Plan Review Details - Permit 16110007
Plan Review Stops For Permit 16110007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-25 Cont ID  
Sent By shill Date 2017-01-25 Time 07:58 Rev Time 0.00
Received By shill Date 2017-01-25 Time 07:03 Sent To M
Notes
2017-01-25 08:02:54NOTE: SPEC SHEET FOR STOTHERM CI CLASSIC PROVIDED; ASTM
 E 84 FLAME SPREAD 25, FBC 1403.5, ALSO TESTED NFPA 285
 TO 12"

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By shill Date 2016-11-16 Time 14:11 Rev Time 0.00
Received By shill Date 2016-11-16 Time 06:26 Sent To  
Notes
2016-11-16 14:12:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE IMPACT FEE REVIEW; REVISE PLAN TO INCLUDE
 ADDITION SQUARE FOOT TOTALS.
  
 2. PER MECHANICAL REVIEWER (CHRIS COLE, [email protected]),
 HOW WILL THE INCREASE IN CONDITIONED SPACE AFFECT THE
 EXISTING MECHANICAL UNITS? HAVE CALCULATIONS BEEN
 PERFORMED? A MECHANICAL REVIEW HAS NOT BEEN DONE AT
 THIS TIME AS NO INFORMATION WAS PROVIDED, BUT A
 MECHANICAL REVIEW WILL BE DONE IN 2ND REVIEW CYCLE.
  
 3. REVISE PLAN TO STATE METHOD OF COMPLIANCE ELECTED BY
 APPLICANT, FBC EB 301.1.
  
 4. REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER
 11, ADDITIONS.
  
 5. ENERGY CALCS REQUIRED, FBC EC 103.1.1.
  
 6. PROVIDE INFORMATION REGARDING THE EIFS COMPLIANCE
 RE: COMBUSTIBILITY, FBC 602.2 (SUCH AS TEST REPORT,
 SPEC SHEET).
  
 7. SEE THRESHOLD REVIEW.
  
 8. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC 107.
  
 9. FBC 449.1.1, SEE FS 553.80(C):?IN ADDITION TO THE
 REQUIREMENTS OF S. 553.79 AND THIS SECTION, FACILITIES
 SUBJECT TO THE PROVISIONS OF CHAPTER 395 AND PARTS II
 AND VIII OF CHAPTER 400 SHALL HAVE FACILITY PLANS
 REVIEWED AND CONSTRUCTION SURVEYED BY THE STATE AGENCY
 AUTHORIZED TO DO SO UNDER THE REQUIREMENTS OF CHAPTER
 395 AND PARTS II AND VIII OF CHAPTER 400 AND THE
 CERTIFICATION REQUIREMENTS OF THE FEDERAL GOVERNMENT.
 FACILITIES SUBJECT TO THE PROVISIONS OF PART IV OF
 CHAPTER 400 MAY HAVE FACILITY PLANS REVIEWED AND SHALL
 HAVE CONSTRUCTION SURVEYED BY THE STATE AGENCY
 AUTHORIZED TO DO SO UNDER THE REQUIREMENTS OF PART IV
 OF CHAPTER 400 AND THE CERTIFICATION REQUIREMENTS OF
 THE FEDERAL GOVERNMENT.
  
 PLEASE ACKNOWLEDGE REQUIREMENT.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-17 Cont ID  
Sent By pleduc Date 2017-01-17 Time   Rev Time 0.00
Received By pleduc Date 2017-01-17 Time 09:37 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-08 Cont ID  
Sent By pleduc Date 2016-11-08 Time   Rev Time 0.00
Received By pleduc Date 2016-11-07 Time 10:13 Sent To B
Notes
2016-11-07 11:27:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) ALL LIFE SAFETY SHEETS - UNDER THE LIFE SAFETY
 GENERAL NOTES IT INDICATES "NO DEVICES OR EXIT OPENINGS
 ARE ALTERED BY THIS PROJECT." HOWEVER, THERE ARE AD
 SHEETS INDICATING SPECIFIC EXITS DOORS BEING REPLACED
 WITH BLOCKED EXIT SIGNS AND REROUTING.
  
 PLEASE CLARIFY AND/OR CORRECT WITH AN APPLICABLE NOTE.
  
  
  
 2) SHEETS AD 2.1 & 3.1 ARE NOT INDICATED WITH ANY FIRE
 SPRINKLER PROTECTION COMMENTS.
  
 WILL THERE BE ANY SPRINKLER HEADS AFFECTED BY THE
 CEILING AREA WORK? IF SO ALL WORK SHALL BE DONE BY
 CERITIFED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE CLARIFY AND/OR CORRECT WITH THE APPLICABLE NOTE.
  
  
  
 3) SHEET A 1.0 - NOTE # 7 INDICATES THAT EXIT SIGNS AND
 EXIT WILL BE BLOCKED WHEN DOORS ARE REPLACED.
  
 PLEASE PROVIDE THE LIFE SAFETY PLANS TO INCLUDE THE
 ALTERNATE EXITS AND APPLICABLE TEMPORARY EXIT SIGNS
 LOCATIONS, WHEN AND WERE THE EXITS WILL BE BLOCKED.
  
  
  
 4) SHEET A1.0 & A 7.1 - THERE ARE DOORS INDICATED AS
 BEING REPLACED; TG001 30.3.N, TG272 31.1.N, TG305
 31.3.N, TG013 31.3.N, TG324 1.1.N, TG055 1.1.N, AND
 TG049 1.1.N. ALL ARE INDICATED AS HAVING NO RATING.
  
 IT APPEARS THAT THESE DOORS ARE IN LOCATIONS THAT
 REQUIRE FIRE RATING. PLEASE REVIEW THE ENGINEER OF
 RECORD SPECS TO ENSURE THAT THEY ARE NOT REQUIRED TO BE
 RATED.
  
  
 5) SHEET A1.0 & A 7.1 - THERE ARE THREE (3) DOORS
 INDICATED AS TG001 30.3.N. THE DOOR TYPES SCHEDULE,
 UNDER SPECIAL DOOR TYPES, INDICATES DOOR TYPE 30 AS A
 SLIDING DOOR. HOWEVER, TWO (2) OF THE TG001 DOORS ARE
 DOUBLE SWING DOORS.
  
 PLEASE REVIEW, CLARIFY AND /OR CORRECT.
  
  
  
 6) 5) SHEET A1.0 & A 7.1 - THERE IS A DOOR SET
 INDICATED AS TG272 31.1.N. THE DOOR TYPES SCHEDULE,
 UNDER SPECIAL DOOR TYPES, INDICATES DOOR TYPE 31 AS A
 SLIDING DOOR. HOWEVER, THE TG272 DOOR IS A DOUBLE SWING
 DOOR.
  
 PLEASE REVIEW, CLARIFY AND /OR CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-30 Cont ID  
Sent By ccole Date 2017-01-30 Time 17:17 Rev Time 0.00
Received By ccole Date 2017-01-11 Time 11:13 Sent To  
Notes
2017-01-25 09:25:411/25 TO MECH BOX
  
  
  
  
2017-01-12 11:13:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-16 Cont ID  
Sent By shill Date 2016-11-16 Time 14:37 Rev Time 0.00
Received By shill Date 2016-11-01 Time 16:18 Sent To  
Notes
2016-11-02 16:20:07ROUTED TO ZONING INBOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2017-01-25 Cont ID  
Sent By shill Date 2017-01-25 Time 09:32 Rev Time 0.00
Received By shill Date 2017-01-25 Time 09:31 Sent To  
Notes
2017-01-25 09:32:36MU 2016 30826, $17,302.28
  
 RECEIPT SENT TO FILENET VIA EMAIL
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-01-24 Cont ID  
Sent By shill Date 2017-01-24 Time 17:57 Rev Time 0.00
Received By shill Date 2017-01-24 Time 17:57 Sent To  
Notes
2017-01-24 17:58:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 MU 2016 30826, $17,302.28
  
 THE PLANS HAVE BEEN STAMPED, BUT THE RECEIPT SHOWING
 THAT FEES HAVE BEEN PAID WAS NOT PROVIDED.
  
 THE RECEIPT MAY BE SENT TO ME VIA EMAIL. AN EMAIL HAS
 BEEN SENT TO THE CONTRACTOR.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By shill Date 2016-11-16 Time 12:17 Rev Time 0.00
Received By shill Date 2016-11-16 Time 12:17 Sent To  
Notes
2016-11-16 12:33:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS APPEARS TO BE AN INCREASE IN HABITABLE SPACE
 (UNDER AIR SQUARE FOOT AREA). REVISE PLAN TO PROVIDE
 THE EXISTING SQUARE FOOT AREA (EACH FLOOR AND TOTAL),
 PROPOSED ADDITION (EACH FLOOR AND TOTAL), NEW TOTALS
 (EACH FLOOR AND TOTAL).
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS STAMPED BY THE COUNTY ARE TO BE SUBMITTED AS
 WELL AS THE RECEIPT SHOWING THAT FEES DUE, IF
 APPLICABLE, WERE PAID.
  
 PLEASE CONTACT 561-233-5025 FOR MORE INFORMATION.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By ccole Date 2017-01-30 Time 17:17 Rev Time 0.00
Received By ccole Date 2017-01-30 Time 17:16 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-11-16 Cont ID  
Sent By shill Date 2016-11-16 Time 07:33 Rev Time 0.00
Received By shill Date 2016-11-16 Time 07:33 Sent To  
Notes
2016-11-16 07:37:33THIS VERY LARGE PARCEL HAS A SMALL PORTION ON THE WEST
 SIDE OF THE LOT LOCATED IN THE SFHA. THE STRUCTURE
 UNDER THIS PERMIT, THE MAIN BUILDING (HOSPITAL), IS NOT
 LOCATED IN THE SFHA. SEE FIRMETTE. THE PERMIT FILE
 FLOOD FIELD IS NOW CHANGED TO C ZONE RATHER THAN AH
 17.0.
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2017-01-27 Cont ID  
Sent By shill Date 2017-01-27 Time 17:18 Rev Time 0.00
Received By shill Date 2017-01-25 Time 06:25 Sent To  
Notes
2017-01-25 06:44:08*****RESIDENT INSPECTOR****
  
 SIGNED BY OWNER'S REP, GREG DALTON
 CONTRACTOR, WESTRBOOKE CORPORATION, ROBERT F LAKE JR
  
 GFA INTERNATIONAL
 HECTOR F VERGARA, PE 25764, SI 283
 MIKE ADAIR, BN 3227
 MARK SHARMAN, BN 4742
 JENNINGS HILL, BN 3142
 NOEL WOODALL, BN 2505
  
 OK PER KC
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-11-30 Cont ID  
Sent By shill Date 2016-11-30 Time 14:04 Rev Time 0.00
Received By shill Date 2016-11-30 Time 14:04 Sent To  
Notes
2016-11-30 14:06:52CONFIRMED WITH KC THAT, DUE TO THE SCOPE OF THIS
 PROJECT, ALTHOUGH THIS IS NOT THRESHOLD (NO STRUCTURAL
 WORK), A RESIDENT INSPECTOR IS REQUIRED.
  
 CONTRACTOR IS TO CONTACT SAMANTHA HILL (561-805-6724)
 OR KEN CONRAD (561-805-6666) IF HE WOULD LIKE TO
 DISCUSS
  
 PROVIDE:
 RESIDENT INSPECTOR AGREEMENT SIGNED BY ALL PARTIES
 INSPECTOR RESUME
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By shill Date 2016-11-16 Time 14:12 Rev Time 0.00
Received By shill Date 2016-11-16 Time 14:12 Sent To  
Notes
2016-11-16 14:16:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CLARIFY; DOES APPLICANT CONSIDER THIS A THRESHOLD
 BUILDING, FS552.79? IF YES, HAVE ENGINEER ADD THE
 STATEMENT REQUIRED BY FS 553.79(7)(D) AND PROVIDE A
 THRESHOLD INSPECTION PLAN.
  
 2. IF IT IS AGREED THAT THIS IS A THRESHOLD PROJECT,
 COMPLETE THE SPECIAL INSPECTOR AGREEMENT. THIS WAS SENT
 VIA EMAIL TO [email protected].
  
 3. PROVIDE RESUMES FOR THE CONTRACTOR, INSPECTORS, SI,
 AND SI FIRM.
  
 4. THRESHOLD DOCUMENTS MAY BE SENT VIA EMAIL FOR
 PRELIMINARY REVIEW.
  
 5. IF APPLICANT DISAGREES THAT THIS IS THRESHOLD,
 PLEASE CONTACT ME TO DISCUSS. A RESIDENT INSPECTOR MAY
 BE REQUIRED DEPENDING ON APPLICANT'S SCHEDULE AND THE
 BUILDING DEPARTMENT'S ABILITY TO COMPLETE INSPECTIONS
 TO MAINTAIN THE SCHEDULE. ALL OF THE SAME INFORMATION
 IS REQUIRED FOR A RESIDENT INSPECTOR PROJECT, BUT THE
 RESIDENT INSPECTOR AGREEMENT IS TO BE COMPLETED.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-04 Cont ID  
Sent By njwira Date 2016-11-04 Time 14:23 Rev Time 0.00
Received By njwira Date 2016-11-04 Time 14:23 Sent To FIRE
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved