| Plan Review Stops For Permit 16100664 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-10 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-10 |
Time |
06:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-20 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-20 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2017-03-20 07:44:35 | ****CORRECTIONS**** | | | REVISED 3/30, EMAILED ENGINEER AND CONTRACTOR | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC A 208.2, SP101 SHOWS THAT ACCESSIBLE PARKING | | | SPACES WILL BE USED FOR TEMPORARY MATERIAL STORAGE. IT | | | IS NOT CLEAR WHETHER THESE SPACES ARE EXTRA (OVER THE | | | MINIMUM NUMBER OF ACCESSIBLE SPACES REQUIRED FOR THIS | | | FACILITY), OR IF THEY ARE REQUIRED. | | | | | | REVISE PLAN TO INCLUDE THE TOTAL NUMBER OF PARKING | | | SPACES, NUMBER OF ACCESSIBLE SPACES. IF THE SPACES ARE | | | REQUIRED, PROVIDE A PLAN TO SHOW HOW THE MINIMUM NUMBER | | | OF ACCESSIBLE PARKING SPACES WILL BE PROVIDED. | | | | | | IT IS POSSIBLE THAT THIS CAN BE ADDRESSED VIA EMAIL AND | | | THAT THIS CAN BE A PROVISO ITEM. DESIGNER OF RECORD MAY | | | PROVIDE THE INFORMATION VIA EMAIL FOR PRELIMINARY | | | REVIEW. DESIGNER OF RECORD IS TO PROPOSE A PROVISO | | | CONDITION. | | | | | | 2. A101 REVISION BAR SHOWS FOUR REVISIONS AND THE PAGE | | | WAS SIGNED ON 3/13/17, BUT THE CLOUDS ARE ALL NUMBERED | | | 1 (10/10/16). IT IS NOT CLEAR WHAT HAS BEEN CHANGED | | | AFTER REVIEW #3 DATED 1/19/17. REVISE PLAN TO CLOUD ALL | | | CHANGES AND CORRELATE CHANGES WITH REVISION NUMBERS, | | | FBC 107, OR CLARIFY WHAT HAS CHANGED ON THIS SHEET FOR | | | REVISIONS #2, #3, & #4, FBC 107. | | | | | | 3. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE | | | TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR | | | PERMIT ISSUANCE. | | | | | | 4. REVISE PLAN TO INCLUDE BUILDING HEIGHT. ALTERNATIVE | | | WAY TO SHOW BUILDING HEIGHT MAY BE ACCEPTABLE, | | | FS553.79(7), THRESHOLD BUILDINGS. | | | | | | OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED | | | FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS | | | SHOULD BE MARKED "VOID" OR "OLD SHEETS". | | | | | | THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY | | | DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS | | | THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS. | | | | | | ALL OLD VOIDED SHEETS SHOULD BE MARKED "VOID" AND | | | RETAINED IN THE SUBMITTAL. IT IS STRONGLY RECOMMENDED | | | THAT ALL VOIDED SHEETS BE RETAINED - DO NOT DISCARD | | | VOIDED SHEETS TO LEAVE ONLY ONE COPY OF EACH VOIDED | | | PAGE. FAILURE TO RETAIN ALL DOCUMENTS IN THE SUBMITTAL | | | PACKAGE MAY RESULT IN PLAN REVIEW DELAYS. | | | | | | A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED | | | WILL HELP TO EXPEDITE YOUR PLAN REVIEW. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-27 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-27 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2016-12-27 15:14:07 | PROVISO | | | ADDRESS PLAN REVIEW COMMENTS MADE BY OTHER TRADES | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-31 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-31 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2016-10-31 12:09:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED | | | IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN | | | SHOWING LOCATION OF PROPOSED IMPROVEMENT. | | | | | | 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY | | | COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED | | | BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN | | | "LICENSE"). | | | | | | 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN | | | THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN | | | CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND | | | SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL | | | COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE | | | COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA | | | BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD | | | WITH A COPY OF A CERTIFICATE OF COMPLETION, | | | FAC61G15-22.001. | | | | | | THE WEBSITE (MYFLORIDALICENSE.ORG) HAS NOT BEEN UPDATED | | | TO REFLECT THAT MR. COOKE, MR. DAVIS, MR. JONES HAS | | | TAKEN THE COURSE. CONTACT FBPE FOR MORE INFORMATION. | | | | | | 4. THE TITLE BLOCKS FOR THE ENGINEERS ARE LACKING THE | | | CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM, | | | PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL | | | SIGNING AND SEALING THE PLAN, FAC61G15-23.002. | | | | | | 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE | | | BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE, | | | OCCUPANCY CLASSIFICATION. | | | | | | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO | | | BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, | | | FBC 107. | | | | | | 7. FOR THE ROOF COVERING, INDICATE THE APPROVED | | | ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF | | | APPLICABLE. | | | | | | CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO | | | ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED. | | | THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE | | | SUBMITTED AS A REVISION. | | | | | | 8. REVISE PLAN TO INCLUDE COMPONENT AND CLADDING | | | PRESSURES, FBC 1603.1.4. | | | | | | 9. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1509.6.5, | | | CLEARANCE BELOW RTU. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-04 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-04 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-11-09 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-11-09 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2016-11-09 08:59:36 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR LIGHTNING | | | PROTECTION AS NOTED ON PLANS , ETC. A NOTE WILL | | | SUFFICE. | | | 2. PLEASE SHOW SPECIFIC CIRCUITS FEEDING UNITS AND | | | WHERE CIRCUITS ORIGINATE,(PANELBOARD SCHEDULE.) | | | 3. ADDRESS BUILDING AND MECHANICAL COMMENTS. | | | 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-10 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-06 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2017-04-07 14:57:23 | RESUB ROUTED TO SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-20 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-15 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2017-03-16 13:49:44 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-01-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-09 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-12-07 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-12-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-12-07 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-10-24 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2017-03-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-03-17 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-03-17 |
Time |
12:52 |
Sent To |
B |
|
| Notes |
| 2017-03-17 12:58:48 | MECHANICAL PROVISOS: | | | 3/17/17 | | | | | | THE PLANS ARE APPROVED WITH THE FOLLOWING LIST OF | | | PROVISOS: | | | | | | 1) SUBMIT STRUCTURAL DETAILS FOR THE COOLING TOWER | | | ACCESS PLATFORM AND PERMANENT LADDER. | | | | | | 2) SUBMIT CHILLED WATER PIPING AND PIPING INSULATION | | | SPECIFICATIONS. | | | | | | 3) COMPLY WITH THE FBC-14 ACCESSIBILTY CODE FOR | | | LOCATING THE TEMPORARY COOLING TOWER AND EQUIPMENT IN | | | THE PARKING LOT- THE LOCATION OF THE EQUIPMENT SHALL | | | NOT REDUCE THE NUMBER OF REQUIRED ACESSIBILE PARKING | | | SPACES. | | | | | | 4) SUBMIT BOTH PRELIMINARY AND FINAL COMMISSIONING | | | REPORTS | | | | | | .CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-12-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-16 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-16 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2016-12-16 09:35:25 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100664 | | | 12/16/16 | | | | | | 1) IN REFERENCE TO 1ST REVIEW COMMENT #6, PLEASE | | | PROVIDE STRUCTURAL DETAILS FOR THE NEW COOLING TOWER | | | PLATFORM, GUARDRAILS, AND PERMANENT LADDER- SEE | | | SECTIONS 304.11 AND 306.5 MECHANICAL, AND SECTION | | | 1509.6.4 FBC-14 BUILDING: THE LADDER SHALL EXTEND FROM | | | THE ROOF SURFACE TO THE PLATFORM AND NOT REQUIRE THE | | | USE OF A PORTABLE LADDER.- SEE THE NOTE FOR LADDER | | | EXTENSION ON SHEET M002. | | | | | | 2) IN REFERENCE TO 1ST REVIEW COMMENT #7, SHOW THE | | | CLEARANCE DISTANCE MEASUREMENTS FROM THE RETURN | | | DUCTWORK OF RTU-4 & 5 TO THE ROOF EDGES. | | | | | | 3) IN REFERENCE TO 1ST REVIEW COMMENT #9, SHOW THE | | | ROOFTOP CONDENSATE PIPING RUNS AND SUPPORT AND | | | PROTECTION DETAILS. | | | | | | 4) PLEASE PROVIDE A SITE PLAN SHOWING THE EXACT | | | LOCATIONS OF THE TEMPORARY COOLING TOWERS, GENERATORS | | | ETC.AND HOW THE EQUIPMENT WILL BE PROTECTED AGAINST | | | DAMAGE- SECTION 303.4 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-11-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-01 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-01 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2016-11-01 12:00:00 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16100664 | | | 11/1/16 | | | | | | 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF | | | CURRENT CODE REFERENCES AND STANDARDS USED IN THE | | | DESIGN OF THE PROJECT. | | | | | | 2) THE MECHANICAL PLANS MUST BE DESIGNED BY A FLORIDA | | | LICENSED ENGINEER PER FLORIDA STATUTE 471.003. THE SEAL | | | ON THE PLANS INDICATES THE DESIGNER HAS A "CERTIFICATE" | | | BUT IS NOT LICENSED. | | | | | | 3) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION- | | | AC SYSTEM COMMISSIONING IS REQUIRED. | | | C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION | | | REQUIREMENTS. | | | PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE | | | REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE | | | OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN | | | ACCORDANCE THE PROVISIONS OF THIS SECTION. | | | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE | | | PROVISIONS FOR COMMISSIONING AND COMPLETION | | | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE | | | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER | | | REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE | | | GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE | | | OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS | | | C408.2.4 AND C408.2.5. | | | | | | 2A) C408.2.1 COMMISSIONING PLAN. | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED | | | DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL | | | INCLUDE THE FOLLOWING ITEMS: | | | | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED | | | TO CALIBRATIONS AND ECONOMIZER CONTROLS. | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER | | | DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE. | | | | | | 3) SHEET M002: PROVIDE IN THE SCHEDULE THE EFFICIENCY | | | RATING OF THE NEW EVAPCO COOLING TOWER- SEE TABLE | | | C403.2.3(8) FBC-14 ENERGY CONSERVATION. | | | | | | 4) PROVIDE WATER PIPING AND PIPE INSULATION | | | SPECIFICATIONS. INDICATE THE SPACING OF THE PIPE | | | SUPPORTS ON THE ROOF. | | | | | | 5) S301: INDICATE THE CLEARANCE DISTANCE HEIGHT FROM | | | THE FINISHED ROOF SURFACE TO THE BOTTOM OF THE COOLING | | | TOWER SUPPORT BASE- REFER TO SECTION 102.8 AND TABLE | | | 1522.3 FBC-14 BUILDING. | | | | | | 6) REFER TO SECTION 908.2 AND INDICATE HOW ACCESS TO | | | THE COOLING TOWER WILL BE PROVIDED- THE PLANS DO NOT | | | INDICATE ANY STAIRS OR PLATFORMS. | | | | | | 7) REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING AND | | | VERIFY THAT ALL MECHANICAL ROOFTOP EQUIPMENT IS NOT | | | LOCATED WITHIN 10' OF ANY ROOF EDGE THAT DOES NOT HAVE | | | A GUARD OR PARAPET AT A MINIMUM HEIGHT OF 42"- SEE | | | SECTION 304.11 FBC-14 MECHANICAL. | | | | | | 8) M101: SHOW THE CLEARANCE DISTANCE MEASUREMENTS FROM | | | THE COOLING TOWER DISCHARGE TO THE RTU AIR INLETS- SEE | | | SECTION 908.3. | | | | | | 9) M201: THE CONDENSATE PIPING SPECIFIED IN DETAIL 1 | | | CANNOT DRAIN ONTO THE ROOF SURFACE AS SPECIFIED. THE | | | PIPING SHALL TERMINATE AT AN APPROVED PLACE OF DISPOSAL | | | SUCH AS A ROOF DRAIN, A DRY WELL, OR PERMEABLE GROUND | | | WHERE IT WILL NOT BE A NUISANCE- SECTION 307.2.1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
N |
Date |
2016-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-27 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-27 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2016-12-27 14:46:38 | ALTHOUGH A PORTION OF THE PARCEL IS LOCATED IN THE | | | SFHA, THE STRUCTURE IS LOCATED OUTSIDE OF THE SFHA | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-31 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-31 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2016-10-31 12:08:06 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS | | | STRUCTURE, FBC 1612. IF AVAILABLE, PROVIDE A SURVEY FOR | | | THIS PROPERTY. | | | | | | THIS SHOULD BE SENT VIA EMAIL PRIOR TO RESUBMITTING. | | | | | | A COMPLETE REVIEW CANNOT BE DONE WITHOUT THIS | | | INFORMATION. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-01-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-09 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-09 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-09 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-09 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2016-11-09 15:24:18 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE DETAIL FOR ROOF DRAIN IT IS UNCLEAR WHAT IS | | | BEING REPLACED AND WHAT IS TO REMAIN. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 2. PROVIDE NOTE ON PLAN EXISTING 1BACKFLOW TO BE | | | RECERTIFIED BY LIC. CONTRACTOR. PER WPB AMEND TO FBC | | | 107.2.1 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-12-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-27 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-27 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2016-12-27 14:36:18 | ROOF PERMIT APPLICATION AND ROOFING PRODUCT APPROVALS | | | REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED | | | PRIOR TO COMMENCEMENT OF ROOFING WORK. | | | | | | ROOFING TO COMPLY WITH THE DESIGN PRESSURES ON S201 | | | | | | ZONE 1 -56.64 | | | ZONE 2 -94.86 | | | ZONE 3 -142.8 | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2017-04-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-13 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-13 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2017-04-13 11:39:34 | TERRACON | | | RECEIVED VIA EMAIL; FORWARDED TO KC AND RECORDS | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-10 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-10 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2017-04-10 06:41:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | PROVISO - AFTER ISSUANCE, CONTRACTOR IS TO COLOR COPY | | | THE PLANS TO PROVIDE A SET FOR THE SI AS A 3RD SET IS | | | NOT AVAILABLE AT THIS TIME. | | | | | | 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN - OK, ROUTED TO | | | KEN CONRAD 4/10 | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG., REQUIRED STATEMENT - OK | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED - PROVISO, AFTER ISSUANCE CONTRACTOR IS TO | | | MAKE 1 COLOR COPY FOR THE SI. | | | | | | G) N/A | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) OK | | | | | | 2. THE COMPLETED SPECIAL INSPECTOR AGREEMENT SIGNED BY | | | ALL PARTIES IS REQUIRED. | | | | | | THE COMPLETE THRESHOLD PACKAGE (SI AGREEMENT, RESUMES) | | | MAY BE SENT VIA EMAIL. | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2017-03-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-31 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-31 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2017-03-31 07:16:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 4/6/17: 3RD SET WILL BE A PROVISO ITEM - AFTER | | | ISSUANCE, CONTRACTOR IS TO COLOR COPY THE PLANS TO | | | PROVIDE A SET FOR THE SI AS A 3RD SET IS NOT AVAILABLE | | | AT THIS TIME. | | | RE: FIRESTOPPING - PROVISO ITEM, PROVIDE INFORMATION IF | | | APPLICABLE AT INSPECTION; SUBJECT TO FIELD INSPECTOR'S | | | DISCRETION, A REVISION MAY BE REQUIRED | | | | | | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN | | | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN | | | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN | | | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 | | | PERSONS. | | | | | | A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING | | | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S | | | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS | | | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS | | | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH | | | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND | | | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE | | | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL | | | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER | | | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. | | | | | | C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. | | | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. | | | | | | F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, | | | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING | | | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE | | | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR | | | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN | | | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR | | | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE | | | IN BLACK & WHITE. | | | | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD | | | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS | | | CONCERNING SPECIAL INSPECTORS. | | | | | | G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, | | | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT | | | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING | | | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND | | | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING | | | DOCUMENTS BY THE CONTRACTOR. | | | | | | H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL | | | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 | | | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. | | | | | | I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES | | | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER | | | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE | | | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR | | | WALLS AND CEILINGS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-12-15 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-12-14 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2016-11-16 |
|
|
Cont ID |
|
| Sent By |
JR |
Date |
2016-11-16 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-11-10 |
Time |
14:17 |
Sent To |
I |
|
| Notes |
|
|