATCH THE | | | EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION | | | - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL | | | S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE | | | WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING | | | CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR | | | THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT | | | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT | | | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. (ONLY ONE SET WAS SUBMITTED. SUBMIT AN | | | ADDITIONAL SET OF SIZING CALCULATIONS.) | | | | | | 2) THE EQUIPMENT SIZING CALCULATIONS, INDICATE 10 | | | PEOPLE. THIS IS TOO MANY PEOPLE FOR A THREE BEDROOM | | | RESIDENCE. PLEASE CORRECT. | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-12-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-12-02 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-12-02 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2016-12-02 17:11:12 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS WITH | | | CALCULATION DATA. THERE WERE THREE OF THESE SUBMITTED | | | AND THE ONLY ONE THAT WAS SIGNED BY THE PREPARER AND | | | THE OWNER/AGENT WAS DIFFERENT FROM THE OTHER TWO. THE | | | ORIENTATION OF THE DWELLING IS INCORRECT ON ALL OF THEM | | | ( THE FRONT DOOR FACES EAST ). IN ORDER TO TAKE THE | | | CEILING FAN CREDIT THE FANS ARE REQUIRED TO BE SIZED | | | ACCORDING TO TABLE R405.7.6 AND THE SIZES SPECIFIED ON | | | THE PLANS. ALL OF THE ENERGY FORM INFORMATION IS | | | REQUIRED TO MATCH THE PLANS. FBC ENERGY CONSERVATION - | | | SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION. THE | | | BUILDING?S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS. | | | THE ENERGY COMPLIANCE FORMS AND THE EQUIPMENT SCHEDULE | | | ON THE MECHANICAL PLANS ARE REQUIRES TO MATCH THE | | | EQUIPMENT SIZING CALCULATIONS. FBC ENERGY CONSERVATION | | | - SECT. 403.6.1 EQUIPMENT SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH ACCA MANUAL | | | S BASED ON THE EQUIPMENT LOADS CALCULATED IN ACCORDANCE | | | WITH MANUAL J OR OTHER APPROVED HEATING AND COOLING | | | CALCULATION METHODOLOGIES, BASED ON BUILDING LOADS FOR | | | THE DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION 302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT | | | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT | | | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-11-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-11-15 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-11-15 |
Time |
16:55 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-11-20 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-11-20 |
Time |
04:26 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-11-20 |
Time |
04:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-01-02 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-01-02 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2018-01-02 16:34:04 | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ASPHALT | | | SHINGLE ROOF. THE PRODUCT APPROVALS SHALL BE SUBMITTED | | | AND APPROVED PRIOR TO ISSUANCE OF THE ROOFING PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-12-01 |
|
|
Cont ID |
|
| Sent By |
LL |
Date |
2017-12-01 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2017-11-27 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2017-12-01 15:50:27 | 12-1-17- APPROVED WITH THE PROVISION THAT A SEPERATE | | | PERMIT IS REQUIRED FOR LANDSCAPING, FENCE/WALLS AND | | | DRIVEWAY/CURB CUTS | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-11-09 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-11-09 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2016-11-09 17:56:07 | 11/9/16- FAILED | | | | | | SF-14 SINGLE FAMILY HIGH DENSITY RESIDENTIAL | | | | | | FAILED | | | 1. TREE ALTERATION PERMIT REQUIRED | | | 2. LANDSCAPE PERMIT REQUIRED | | | 3. DRIVEWAY PERMIT REQUIRED SEPORATELY. | | | | | | PASSED | | | 1. ONE KITCHEN MAKES THIS ONE(1)UNIT | | | 2. 14FT. HIGH HOUSE MEETS THE 30FT. HEIGHT LIMIT | | | 3. A/C UNIT IS NOT IN A REQUIRED SETBACK | | | 4. ROOF DOESN'T PROJECT INTO A REQUIRED SETBACK | | | 5. FRONT SETBACK IS 25FT. MEETING 25FT. SETBACK | | | REQUIREMENT. | | | 6. REAR SETBACK IS 9.03FT. MEETING THE 10% OF 90FT. | | | SETBACK OF 9FT. | | | 7. HOUSE MEETS 5FT. MINIMUM 15FT. TOTAL SIDE SETBACK. | | | | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|