Plan Review Details - Permit 16100936
Plan Review Stops For Permit 16100936
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-04 Cont ID  
Sent By ccole Date 2016-11-07 Time 08:26 Rev Time 0.00
Received By wjolin Date 2016-11-04 Time 11:55 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 15:45 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 10:56 Sent To  
Notes
2016-12-07 10:56:47RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-28 Cont ID  
Sent By ccole Date 2016-11-28 Time 08:42 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 07:50 Sent To  
Notes
2016-11-23 07:50:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 16:57 Rev Time 0.00
Received By ccole Date 2016-11-09 Time 11:43 Sent To  
Notes
2016-11-14 11:43:35RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 08:26 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 13:42 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-12-07 Cont ID  
Sent By ccole Date 2016-12-07 Time 15:45 Rev Time 0.00
Received By ccole Date 2016-12-07 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-28 Cont ID  
Sent By ccole Date 2016-11-28 Time 08:42 Rev Time 0.00
Received By ccole Date 2016-11-28 Time 08:42 Sent To  
Notes
2016-11-28 08:50:203RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100936
 11/289/16
  
 1) THE LETTER FROM KAMM ENGINEERING DOES NOT
 SPECIFICALLY ADDRESS THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE MAKEUP AIR TEMPERATURE AND THE AIR IN THE
 CONDITIONED SPACE, AND NO EVIDENCE HAS BEEN PROVIDED TO
 VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 16:56 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 16:56 Sent To  
Notes
2016-11-14 17:14:462ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100936
 11/14/16
  
 1) DOCUMENTATION IS REQUIRED TO VERIFY DESIGN CONDITION
 OF 80 DEGREES AMBIENT TEMPERATURE IN THE COOKING AREA.
 PLEASE SEE KAMM ENGINEERING PLANS AND CALCULATIONS
 UNDER PERMIT #15090611 FOR THE MARY FISHER STUDIO.
 OARTU-1 IS THE SYSTEM SUPPLYING CONDITIONED AIR TO THE
 COOKING AREA. REFER TO THE ENGINEER'S CALCULATIONS FOR
 ENTERING AND LEAVING TEMPERATURES AND THE
  
 SYSTEM PERFORMANCE DATA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By ccole Date 2016-11-07 Time 07:22 Rev Time 0.00
Received By ccole Date 2016-11-07 Time 07:22 Sent To  
Notes
2016-11-07 07:37:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100936
 11/7/16
  
 1) REVISE THE PLANS TO SHOW COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE.
  
 2) PROVIDE THE NOA'S FOR THE FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  