Plan Review Details - Permit 16100812
Plan Review Stops For Permit 16100812
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-10 Cont ID  
Sent By shill Date 2017-02-10 Time 08:14 Rev Time 0.00
Received By shill Date 2017-02-10 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By shill Date 2016-11-04 Time 07:58 Rev Time 0.00
Received By shill Date 2016-11-04 Time 07:20 Sent To  
Notes
2016-11-04 07:58:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN CONFLICTS WITH APPLICATION; SCOPE NOT CLEAR,
 FBC 107.
  
 THE APPLICATION WORK DESCRIPTION DESCRIBES A BATHROOM
 AND GIVES AN NOA NUMBER FOR A DOOR. THE NOA WAS NOT
 PROVIDED. ALUMINUM WINDOW WALL NOAS WERE PROVIDED. THE
 PLANS DO NOT SHOW WINDOW WALL OR DOOR REPLACEMENT.
 VALUE ON APPLICATION APPEARS TOO LOW.
  
 REVISE PLAN TO SHOW ALL WORK PROPOSED. PROVIDE PRODUCT
 APPROVALS FOR COMPONENTS AND CLADDING IN THE SCOPE OF
 THIS PERMIT. DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 3. REVISE PLAN TO SHOW 18 INCH MANEUVERING CLEARANCE,
 PULL SIDE, FOR THE BATHROOM DOOR, FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.
  
 4. IF COMPONENTS AND CLADDING ARE TO BE INCLUDED IN THE
 SCOPE OF THIS PERMIT, REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA FBC 1603.1.4.
  
 5. THERE IS AN OUTDATED CODE REFERENCE ON SHEET 2 (FBC
 11 430), REVISE.
  
 6. FBC 5TH EDITION ACCESSIBILITY 609.4, THE GRAB BAR IS
 SHOWN AS 36 IN TO THE CENTER OF THE BAR, THIS IS TO
 MEASURED TO THE TOP (SO THE DETAIL DOES NOT COMPLY),
 REVISE.
  
 7. FBC 5TH EDITION ACCESSIBILITY 604.4, THE WATER
 CLOSET IS TO BE MEASURED TO THE TOP OF THE SEAT. DETAIL
 4, SHEET 2 IS NOT CLEAR. THE DIMENSION IS SHOWN TO THE
 TOP OF THE FIXTURE, WHICH IS USUALLY THE TOP OF THE LID
 (NOT THE SEAT). REVISE DETAIL TO CLARIFY.
  
 8. SHOW ACCESSIBLE ROUTE TO THE ALTERED AREA, FBC 5TH
 EDITION 202.3. REVISE THE PLAN TO SHOW ACCESSIBLE ROUTE
 AND INCLUDE THE FLOOR PLAN TO SHOW HOW THE EXISTING
 SPACE WILL BE AFFECTED BY THE PROPOSED RENOVATION, FBC
 107, FBC CHAPTER 10.
  
 9. IF ENTRY DOOR REPLACEMENT IS PROPOSED, PROVIDE THE
 PRODUCT APPROVAL (REVIEWED BY THE DESIGNER OF RECORD),
 AND INDICATE HARDWARE PROPOSED. REVISE PLAN TO INCLUDE
 OCCUPANCY CLASSIFICATION FOR THE AREAS AFFECTED BY THE
 NEW ENTRY DOOR. PANIC HARDWARE REQUIRED FOR A, E AND H
 OCCUPANCIES, FBC 1008.1.10.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-01 Cont ID  
Sent By mvaldes Date 2017-02-01 Time 10:51 Rev Time 0.00
Received By mvaldes Date 2017-02-01 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By mvaldes Date 2016-11-07 Time 14:00 Rev Time 0.00
Received By mvaldes Date 2016-11-07 Time 13:54 Sent To  
Notes
2016-11-07 14:11:011ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] ALL RECEPTACLES INSTALLED IN BATHROOMS SHALL BE GFCI
 PROTECTED IN ACCORDANCE WITH NEC 210.8(B)(1). SHOW
 COMPLIANCE.
  
 2] PROVIDE AN ADA DETAIL FOR OBSTRUCTED & UNOBSTRUCTED
 REACH RANGES OF DEVICES PER FBC-A SECTION 308.
  
 3] CLARIFY IF THE SCOPE OF WORK INCLUDES DRINKING
 FOUNTAIN INSTALLATION ? IF SO PLEASE SHOW THE DEDICATED
 RECEPTACLE OUTET WITH GFCI PROTECTION PER NEC 422.52.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By pleduc Date 2017-01-27 Time   Rev Time 0.00
Received By pleduc Date 2017-01-27 Time 09:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-09 Cont ID  
Sent By wjolin Date 2016-11-09 Time 11:19 Rev Time 0.00
Received By wjolin Date 2016-11-09 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-10 Cont ID  
Sent By gjohnson Date 2017-03-10 Time 11:09 Rev Time 0.00
Received By gjohnson Date 2017-01-24 Time 15:35 Sent To  
Notes
2017-03-08 16:34:28ROUTED TO GEORGE JOHNSON 3/8/2017 - JORGE V.
2017-01-25 15:36:00B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-29 Cont ID  
Sent By cpuell Date 2016-11-29 Time 11:18 Rev Time 0.00
Received By cpuell Date 2016-10-26 Time 12:49 Sent To  
Notes
2016-10-28 12:50:21B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-08 Cont ID  
Sent By jvalido Date 2017-03-08 Time 16:35 Rev Time 0.00
Received By jvalido Date 2017-03-08 Time 16:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-28 Cont ID  
Sent By jvalido Date 2016-11-28 Time 17:10 Rev Time 0.00
Received By jvalido Date 2016-11-28 Time 16:56 Sent To  
Notes
2016-11-28 16:57:49CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS SHOWING REQUIRED EXHAUST.
 (2) PROVIDE EXHAUST FAN IN BATHROOM.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-03-10 Cont ID  
Sent By gjohnson Date 2017-03-10 Time 11:09 Rev Time 0.00
Received By gjohnson Date 2017-03-10 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-02-03 Cont ID  
Sent By gjohnson Date 2017-02-03 Time 09:34 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 15:26 Sent To  
Notes
2017-02-03 10:25:172ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IS THIS THE ONLY BATHROOM SERVING THIS FLOOR OR IS
 THERE A COMMON BATHROOM GROUP FOR THIS FLOOR PLEASE
 CLARIFY. PER WPB AMEND TO FBC
  
 2. THE OCCUPANT LOAD IS UNCLEAR UNDER THE OCCUPANT LOAD
 BREAK DOWN IT STATES 95 PEOPLE UNDER THE LIFE SAFETY
 DATA IT SHOWS 18 PEOPLE PLEASE CLARIFY. PER WPB AMEND
 TO FBC
  
 3.IF THE OCCUPANT LOAD IS 95 THE PLUMING FIXTURE COUNT
 SHALL BE 2 TOILETS FOR MEN , 2 TOILETS FOR WOMEN AND 2
 LAVS FOR EACH SEX. PER FBC PL TABLE 403.1
  
 4. THE RISER DIAGRAM DOES NOT MATCH THE LAY OUT OF THE
 FLOOR PLAN , IT IS NOT POSSIBLE TO DETERMINE IF THE
 RISER IS CODE COMPLIANT THERE IS TO MANY DEFICIENCY'S
 TO LIST PLEASE PROVIDE A CLEAR AND CONCISE CODE
 COMPLIANT RISER THAT MATCHES THE FLOOR PLAN. PER WPB
 AMEND TO FBC
  
 5. SHT. 1 THE PLUMBING PLAN DETAIL IS SHOWING A FIXTURE
 BEHIND THE TOILET PLEASE THE IDENTIFY FIXTURE AND SHOW
 ON RISER DIAGRAM. PER WPB AMEND TO FBC
  
 6. PLEASE SHOW COMPLIANCE WITH FBC PL
 SECTION 607 HOT WATER SUPPLY SYSTEM
  
 607.1 WHERE REQUIRED.
 IN RESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED
 TO PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE. IN NONRESIDENTIAL
 OCCUPANCIES,HOT WATER SHALL BE SUPPLIED FOR CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE
 PURPOSES. IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR
 TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND
 WASHING PURPOSES.
  
 7. ALL LAVATORY'S SHALL COMPLY WITH FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-23 Cont ID  
Sent By gjohnson Date 2016-11-23 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2016-11-23 Time 13:27 Sent To  
Notes
2016-11-23 15:48:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE OVERALL WIDTH OF THE ACCESSIBLE BATHROOM NEEDS
 TO BE A MIN OF 84" TO ALLOW FOR THE 60'X54" TOILET
 CLEARANCE IT CAN NOT HAVE ANY OTHER FIXTURES IN IT .
 AND THE CLEARANCE REQUIRED FOR THE LAVATORY. PER FBC
 ACC 603/ 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. THE PLAN NOTES A HI LO EWC BUT IT SHOWS A SINGLE A
 MINIMUM OF TWO IS REQUIRED FBC ACC 211.2 MINIMUM
 NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 PLEASE CLARIFY.
  
 3. THE CLEAR FLOOR SPACE FOR THE WATER FOUNTAIN IS
 SHOWN EXTENDING INTO THE WALL PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE SIDE WALL GRAB BAR SHALL COMPLY WITH FBC ACC
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 THE DETAIL SHOWING THE BACKING FOR GRAB BAR DOES NOT
 COMPLY PLEASE REMOVE. PER WPB AMEND TO FBC 107.2.1
  
 5. THE HIGHT OF THE GRAB BAR SHALL COMPLY FBC ACC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 6. TOILET PAPER DISPENSER SHALL BE 7" TO 9" MEASURED
 OFF THE FRONT OF THE TOILET. PER FBC ACC 604.7
  
 7. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAM. PER
 WPB AMEN TO FBC 107.3.5.1.3(13)
  
 8. PLEASE PROVIDE OCCUPANT LOAD AND NUMBER OF EXISTING
 BATHROOMS . PER WPB AMEND TO FBC 107.2.1
  
 9. PLEASE PROVIDE THE SPECIFIC CODES PROJECT IS BEING
 DESIGNED TO. PER WPB AMEND TO FBC 107.2.1