Plan Review Details - Permit 16100664
Plan Review Stops For Permit 16100664
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-04-10 Cont ID  
Sent By shill Date 2017-04-10 Time 07:08 Rev Time 0.00
Received By shill Date 2017-04-10 Time 06:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-03-20 Cont ID  
Sent By shill Date 2017-03-20 Time 07:43 Rev Time 0.00
Received By shill Date 2017-03-20 Time 06:55 Sent To  
Notes
2017-03-20 07:44:35****CORRECTIONS****
 REVISED 3/30, EMAILED ENGINEER AND CONTRACTOR
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A 208.2, SP101 SHOWS THAT ACCESSIBLE PARKING
 SPACES WILL BE USED FOR TEMPORARY MATERIAL STORAGE. IT
 IS NOT CLEAR WHETHER THESE SPACES ARE EXTRA (OVER THE
 MINIMUM NUMBER OF ACCESSIBLE SPACES REQUIRED FOR THIS
 FACILITY), OR IF THEY ARE REQUIRED.
  
 REVISE PLAN TO INCLUDE THE TOTAL NUMBER OF PARKING
 SPACES, NUMBER OF ACCESSIBLE SPACES. IF THE SPACES ARE
 REQUIRED, PROVIDE A PLAN TO SHOW HOW THE MINIMUM NUMBER
 OF ACCESSIBLE PARKING SPACES WILL BE PROVIDED.
  
 IT IS POSSIBLE THAT THIS CAN BE ADDRESSED VIA EMAIL AND
 THAT THIS CAN BE A PROVISO ITEM. DESIGNER OF RECORD MAY
 PROVIDE THE INFORMATION VIA EMAIL FOR PRELIMINARY
 REVIEW. DESIGNER OF RECORD IS TO PROPOSE A PROVISO
 CONDITION.
  
 2. A101 REVISION BAR SHOWS FOUR REVISIONS AND THE PAGE
 WAS SIGNED ON 3/13/17, BUT THE CLOUDS ARE ALL NUMBERED
 1 (10/10/16). IT IS NOT CLEAR WHAT HAS BEEN CHANGED
 AFTER REVIEW #3 DATED 1/19/17. REVISE PLAN TO CLOUD ALL
 CHANGES AND CORRELATE CHANGES WITH REVISION NUMBERS,
 FBC 107, OR CLARIFY WHAT HAS CHANGED ON THIS SHEET FOR
 REVISIONS #2, #3, & #4, FBC 107.
  
 3. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 4. REVISE PLAN TO INCLUDE BUILDING HEIGHT. ALTERNATIVE
 WAY TO SHOW BUILDING HEIGHT MAY BE ACCEPTABLE,
 FS553.79(7), THRESHOLD BUILDINGS.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 ALL OLD VOIDED SHEETS SHOULD BE MARKED "VOID" AND
 RETAINED IN THE SUBMITTAL. IT IS STRONGLY RECOMMENDED
 THAT ALL VOIDED SHEETS BE RETAINED - DO NOT DISCARD
 VOIDED SHEETS TO LEAVE ONLY ONE COPY OF EACH VOIDED
 PAGE. FAILURE TO RETAIN ALL DOCUMENTS IN THE SUBMITTAL
 PACKAGE MAY RESULT IN PLAN REVIEW DELAYS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 15:13 Rev Time 0.00
Received By shill Date 2016-12-27 Time 14:00 Sent To  
Notes
2016-12-27 15:14:07PROVISO
 ADDRESS PLAN REVIEW COMMENTS MADE BY OTHER TRADES
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 12:53 Rev Time 0.00
Received By shill Date 2016-10-31 Time 12:53 Sent To  
Notes
2016-10-31 12:09:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED
 IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN
 SHOWING LOCATION OF PROPOSED IMPROVEMENT.
  
 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY
 COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED
 BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN
 "LICENSE").
  
 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND
 SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL
 COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE
 COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA
 BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD
 WITH A COPY OF A CERTIFICATE OF COMPLETION,
 FAC61G15-22.001.
  
 THE WEBSITE (MYFLORIDALICENSE.ORG) HAS NOT BEEN UPDATED
 TO REFLECT THAT MR. COOKE, MR. DAVIS, MR. JONES HAS
 TAKEN THE COURSE. CONTACT FBPE FOR MORE INFORMATION.
  
 4. THE TITLE BLOCKS FOR THE ENGINEERS ARE LACKING THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM,
 PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL
 SIGNING AND SEALING THE PLAN, FAC61G15-23.002.
  
 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE
 BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE,
 OCCUPANCY CLASSIFICATION.
  
 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO
 BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL,
 FBC 107.
  
 7. FOR THE ROOF COVERING, INDICATE THE APPROVED
 ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF
 APPLICABLE.
  
 CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO
 ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED.
 THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE
 SUBMITTED AS A REVISION.
  
 8. REVISE PLAN TO INCLUDE COMPONENT AND CLADDING
 PRESSURES, FBC 1603.1.4.
  
 9. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1509.6.5,
 CLEARANCE BELOW RTU.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-04 Cont ID  
Sent By vperez Date 2017-01-04 Time 08:09 Rev Time 0.00
Received By vperez Date 2017-01-04 Time 08:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By vperez Date 2016-11-09 Time 08:59 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 08:59 Sent To  
Notes
2016-11-09 08:59:36APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR LIGHTNING
 PROTECTION AS NOTED ON PLANS , ETC. A NOTE WILL
 SUFFICE.
 2. PLEASE SHOW SPECIFIC CIRCUITS FEEDING UNITS AND
 WHERE CIRCUITS ORIGINATE,(PANELBOARD SCHEDULE.)
 3. ADDRESS BUILDING AND MECHANICAL COMMENTS.
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-04-10 Cont ID  
Sent By shill Date 2017-04-10 Time 07:08 Rev Time 0.00
Received By shill Date 2017-04-06 Time 14:57 Sent To  
Notes
2017-04-07 14:57:23RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-20 Cont ID  
Sent By shill Date 2017-03-20 Time 07:47 Rev Time 0.00
Received By shill Date 2017-03-15 Time 13:49 Sent To  
Notes
2017-03-16 13:49:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 14:36 Rev Time 0.00
Received By gjohnson Date 2016-12-07 Time 14:23 Sent To  
Notes
2016-12-07 14:23:45C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-12-07 Cont ID  
Sent By lmarchan Date 2016-12-07 Time 14:22 Rev Time 0.00
Received By lmarchan Date 2016-10-24 Time 12:53 Sent To  
Notes
2016-10-25 13:06:07C16

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 12:52 Rev Time 0.00
Received By ccole Date 2017-03-17 Time 12:52 Sent To B
Notes
2017-03-17 12:58:48MECHANICAL PROVISOS:
 3/17/17
  
 THE PLANS ARE APPROVED WITH THE FOLLOWING LIST OF
 PROVISOS:
  
 1) SUBMIT STRUCTURAL DETAILS FOR THE COOLING TOWER
 ACCESS PLATFORM AND PERMANENT LADDER.
  
 2) SUBMIT CHILLED WATER PIPING AND PIPING INSULATION
 SPECIFICATIONS.
  
 3) COMPLY WITH THE FBC-14 ACCESSIBILTY CODE FOR
 LOCATING THE TEMPORARY COOLING TOWER AND EQUIPMENT IN
 THE PARKING LOT- THE LOCATION OF THE EQUIPMENT SHALL
 NOT REDUCE THE NUMBER OF REQUIRED ACESSIBILE PARKING
 SPACES.
  
 4) SUBMIT BOTH PRELIMINARY AND FINAL COMMISSIONING
 REPORTS
  
 .CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-16 Cont ID  
Sent By ccole Date 2016-12-16 Time 09:19 Rev Time 0.00
Received By ccole Date 2016-12-16 Time 08:47 Sent To  
Notes
2016-12-16 09:35:252ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100664
 12/16/16
  
 1) IN REFERENCE TO 1ST REVIEW COMMENT #6, PLEASE
 PROVIDE STRUCTURAL DETAILS FOR THE NEW COOLING TOWER
 PLATFORM, GUARDRAILS, AND PERMANENT LADDER- SEE
 SECTIONS 304.11 AND 306.5 MECHANICAL, AND SECTION
 1509.6.4 FBC-14 BUILDING: THE LADDER SHALL EXTEND FROM
 THE ROOF SURFACE TO THE PLATFORM AND NOT REQUIRE THE
 USE OF A PORTABLE LADDER.- SEE THE NOTE FOR LADDER
 EXTENSION ON SHEET M002.
  
 2) IN REFERENCE TO 1ST REVIEW COMMENT #7, SHOW THE
 CLEARANCE DISTANCE MEASUREMENTS FROM THE RETURN
 DUCTWORK OF RTU-4 & 5 TO THE ROOF EDGES.
  
 3) IN REFERENCE TO 1ST REVIEW COMMENT #9, SHOW THE
 ROOFTOP CONDENSATE PIPING RUNS AND SUPPORT AND
 PROTECTION DETAILS.
  
 4) PLEASE PROVIDE A SITE PLAN SHOWING THE EXACT
 LOCATIONS OF THE TEMPORARY COOLING TOWERS, GENERATORS
 ETC.AND HOW THE EQUIPMENT WILL BE PROTECTED AGAINST
 DAMAGE- SECTION 303.4
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-01 Cont ID  
Sent By ccole Date 2016-11-01 Time 11:52 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 11:52 Sent To  
Notes
2016-11-01 12:00:001ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16100664
 11/1/16
  
 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF
 CURRENT CODE REFERENCES AND STANDARDS USED IN THE
 DESIGN OF THE PROJECT.
  
 2) THE MECHANICAL PLANS MUST BE DESIGNED BY A FLORIDA
 LICENSED ENGINEER PER FLORIDA STATUTE 471.003. THE SEAL
 ON THE PLANS INDICATES THE DESIGNER HAS A "CERTIFICATE"
 BUT IS NOT LICENSED.
  
 3) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION-
 AC SYSTEM COMMISSIONING IS REQUIRED.
 C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
 2A) C408.2.1 COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
 5. MEASURABLE CRITERIA FOR PERFORMANCE.
  
 3) SHEET M002: PROVIDE IN THE SCHEDULE THE EFFICIENCY
 RATING OF THE NEW EVAPCO COOLING TOWER- SEE TABLE
 C403.2.3(8) FBC-14 ENERGY CONSERVATION.
  
 4) PROVIDE WATER PIPING AND PIPE INSULATION
 SPECIFICATIONS. INDICATE THE SPACING OF THE PIPE
 SUPPORTS ON THE ROOF.
  
 5) S301: INDICATE THE CLEARANCE DISTANCE HEIGHT FROM
 THE FINISHED ROOF SURFACE TO THE BOTTOM OF THE COOLING
 TOWER SUPPORT BASE- REFER TO SECTION 102.8 AND TABLE
 1522.3 FBC-14 BUILDING.
  
 6) REFER TO SECTION 908.2 AND INDICATE HOW ACCESS TO
 THE COOLING TOWER WILL BE PROVIDED- THE PLANS DO NOT
 INDICATE ANY STAIRS OR PLATFORMS.
  
 7) REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING AND
 VERIFY THAT ALL MECHANICAL ROOFTOP EQUIPMENT IS NOT
 LOCATED WITHIN 10' OF ANY ROOF EDGE THAT DOES NOT HAVE
 A GUARD OR PARAPET AT A MINIMUM HEIGHT OF 42"- SEE
 SECTION 304.11 FBC-14 MECHANICAL.
  
 8) M101: SHOW THE CLEARANCE DISTANCE MEASUREMENTS FROM
 THE COOLING TOWER DISCHARGE TO THE RTU AIR INLETS- SEE
 SECTION 908.3.
  
 9) M201: THE CONDENSATE PIPING SPECIFIED IN DETAIL 1
 CANNOT DRAIN ONTO THE ROOF SURFACE AS SPECIFIED. THE
 PIPING SHALL TERMINATE AT AN APPROVED PLACE OF DISPOSAL
 SUCH AS A ROOF DRAIN, A DRY WELL, OR PERMEABLE GROUND
 WHERE IT WILL NOT BE A NUISANCE- SECTION 307.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 14:46 Rev Time 0.00
Received By shill Date 2016-12-27 Time 14:46 Sent To  
Notes
2016-12-27 14:46:38ALTHOUGH A PORTION OF THE PARCEL IS LOCATED IN THE
 SFHA, THE STRUCTURE IS LOCATED OUTSIDE OF THE SFHA
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 12:07 Rev Time 0.00
Received By shill Date 2016-10-31 Time 12:07 Sent To  
Notes
2016-10-31 12:08:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS
 STRUCTURE, FBC 1612. IF AVAILABLE, PROVIDE A SURVEY FOR
 THIS PROPERTY.
  
 THIS SHOULD BE SENT VIA EMAIL PRIOR TO RESUBMITTING.
  
 A COMPLETE REVIEW CANNOT BE DONE WITHOUT THIS
 INFORMATION.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-09 Cont ID  
Sent By gjohnson Date 2017-01-09 Time 14:36 Rev Time 0.00
Received By gjohnson Date 2017-01-09 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By gjohnson Date 2016-11-09 Time 15:20 Rev Time 0.00
Received By gjohnson Date 2016-11-09 Time 15:12 Sent To  
Notes
2016-11-09 15:24:181ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAIL FOR ROOF DRAIN IT IS UNCLEAR WHAT IS
 BEING REPLACED AND WHAT IS TO REMAIN. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN EXISTING 1BACKFLOW TO BE
 RECERTIFIED BY LIC. CONTRACTOR. PER WPB AMEND TO FBC
 107.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 14:28 Rev Time 0.00
Received By shill Date 2016-12-27 Time 14:28 Sent To  
Notes
2016-12-27 14:36:18ROOF PERMIT APPLICATION AND ROOFING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED
 PRIOR TO COMMENCEMENT OF ROOFING WORK.
  
 ROOFING TO COMPLY WITH THE DESIGN PRESSURES ON S201
  
 ZONE 1 -56.64
 ZONE 2 -94.86
 ZONE 3 -142.8
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2017-04-13 Cont ID  
Sent By shill Date 2017-04-13 Time 11:39 Rev Time 0.00
Received By shill Date 2017-04-13 Time 11:39 Sent To  
Notes
2017-04-13 11:39:34TERRACON
 RECEIVED VIA EMAIL; FORWARDED TO KC AND RECORDS
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2017-04-10 Cont ID  
Sent By shill Date 2017-04-10 Time 07:01 Rev Time 0.00
Received By shill Date 2017-04-10 Time 07:01 Sent To  
Notes
2017-04-10 06:41:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 PROVISO - AFTER ISSUANCE, CONTRACTOR IS TO COLOR COPY
 THE PLANS TO PROVIDE A SET FOR THE SI AS A 3RD SET IS
 NOT AVAILABLE AT THIS TIME.
  
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN - OK, ROUTED TO
 KEN CONRAD 4/10
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT - OK
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED - PROVISO, AFTER ISSUANCE CONTRACTOR IS TO
 MAKE 1 COLOR COPY FOR THE SI.
  
 G) N/A
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) OK
  
 2. THE COMPLETED SPECIAL INSPECTOR AGREEMENT SIGNED BY
 ALL PARTIES IS REQUIRED.
  
 THE COMPLETE THRESHOLD PACKAGE (SI AGREEMENT, RESUMES)
 MAY BE SENT VIA EMAIL.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-03-31 Cont ID  
Sent By shill Date 2017-03-31 Time 07:15 Rev Time 0.00
Received By shill Date 2017-03-31 Time 07:15 Sent To  
Notes
2017-03-31 07:16:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 4/6/17: 3RD SET WILL BE A PROVISO ITEM - AFTER
 ISSUANCE, CONTRACTOR IS TO COLOR COPY THE PLANS TO
 PROVIDE A SET FOR THE SI AS A 3RD SET IS NOT AVAILABLE
 AT THIS TIME.
 RE: FIRESTOPPING - PROVISO ITEM, PROVIDE INFORMATION IF
 APPLICABLE AT INSPECTION; SUBJECT TO FIELD INSPECTOR'S
 DISCRETION, A REVISION MAY BE REQUIRED
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By njwira Date 2016-12-15 Time 15:45 Rev Time 0.00
Received By njwira Date 2016-12-14 Time 17:07 Sent To  
Notes
***NONE***