Plan Review Details - Permit 16110022
Plan Review Stops For Permit 16110022
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-16 Cont ID  
Sent By mvaldes Date 2016-11-16 Time 15:55 Rev Time 0.00
Received By mvaldes Date 2016-11-16 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By mvaldes Date 2016-11-03 Time 18:17 Rev Time 0.00
Received By mvaldes Date 2016-11-03 Time 18:17 Sent To  
Notes
2016-11-03 18:18:26REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PLEASE ADDRESS FIRE COMMENTS TO PASS ELECTRICAL
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-15 Cont ID  
Sent By pleduc Date 2016-11-15 Time   Rev Time 0.00
Received By pleduc Date 2016-11-15 Time 16:57 Sent To E
Notes
2016-11-15 17:07:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL COMPLY WITH ALL THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS:
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By pleduc Date 2016-11-03 Time   Rev Time 0.00
Received By pleduc Date 2016-11-03 Time 10:44 Sent To E
Notes
2016-11-03 10:57:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) A FLOOR PLAN INDICATING WHICH 5 DOORS AND THEIR
 LOCATIONS WAS NOT PROVIDED.
  
 PLEASE PROVIDE A FLOOR PALN INDICATING THE PROPOSED
 DOORS.
  
  
  
 2) ELECTRICAL WIRING DETAILS NOT PROVIDED.
  
 PLEASE PROVIDE POWER SOURCE AND WIRING DETAILS.
  
  
 3) THERE IS NO INDICATION OF AN EXISITNG FIRE ALARM AND
 IF ANY DOORS WILL BE TIED - IN TO IT.
  
 PLEASE PROVIDE THE APPLICANLE NOTE.
  
 ANY TIE - IN TO THE FIRE ALARM SHALL BE DONE BY
 CERITIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP
 DRAWINGS.
  
  
  
 4) PLEASE PROVIDE DETAILS ON EXITING OUT EACH DOOR.
 EGRESS SHALL NOT BE IMPAIRED AND SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-16 Cont ID  
Sent By mvaldes Date 2016-11-16 Time 15:56 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 11:58 Sent To  
Notes
2016-11-09 11:58:42RESUB ROUTED TO PLEDUC VIA FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-03 Cont ID  
Sent By mvaldes Date 2016-11-03 Time 18:18 Rev Time 0.00
Received By mvaldes Date 2016-11-01 Time 14:35 Sent To  
Notes
2016-11-01 14:35:59ROUTED TO FIRE INBOX