| Plan Review Stops For Permit 16100812 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2017-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-02-10 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-02-10 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-11-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-11-04 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-11-04 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2016-11-04 07:58:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLAN CONFLICTS WITH APPLICATION; SCOPE NOT CLEAR, | | | FBC 107. | | | | | | THE APPLICATION WORK DESCRIPTION DESCRIBES A BATHROOM | | | AND GIVES AN NOA NUMBER FOR A DOOR. THE NOA WAS NOT | | | PROVIDED. ALUMINUM WINDOW WALL NOAS WERE PROVIDED. THE | | | PLANS DO NOT SHOW WINDOW WALL OR DOOR REPLACEMENT. | | | VALUE ON APPLICATION APPEARS TOO LOW. | | | | | | REVISE PLAN TO SHOW ALL WORK PROPOSED. PROVIDE PRODUCT | | | APPROVALS FOR COMPONENTS AND CLADDING IN THE SCOPE OF | | | THIS PERMIT. DESIGNER OF RECORD IS TO REVIEW PRODUCT | | | APPROVALS PRIOR TO SUBMITTAL. | | | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | 3. REVISE PLAN TO SHOW 18 INCH MANEUVERING CLEARANCE, | | | PULL SIDE, FOR THE BATHROOM DOOR, FBC 5TH EDITION | | | ACCESSIBILITY 404.2.4. | | | | | | 4. IF COMPONENTS AND CLADDING ARE TO BE INCLUDED IN THE | | | SCOPE OF THIS PERMIT, REVISE PLAN TO INCLUDE WIND | | | DESIGN CRITERIA FBC 1603.1.4. | | | | | | 5. THERE IS AN OUTDATED CODE REFERENCE ON SHEET 2 (FBC | | | 11 430), REVISE. | | | | | | 6. FBC 5TH EDITION ACCESSIBILITY 609.4, THE GRAB BAR IS | | | SHOWN AS 36 IN TO THE CENTER OF THE BAR, THIS IS TO | | | MEASURED TO THE TOP (SO THE DETAIL DOES NOT COMPLY), | | | REVISE. | | | | | | 7. FBC 5TH EDITION ACCESSIBILITY 604.4, THE WATER | | | CLOSET IS TO BE MEASURED TO THE TOP OF THE SEAT. DETAIL | | | 4, SHEET 2 IS NOT CLEAR. THE DIMENSION IS SHOWN TO THE | | | TOP OF THE FIXTURE, WHICH IS USUALLY THE TOP OF THE LID | | | (NOT THE SEAT). REVISE DETAIL TO CLARIFY. | | | | | | 8. SHOW ACCESSIBLE ROUTE TO THE ALTERED AREA, FBC 5TH | | | EDITION 202.3. REVISE THE PLAN TO SHOW ACCESSIBLE ROUTE | | | AND INCLUDE THE FLOOR PLAN TO SHOW HOW THE EXISTING | | | SPACE WILL BE AFFECTED BY THE PROPOSED RENOVATION, FBC | | | 107, FBC CHAPTER 10. | | | | | | 9. IF ENTRY DOOR REPLACEMENT IS PROPOSED, PROVIDE THE | | | PRODUCT APPROVAL (REVIEWED BY THE DESIGNER OF RECORD), | | | AND INDICATE HARDWARE PROPOSED. REVISE PLAN TO INCLUDE | | | OCCUPANCY CLASSIFICATION FOR THE AREAS AFFECTED BY THE | | | NEW ENTRY DOOR. PANIC HARDWARE REQUIRED FOR A, E AND H | | | OCCUPANCIES, FBC 1008.1.10. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-02-01 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2017-02-01 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2017-02-01 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-11-07 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-11-07 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-11-07 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2016-11-07 14:11:01 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] ALL RECEPTACLES INSTALLED IN BATHROOMS SHALL BE GFCI | | | PROTECTED IN ACCORDANCE WITH NEC 210.8(B)(1). SHOW | | | COMPLIANCE. | | | | | | 2] PROVIDE AN ADA DETAIL FOR OBSTRUCTED & UNOBSTRUCTED | | | REACH RANGES OF DEVICES PER FBC-A SECTION 308. | | | | | | 3] CLARIFY IF THE SCOPE OF WORK INCLUDES DRINKING | | | FOUNTAIN INSTALLATION ? IF SO PLEASE SHOW THE DEDICATED | | | RECEPTACLE OUTET WITH GFCI PROTECTION PER NEC 422.52. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-01-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2017-01-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-01-27 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-11-09 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-11-09 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-10 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-24 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2017-03-08 16:34:28 | ROUTED TO GEORGE JOHNSON 3/8/2017 - JORGE V. | | 2017-01-25 15:36:00 | B07 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-11-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-11-29 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-10-26 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2017-03-08 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2017-03-08 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2017-03-08 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-11-28 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-11-28 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-11-28 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2016-11-28 16:57:49 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE MECHANICAL PLANS SHOWING REQUIRED EXHAUST. | | | (2) PROVIDE EXHAUST FAN IN BATHROOM. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-03-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-10 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-10 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2017-02-03 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-02-03 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-02-02 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2017-02-03 10:25:17 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. IS THIS THE ONLY BATHROOM SERVING THIS FLOOR OR IS | | | THERE A COMMON BATHROOM GROUP FOR THIS FLOOR PLEASE | | | CLARIFY. PER WPB AMEND TO FBC | | | | | | 2. THE OCCUPANT LOAD IS UNCLEAR UNDER THE OCCUPANT LOAD | | | BREAK DOWN IT STATES 95 PEOPLE UNDER THE LIFE SAFETY | | | DATA IT SHOWS 18 PEOPLE PLEASE CLARIFY. PER WPB AMEND | | | TO FBC | | | | | | 3.IF THE OCCUPANT LOAD IS 95 THE PLUMING FIXTURE COUNT | | | SHALL BE 2 TOILETS FOR MEN , 2 TOILETS FOR WOMEN AND 2 | | | LAVS FOR EACH SEX. PER FBC PL TABLE 403.1 | | | | | | 4. THE RISER DIAGRAM DOES NOT MATCH THE LAY OUT OF THE | | | FLOOR PLAN , IT IS NOT POSSIBLE TO DETERMINE IF THE | | | RISER IS CODE COMPLIANT THERE IS TO MANY DEFICIENCY'S | | | TO LIST PLEASE PROVIDE A CLEAR AND CONCISE CODE | | | COMPLIANT RISER THAT MATCHES THE FLOOR PLAN. PER WPB | | | AMEND TO FBC | | | | | | 5. SHT. 1 THE PLUMBING PLAN DETAIL IS SHOWING A FIXTURE | | | BEHIND THE TOILET PLEASE THE IDENTIFY FIXTURE AND SHOW | | | ON RISER DIAGRAM. PER WPB AMEND TO FBC | | | | | | 6. PLEASE SHOW COMPLIANCE WITH FBC PL | | | SECTION 607 HOT WATER SUPPLY SYSTEM | | | | | | 607.1 WHERE REQUIRED. | | | IN RESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE SUPPLIED | | | TO PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR | | | BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY | | | OR BUILDING MAINTENANCE. IN NONRESIDENTIAL | | | OCCUPANCIES,HOT WATER SHALL BE SUPPLIED FOR CULINARY | | | PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE | | | PURPOSES. IN NONRESIDENTIAL OCCUPANCIES, HOT WATER OR | | | TEMPERED WATER SHALL BE SUPPLIED FOR BATHING AND | | | WASHING PURPOSES. | | | | | | 7. ALL LAVATORY'S SHALL COMPLY WITH FBC PL | | | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | | FACILITIES. | | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | | 1070 OR CSA B125.3. | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-11-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-23 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-23 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2016-11-23 15:48:12 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE OVERALL WIDTH OF THE ACCESSIBLE BATHROOM NEEDS | | | TO BE A MIN OF 84" TO ALLOW FOR THE 60'X54" TOILET | | | CLEARANCE IT CAN NOT HAVE ANY OTHER FIXTURES IN IT . | | | AND THE CLEARANCE REQUIRED FOR THE LAVATORY. PER FBC | | | ACC 603/ 604.3.2 OVERLAP. | | | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE | | | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB | | | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT | | | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE | | | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE | | | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL | | | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. | | | | | | 2. THE PLAN NOTES A HI LO EWC BUT IT SHOWS A SINGLE A | | | MINIMUM OF TWO IS REQUIRED FBC ACC 211.2 MINIMUM | | | NUMBER. | | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | PLEASE CLARIFY. | | | | | | 3. THE CLEAR FLOOR SPACE FOR THE WATER FOUNTAIN IS | | | SHOWN EXTENDING INTO THE WALL PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. THE SIDE WALL GRAB BAR SHALL COMPLY WITH FBC ACC | | | 604.5.1 SIDE WALL. | | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) | | | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM | | | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM | | | FROM THE REAR WALL. | | | THE DETAIL SHOWING THE BACKING FOR GRAB BAR DOES NOT | | | COMPLY PLEASE REMOVE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. THE HIGHT OF THE GRAB BAR SHALL COMPLY FBC ACC 609.4 | | | POSITION OF GRAB BARS. | | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE, | | | | | | 6. TOILET PAPER DISPENSER SHALL BE 7" TO 9" MEASURED | | | OFF THE FRONT OF THE TOILET. PER FBC ACC 604.7 | | | | | | 7. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAM. PER | | | WPB AMEN TO FBC 107.3.5.1.3(13) | | | | | | 8. PLEASE PROVIDE OCCUPANT LOAD AND NUMBER OF EXISTING | | | BATHROOMS . PER WPB AMEND TO FBC 107.2.1 | | | | | | 9. PLEASE PROVIDE THE SPECIFIC CODES PROJECT IS BEING | | | DESIGNED TO. PER WPB AMEND TO FBC 107.2.1 |
|
|