Plan Review Details - Permit 16100741
Plan Review Stops For Permit 16100741
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 14:54 Rev Time 0.00
Received By shill Date 2016-10-31 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 17:35 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 16:32 Sent To  
Notes
2016-11-09 17:36:30REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S (REVISION REQUIRED)
  
 1] CORRECT NOTE 2 TYPO TO "TAMPER RESISTANT".
 2] CORRECT LOAD DEMAND OF 210 AMPS TO MATCH PANEL
 SCHEDULE.
 3] ILLUMINATION REQUIRED FOR PANEL DEDICATED WORK SPACE
 PER NEC 110.26(D).
 4] GFCI PROTECTION REQUIRED FOR KITCHEN COUNTER-TOP
 RECEPTACLES PER NEC 210.8(A)(6)
 5] SMALL APPLIANCE CIRCUITS SHALL BE A MINIMUM OF 20
 AMP WITH 12 AWG WIRE PER NEC 210.52(B)(4).
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 17:37 Rev Time 0.00
Received By mvaldes Date 2016-10-25 Time 14:19 Sent To  
Notes
2016-10-25 14:23:41B11

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-09 Cont ID  
Sent By gjohnson Date 2016-11-09 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2016-11-09 Time 14:49 Sent To  
Notes
***NONE***