Plan Review Details - Permit 16100694
Plan Review Stops For Permit 16100694
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-19 Cont ID  
Sent By rmcdouga Date 2016-12-19 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2016-12-19 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-12-06 Cont ID  
Sent By rmcdouga Date 2016-12-06 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2016-12-05 Time 18:31 Sent To  
Notes
2016-12-06 11:02:11REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC R902
  
 2) SHEET D-1 IS TITLED A PROPOSED GARAGE. CORRECTION
 REQUIRED. FBC 107.2.1
  
 3) THE NOTE ON THE WALL SECTION ON SHEET D-1 SPECIFIES
 THE SOFFIT VENTS AT 6 INCHES (6") ON CENTER. PLEASE
 CLARIFY. FBC R806
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ROOFING MATERIALS, WINDOW/GLASS TYPES, AND EXTERIOR
 DOOR TYPES.
  
 5) FBC - R301.2.1.2 PROTECTION OF OPENINGS. GLAZED
 OPENINGS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL BE PROTECTED FROM WINDBORNE DEBRIS.
 GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM
 E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD 12, TAS
 201, 202 AND 203 OR AAMA 506, AS APPLICABLE.
  
 6) GENERAL NOTE 10 ON D-1 INCORRECTLY SPECIFIES ACI 318
 - 05. THE 2011 EDITION OF ACI 318 IS REFERENCED IN THE
 2014 FBC.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By skennedy Date 2016-12-22 Time 10:34 Rev Time 0.00
Received By skennedy Date 2016-12-22 Time 10:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By mvaldes Date 2016-10-31 Time 13:40 Rev Time 0.00
Received By mvaldes Date 2016-10-31 Time 11:36 Sent To  
Notes
2016-10-31 13:43:20JOB PERMIT NUMBER: 16100694
 JOB ADDRESS: 708 HILLCREST BLVD
 WEST PALM BEACH FLORIDA
 DATE: OCTOBER 31, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF THE ITEMS NOTED.
  
 1] CLARIFY IN THE RISER DIAGRAM IF THE MAIN
 DISCONNECTING MEANS IS LOCATED NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. AS ITS SHOWN THERE
 IS NO MAIN OUTSIDE THEREFORE IT APPEARS THE UNFUSED
 SERVICE CONDUCTORS PASS THROUGH THE INTERIOR OF THE
 HOUSE WITH NO OVER-CURRENT PROTECTION. FBC-R SECTION
 E3601.6.2
  
 2] EXISTING PANEL SCHEDULES REFLECTS THE W/H CIRCUIT
 WITH INCORRECT WIRE AND BREAKER SIZE. 8500 VA / 240
 VOLTS = 35 AMPS X 1.25 CONTINUOUS FACTOR = 44 AMPS.
 PLEASE REFER TO TABLE NEC 310.15(B)(16) FOR ALLOWABLE
 AMPACITIES OF CONDUCTORS. FBC-107
  
 3] PLEASE LABEL OUTDOOR RECEPTACLE OUTLETS AS GFCI PER
 FBC-R SECTION E3902.3 (GFCI PROTECTION REQUIRED.)
  
 4] BOXES USED FOR THE SOLE SUPPORT OF CEILING FANS
 SHALL BE MARKED BY THE MANUFACTURER AS SUITABLE FOR THE
 PURPOSE, AND INDICATE THE WEIGHT LIMITATIONS BUT SHALL
 NOT BE USED TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 CORRECT PADDLE FAN NOTE IN ACCORDANCE WITH FBC-R
 SECTION E4101.6.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS.WHEN RESUBMITTING, FOR A QUICKER RETURN
 ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-22 Cont ID  
Sent By skennedy Date 2016-12-22 Time 10:34 Rev Time 0.00
Received By skennedy Date 2016-12-13 Time 14:25 Sent To  
Notes
2016-12-14 14:25:31R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-06 Cont ID  
Sent By rmcdouga Date 2016-12-06 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2016-10-24 Time 12:20 Sent To  
Notes
2016-10-25 12:20:11R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-01-03 Cont ID  
Sent By rmcdouga Date 2017-01-03 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2017-01-03 Time 14:33 Sent To  
Notes
2017-01-03 14:36:14NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-05 Cont ID  
Sent By rmcdouga Date 2016-12-05 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2016-12-05 Time 18:31 Sent To  
Notes
2016-12-05 18:32:04BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-01-03 Cont ID  
Sent By rmcdouga Date 2017-01-03 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2017-01-03 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-19 Cont ID  
Sent By rmcdouga Date 2016-12-19 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2016-12-19 Time 09:13 Sent To  
Notes
2016-12-19 14:13:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM R405-2014 THAT WAAS SUBMITTED IS NOT
 ACCEPTABLE. FBC ENERGY CONSERVATION SECTION
 R101.5.1.1.2 AND R103.1.1.2
 - THE LOCATION ON THE FORM SHOULD BE WEST PALM BEACH
 NOT OKEECHOBEE.
 - THE OWNER AND BUILDER NAMES ARE MISSING FROM THE
 FORM.
 - THE CONSTRUCTION IS EXISTING WITH A NEW ADDITION, THE
 FORM STATES NEW CONSTRUCTION.
 - THIS IS SITE SPECIFIC AND CAN NOT BE WORST CASE. THE
 CORRECT ORIENTATION OF THE DWELLING IS REQUIRED TO BE
 USED FOR THE CALCULATIONS.
 - THE ROTATION ANGLE IS 0.
 - THERE ARE 3 BEDROOMS SO THE NUMBER OF OCCUPANTS
 SHOULD BE 6.
 - THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 R405-2014 FORM.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-12-06 Cont ID  
Sent By rmcdouga Date 2016-12-06 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2016-12-05 Time 18:57 Sent To  
Notes
2016-12-06 08:42:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS TO SHOW THAT
 EXISTING EQUIPMENT IS ADEQUATE FOR ADDITIONAL SPACE.
  
 2) THE ENERGY FORM R402 IS NOT COMPLETELY FILLED OUT
 AND THE OWNER/AGENT SIGNATURE IS MISSING. FBC ENERGY
 R103.1.1.2 AND R402.1
  
 3) THE ATTIC INSULATION ON THE WALL SECTION ON SHEET
 D-1 SHOWS R-19 CEILING INSULATION AND R-30 IS REQUIRED
 WHEN THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC
 ENERGY R402.1
  
 4) THE A/C SUPPLY DUCTS THAT ARE LOCATED IN THE ATTIC
 ARE REQUIRED TO BE INSULATED TO A MINIMUM OF R-8 WHEN
 THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC
 ENERGY R403.2.1
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By skennedy Date 2016-12-22 Time 10:34 Rev Time 0.00
Received By skennedy Date 2016-12-22 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-23 Cont ID  
Sent By gjohnson Date 2016-11-23 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2016-11-23 Time 13:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-10-27 Cont ID  
Sent By nwair Date 2016-10-27 Time 16:24 Rev Time 0.00
Received By njwira Date 2016-10-27 Time 16:01 Sent To  
Notes
2016-10-27 16:26:2410/27/16- PASSED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
 SIDE SETBACK MEETS THE 5FT. MINIMUM 15FT. TOTAL
 NOT BUILT INTO THE FRONT OR REAR SETBACK
 NO TREES BEING REMOVED
 DOESN'T EXCEED THE 30FT. HEIGHT LIMIT
 ONE KITCHEN ONE UNIT
 NOT A HISTORIC HOUSE
  