Plan Review Details - Permit 16100873
Plan Review Stops For Permit 16100873
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-25 Cont ID  
Sent By mvaldes Date 2017-01-26 Time 10:03 Rev Time 0.00
Received By shill Date 2017-01-25 Time 12:54 Sent To  
Notes
2017-01-25 12:54:19****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVISO; SHOP DRAWINGS OR PRODUCT APPROVAL REQUIRED
 FOR REAR EXIT DOOR, FBC 1008, PANIC DEVICE OR FIRE EXIT
 HARDWARE REQUIRED. INSTALLATION OF A NEW DOOR REQUIRES
 A REVISION AND PRODUCT APPROVAL. MODIFICATION OF AN
 EXISTING DOOR MAY REQUIRE A REVISION SUBJECT TO THE
 FIELD INSPECTOR'S DISCRETION.
  
 3. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE,
 FBC 1008.1.10, 1008.2.
  
 3. PER ARCHITECT, ALL BENCHES ARE MOVEABLE - ADDITION
 OF ANY BUILT IN BENCHES REQUIRE A REVISION OR, IF DONE
 AFTER THIS PERMIT IS CLOSED, A SEPARATE PERMIT.
  
 4. FBC A 403.3. THIS APPEARS TO BE A RAMP; RISE CANNOT
 EXCEED 6 INCHES. IF RISE EXCEEDS 6 INCHES, HANDRAILS
 AND EDGE PROTECTION ARE REQUIRED (AND A REVISION IS
 REQUIRED). THIS COMMENT APPLIES TO THE 1/12 DOWNWARD
 SLOPE LEADING TO THE RAMP AT THE REAR OF THE BUILDING.
 SHEET A1 APPEARS TO SHOW HANDRAILS FOR THIS PORTION,
 SHEET A3 DOES NOT.
  
 5. MEANS OF EGRESS ILLUMINATION REQUIRED IN THE EXIT
 DISCHARGE TO THE PUBLIC WAY, FBC 1027.
  
 6. THIS IS A CHANGE OF OCCUPANCY AND SHALL COMPLY WITH
 ALL REQUIREMENTS OF FBC EXISTING BUILDING CHAPTER 10.
 PLANS HAVE BEEN REDLINED TO NOTE CHANGE OF OCCUPANCY.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By shill Date 2016-12-13 Time 12:37 Rev Time 0.00
Received By shill Date 2016-12-13 Time 12:06 Sent To  
Notes
2016-12-13 12:07:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC
 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN
 TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
  
 2ND REVIEW, INFORMATION REGARDING THE EXISTING
 OCCUPANCY WAS NOT PROVIDED.
  
 COMPLIANCE WITH THE FOLLOWING IS NOT CLEAR:
  
 FBC EB TABLE 1012.5, FBC B TABLE 503, AS CHANGE OF
 OCCUPANCY IS PROPOSED TO A HIGHER HAZARD, COMPLIANCE
 WITH FBC B CHAPTER 5 IS REQUIRED. IT APPEARS THAT THE
 PROPOSED NEW OCCUPANCY MAY COMPLY, BUT REQUIRES
 CALCULATIONS AND INFORMATION REGARDING THE EXISTING
 OCCUPANCIES TO BE PROVIDED FBC B 503.1.
  
 FBC EB TABLE 1012.6, APPEARS TO COMPLY, BUT NO
 INFORMATION PROVIDED (FROM S1 OR S2 TO A OR B? B TO A?)
  
 6. SEE IMPACT FEE REVIEW.
  
 THIS IS REQUIRED PRIOR TO PERMIT ISSUANCE BUT MAY BE
 DONE AFTER ALL REVIEWS HAVE PASSED.
  
 NEW COMMENT:
  
 THE DOOR IN THE WOMENS RESTROOM SWINGS INTO THE CLEAR
 FLOOR SPACE, FBC A 603.2.3.
  
 PROVISO, DETAILS FOR TOILET DO NOT COMPLY, HEIGHT TO BE
 MEASURED AT TOP OF SEAT, FBC A 604.4, REVISE DETAILS.
  
 * * * * * * * * * * * * *
  
 THE FOLLOWING ITEMS WERE ADDRESSED IN A RESPONSE
 LETTER. IF THE SHEETS ARE REVISED DUE TO OTHER TRADES,
 REVISE THE PLAN TO INCORPORATE THE INFORMATION.
  
 1. PROVISO; SHOP DRAWINGS OR PRODUCT APPROVAL REQUIRED
 FOR REAR EXIT DOOR, FBC 1008.
  
 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107.
 PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE
 STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON
 THE RACKS.
  
 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE,
 FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY. (DOORS
 SPECIFIED, REVISE TO INCLUDE GATES)
  
 10. INCORPORATE INFORMATION REGARDING THE BENCH SEATS
 INTO THE PLAN, FBC 5TH EDITION ACCESSIBILITY 903. PER
 RESPONSE LETTER THEY ARE MOVEABLE AND BACKLESS.
  
 18. THE SLOPE EXCEEDS THE MAXIMUM SLOPE OF 1:20 (1:12
 SHOWN), FBC A 403.3. THIS APPEARS TO BE A RAMP; RISE
 CANNOT EXCEED 6 INCHES. IF RISE EXCEEDS 6 INCHES,
 HANDRAILS AND EDGE PROTECTION ARE REQUIRED (AND A
 REVISION IS REQUIRED).
  
 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE
 PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL
 REQUIREMENTS, INCLUDING ILLUMINATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By shill Date 2016-11-07 Time 15:06 Rev Time 0.00
Received By shill Date 2016-11-04 Time 11:51 Sent To  
Notes
2016-11-07 15:06:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN SHOWS AN EXISTING DOOR TO HAVE A PANIC BAR
 INSTALLED. PROVIDE PRODUCT INFORMATION FOR THE EXISTING
 DOOR AND FOR THE PROPOSED PANIC HARDWARE. EXTERIOR
 DOORS ARE TESTED WITH HARDWARE, SO IT IS NOT CLEAR HOW
 THIS WILL AFFECT THE INTEGRITY OF THE DOOR, FBC 1609,
 107.
  
 2. THIS PROJECT INCLUDES A CHANGE OF OCCUPANCY. SEE FBC
 5TH EDITION EXISTING BUILDING CHAPTER 10. REVISE PLAN
 TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
  
 3. PROVIDE A DETAIL FOR THE STORAGE RACKS, FBC 107.
 PROVIDE INFORMATION REGARDING THE EQUIPMENT TO BE
 STORED THERE AND THE WEIGHT OF ITEMS TO BE STORED ON
 THE RACKS.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB,
 INCLUDING A COST BREAKDOWN FOR ALL WORK INCLUDING LABOR
 AND MATERIALS, OVERHEAD AND PROFIT, INCLUDING ITEMS
 ALREADY INSTALLED WITHOUT PERMIT (PROVIDE VALUE OF WHAT
 A CONTRACTOR WOULD HAVE CHARGED FOR THE WORK TO BE
 DONE), FBC 109. VALUE IS TOO LOW. FAILURE TO PROVIDE AN
 ACCURATE VALUE WILL RESULT IN PERMIT ISSUANCE DELAY.
  
 5. THE RATIONALE FOR BUSINESS OCCUPANCY IS NOT CLEAR.
 REVISE PLAN TO INCLUDE INFORMATION AS TO USE OF EACH
 AREA. THE TWO SMALL OFFICES ARE BUSINESS, BUT THE REST
 OF THE SPACE APPEARS TO BE ASSEMBLY, FBC CHAPTER 3.
  
 6. SEE IMPACT FEE REVIEW.
  
 7. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE
 GAME AREA. PROVIDE A SPECIFICATION FOR THE NETTING AND
 THE DOORS, FBC 107.
  
 8. ALL DOORS AND GATES ARE TO INCLUDE PANIC HARDWARE,
 FBC 1008.1.10, 1008.2. REVISE PLAN TO SPECIFY.
  
 9. SEE FBC 303.3, EXPLAIN RATIONALE FOR OCUPANCY A2,
 USES INTENDED FOR FOOD AND DRINK.
  
 10. PROVIDE A DETAIL FOR THE BENCH SEATS, FBC 5TH
 EDITION ACCESSIBILITY 903.
  
 11. PROVIDE A DETAIL FOR THE SALES AND SERVICE COUNTER
 OR CHECK OUT AISLE, FBC 5TH EDITION ACCESSIBILITY 9 04.
  
 12. IDENTIFY THE UNIDENTIFIED RECTANGLE ADJACENT TO THE
 DOOR IN THE EQUIPMENT AREA, FBC 107.
  
 13. REVISE PLAN TO SHOW THE 18 INCH MANEUVERING
 CLEARANCE FOR THE DOOR FOR THE UNIDENTIFIED ROOM
 ADJACENT TO THE PROPOSED REST ROOMS A2, FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.1.
  
 14. PROPOSED FLOOR PLAN INCLUDES DEMO AREA FOR THE REST
 ROOMS BUT NOT THE PROPSED PLAN, REVISE PLAN TO BE
 CONSISTENT WITH THE NAME OF THE DETAIL. IF NECESSARY,
 PROVIDE A DEMO PLAN TO CLARIFY, FBC 107.
  
 15. A3 RAMP DETAIL HAS OLD CODE REFERENCE, REVISE TO
 CURRENT, FBC 5TH EDITION ACCESSIBILITY.
  
 16. REVISE PLAN TO SHOW THE RISE OF THE RAMP, FBC 5TH
 EDITION ACCESSIBILITY 405.6.
  
 17. REAR DOOR AT RAMP, CLARIFY DOOR SWING. ONE PAGE
 SHOWS A RIGHT HAND, ANOTHER PAGE SHOWS LEFT. DOORS ARE
 TO HAVE 18 IN MANEUVERING CLEARANCE ON THE PULL SIDE,
 FBC 5TH EDITION ACCESSIBILITY 404.2.4.1.
  
 18. RAMP DETAIL SHOWS A SLOPE DOWN, A LANDING, AND A
 RAMP UP. REVISE PLAN TO INCLUDE THE SLOPE, FBC 107.
  
 19. REVISE PLAN TO INCLUDE THE EXIT DISCHARGE TO THE
 PUBLIC WAY, FBC 1027. SHOW COMPLIANCE WITH ALL
 REQUIREMENTS, INCLUDING ILLUMINATION.
  
 20. HANDRAIL EXTENSION REQUIRED AT THE TOP OF THE RAMP,
 FBC 5TH EDITION 505.10.
  
 21. SHOW THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY AND
 FROM ACCESSIBLE PARKING SPACE TO THE ALTERED AREA, FBC
 5TH EDITION 202.4.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-26 Cont ID  
Sent By mvaldes Date 2017-01-25 Time 10:44 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 10:26 Sent To B
Notes
2017-01-25 11:08:573RD REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 1] EXIT & EMERGENCY LIGHTING REQUIRED PER FBC 1006 &
 1011. (MEANS OF EGRESS ILLUMINATION FOR EXIT DISCHARGE)
  
 2] ELECTRICAL LOAD CALCULATIONS, SINGLE LINE RISER
 DIAGRAM INCLUDING WIRE & CONDUIT SIZES, & PANEL
 SCHEDULES SHALL BE SUBMITTED FOR TENANT PERMIT #
 16100033.
  
 3] FBC-E SECTION C101.4.4 CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE.
 WHERE THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 4] ELECTRIC WATER FOUNTAINS REQUIRES GFCI PROTECTION
 PER NEC 422.52
2017-01-25 10:44:27ROUTED TO SH.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-01-04 Cont ID  
Sent By mvaldes Date 2017-01-04 Time 10:05 Rev Time 0.00
Received By mvaldes Date 2017-01-04 Time 09:06 Sent To  
Notes
2017-01-04 10:02:092ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] NEW DRAWING INDICATE A ELECTRIC WATER FOUNTAIN
 THEREFORE THE POWER OUTLET MUST BE GFCI PROTECTED PER
 NEC 422.52. (SHOW COMPLIANCE)
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By mvaldes Date 2016-11-02 Time 18:43 Rev Time 0.00
Received By mvaldes Date 2016-11-02 Time 17:41 Sent To  
Notes
2016-11-02 18:23:401ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - NO ELECTRICAL INFORMATION, PLEASE PROVIDE AN
 ELECTRICAL SCOPE OF WORK. INCLUDE THE FOLLOWING ITEMS
  
 1] SHOW A DETAIL FOR OBSTRUCTED AND UNBOSTRUCTED REACH
 RANGES OF DEVICES IN ACCORDANCE WITH FBC-A SECTION 308.
  
 2] SHOW A DETAIL FOR THE MEANS OF SUPPORT OF THE LAY IN
 LUMINAIRE TO THE SUSPENDED CEILING PER NEC 410.36(B).
  
 3] THE ADA RAMP WILL BE A MEANS OF EGRESS EXIT
 DISCHARGE THEREFORE ILLUMINATION IS REQUIRED.
 FBC-1006.1 (SHOW COMPLIANCE).

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-20 Cont ID  
Sent By wjolin Date 2016-12-20 Time 12:00 Rev Time 0.00
Received By wjolin Date 2016-12-20 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By wjolin Date 2016-11-10 Time 10:08 Rev Time 0.00
Received By wjolin Date 2016-11-10 Time 09:16 Sent To  
Notes
2016-11-10 10:08:261500 NORTH FLORIDA MANGO ROAD - SUITE #14 & #15
 PERMIT #16100873
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE A LIMITED WORK SCOPE OF BATHROOM
 RENOVATIONS AND ADA RAMP; HOWEVER, A COMPLETE SET OF
 PLANS ARE NEEDED AS THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY FROM MERCANTILE TO A MIXED USE
 ASSEMBLY/BUSINESS OCCUPANCY. "CMS INDOOR ACTION SPORTS"
 APPLIED FOR A BUSINESS TAX EARLIER THIS YEAR (2016) BUT
 NO PERMITS COULD BE LOCATED SUPPORTING THE CHANGE OF
 USE.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, OCCUPANCY
 SEPARATIONS, EXITS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL, PANIC DOOR
 HARDWARE ETC.
  
 NO FLAME SPREAD OR SMOKE OBSCURATION INFORMATION
 PROVIDED ON THE FLOORING, WALL COVERINGS, CEILING ETC.
  
 TWO EXIT DOORS FROM TWO DIFFERENT TENANTS ARE BEING
 FUNNELED DOWN ONE EGRESS ADA RAMP. REDUCED EGRESS WIDTH
 IS NOT PERMITTED.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES.
  
 HOW IS THE EGRESS RAMP BEING PROTECTED FROM VEHICULAR
 TRAFFIC OR BLOCKED CARS?
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-26 Cont ID  
Sent By mvaldes Date 2017-01-26 Time 10:22 Rev Time 0.00
Received By mvaldes Date 2017-01-25 Time 10:10 Sent To  
Notes
2017-01-25 10:10:501/25 ROUTED TO MV DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 13:46 Rev Time 0.00
Received By gjohnson Date 2016-12-08 Time 14:27 Sent To  
Notes
2016-12-09 14:27:10B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-23 Cont ID  
Sent By shill Date 2016-11-18 Time 10:57 Rev Time 0.00
Received By shill Date 2016-10-28 Time 12:47 Sent To  
Notes
2016-11-02 16:33:38ROUTED TO MARIO VALDEZ 11/02/16 - JORGE V.
2016-11-01 12:48:08B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-01-25 Cont ID  
Sent By shill Date 2017-01-25 Time 14:57 Rev Time 0.00
Received By shill Date 2017-01-25 Time 14:57 Sent To  
Notes
2017-01-25 14:57:41MU 2017-663
 $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By shill Date 2016-11-07 Time 07:51 Rev Time 0.00
Received By shill Date 2016-11-07 Time 07:51 Sent To  
Notes
2016-11-07 07:52:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE HAVE BEEN PAID (IF APPLICABLE) IS TO BE
 PROVIDED.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-11-02 Cont ID  
Sent By jvalido Date 2016-11-02 Time 16:32 Rev Time 0.00
Received By jvalido Date 2016-11-02 Time 16:06 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-11-07 Cont ID  
Sent By shill Date 2016-11-07 Time 07:52 Rev Time 0.00
Received By shill Date 2016-11-07 Time 07:52 Sent To  
Notes
2016-11-07 07:54:29THIS PROPERTY IS LOCATED IN A SPECIAL HAZARD FLOOD AREA
 CUMULATIVE 5 YEAR IMPROVEMENTS ARE $118,253; PAPA 2016
 VALUE FOR STRUCTURE IS $4,469,726 (3%); NOT A
 SUBSTANTIAL IMPROVEMENT
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 13:46 Rev Time 0.00
Received By gjohnson Date 2017-01-09 Time 13:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By gjohnson Date 2016-11-09 Time 08:52 Rev Time 0.00
Received By gjohnson Date 2016-11-08 Time 13:20 Sent To  
Notes
2016-11-08 16:15:481ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. VALUATIONS SEEMS LOW PLEASE PROVIDE BONA FIDE SIGNED
 CONTRACTS WITH PRICE BREAK DOWN FOR ALL TRADES. PER WPB
 AMEND. TO FBC 109.3
  
 2. ALL ACCESSIBILITY ELEMENTS SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE
 5TH EDITION (2014) ACCESSIBILITY WITCH DIFFERS FROM THE
 ADA/ ANZI -A117.1
 PLEASE CHECK YOUR NOTES TO ENSURE THEY ALL COMPLY WITH
 FBC ACC AND REMOVE REFERENCE TO ADA/ ANZI-A117.1
 PER WPB AMENS. TO FBC 107.2.1
  
 3. SHOW COMPLIANCE FORTOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE NOT CENTERLINE OF BAR. PER FBC
 ACC 609.4
  
 5. THE REAR WALLL GRAB BAR SHALL BE 36 INCHES (915 MM)
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE IF TOILET
 IS SET AT 18" OFF SIDE WALL YOU WILL HAVE 6" FROM END
 OF THE BAR TO THE SIDE WAL YOU ARE SHOWING 2" PLEASE
 CLARIFY . PER FBC ACC 604.5.2
  
 6. A WATER FOUNTAIN COMPLYING WITH FBC ACC 602 AND FBC
 PL [B] 410.2 IS REQUIRED.
  
 7. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAM. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 9. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-01-04 Time   Rev Time 0.00
Received By pgreilic Date 2017-01-04 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By   Date 2016-12-15 Time   Rev Time 0.00
Received By pgreilic Date 2016-12-15 Time 16:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2016-11-18 Time   Rev Time 0.00
Received By pgreilic Date 2016-11-18 Time 16:24 Sent To  
Notes
2016-11-18 16:24:44PAUL GREILICH, SENIOR PLANNER
 (561)-822-1443
 [email protected]