Plan Review Details - Permit 16100663
Plan Review Stops For Permit 16100663
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-04-07 Cont ID  
Sent By shill Date 2017-04-07 Time 12:14 Rev Time 0.00
Received By shill Date 2017-04-07 Time 12:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 07:08 Rev Time 0.00
Received By shill Date 2017-03-30 Time 07:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-03-28 Cont ID  
Sent By shill Date 2017-03-27 Time 13:05 Rev Time 0.00
Received By shill Date 2017-03-27 Time 12:57 Sent To  
Notes
2017-03-28 17:10:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS553.79, PROVIDE THE BUILDING HEIGHT. IF THIS IS A
 THRESHOLD BUILDING, A SPECIAL INSPECTOR MAY BE
 REQUIRED.
  
 THE PLANS HAVE BEEN STAMPED. THIS INFORMATION MAY BE
 PROVIDED IN A SIGNED AND SEALED LETTER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 07:13 Rev Time 0.00
Received By shill Date 2016-12-14 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 09:49 Rev Time 0.00
Received By shill Date 2016-10-31 Time 09:49 Sent To  
Notes
2016-10-31 10:10:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED
 IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN
 SHOWING LOCATION OF PROPOSED IMPROVEMENT.
  
 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY
 COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED
 BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN
 "LICENSE").
  
 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND
 SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL
 COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE
 COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA
 BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD
 WITH A COPY OF A CERTIFICATE OF COMPLETION,
 FAC61G15-22.001.
  
 THE WEBSITE HAS NOT BEEN UPDATED TO REFLECT THAT MR.
 COOKE AND MR. DAVIS HAVE TAKEN THE COURSE. CONTACT FBPE
 FOR MORE INFORMATION.
  
 4. THE TITLE BLOCK FOR THE ENGINEERS IS LACKING THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM,
 PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL
 SIGNING AND SEALING THE PLAN.
  
 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE
 BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE,
 OCCUPANCY CLASSIFICATION.
  
 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO
 BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL,
 FBC 107.
  
 7. FOR THE ROOF COVERING, INDICATE THE APPROVED
 ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF
 APPLICABLE.
  
 CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO
 ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED.
 THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE
 SUBMITTED AS A REVISION.
  
 8. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. (THIS IS REQUIRED FOR BOTH A SHEETS AND S
 SHEETS.)
  
 9. METHOD OF MOUNTING OF EQUIPMENT NOT CLEAR, PROVIDE A
 DETAIL, FBC 107, FBC 1609. IF USING A STAND, PROVIDE
 THE PRODUCT APPROVAL. ON THE PRODUCT APPROVAL, INDICATE
 THE INSTALLATION PROPOSED. NOTE THAT NO STRUCTURAL
 DRAWINGS WERE SUBMITTED. WHEN RESUBMITTING, SHOW
 COMPLIANCE WITH FBC TABLE 1509.6.5 IF APPLICABLE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-04 Cont ID  
Sent By vperez Date 2017-01-04 Time 11:16 Rev Time 0.00
Received By vperez Date 2017-01-04 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By vperez Date 2016-11-09 Time 08:56 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 08:56 Sent To  
Notes
2016-11-09 08:56:35APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR LIGHTNING
 PROTECTION AS NOTED ON PLANS , ETC. A NOTE WILL
 SUFFICE.
 2. PLEASE SHOW SPECIFIC CIRCUITS FEEDING UNITS AND
 WHERE CIRCUITS ORIGINATE,(PANELBOARD SCHEDULE.)
 3. ADDRESS BUILDING AND MECHANICAL COMMENTS.
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-04-24 Cont ID  
Sent By ccole Date 2017-04-24 Time 12:13 Rev Time 0.00
Received By ccole Date 2017-04-20 Time 12:23 Sent To  
Notes
2017-04-21 12:23:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-04-07 Cont ID  
Sent By shill Date 2017-04-07 Time 12:14 Rev Time 0.00
Received By shill Date 2017-04-05 Time 14:35 Sent To  
Notes
2017-04-06 14:35:51RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-29 Cont ID  
Sent By gjohnson Date 2017-03-29 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2017-03-15 Time 14:39 Sent To  
Notes
2017-03-15 14:39:51C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-19 Cont ID  
Sent By jroach Date 2017-01-19 Time 14:10 Rev Time 0.00
Received By jroach Date 2016-12-07 Time 14:18 Sent To  
Notes
2016-12-07 14:19:37C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-23 Cont ID  
Sent By gjohnson Date 2016-11-23 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2016-10-24 Time 13:03 Sent To  
Notes
2016-10-25 13:03:34C12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-04-24 Cont ID  
Sent By ccole Date 2017-04-24 Time 12:12 Rev Time 0.00
Received By ccole Date 2017-04-24 Time 12:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-04-07 Time 08:47 Rev Time 0.00
Received By ccole Date 2017-04-07 Time 07:03 Sent To  
Notes
2017-04-07 09:38:174TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16100663
 4/7/16
  
 1) THE SUBMITTED LETTERS FROM MW/DAVIS DUMAS &
 ASSOCIATES, INC. JIMMY JEFFCOAT PE FROM TRANE, ALONG
 WITH THE DATA REPORTS FOR THE CONDENSERS AND COILS ARE
 NOT INDICATING THAT THE THE TWO COMPONENTS OF THE
 PROPOSED DX SYSTEM- NEW TRANE CONDENSERS PAIRED WITH
 THE NEW TRANE AHU COILS- WILL MEET THE EFFICIENCY
 RATING WHEN TESTED IN ACCORDANCE WITH AHRI 340/360- SEE
  
 TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. IN
 ACCORDANCE WITH SECTION C101.4.7 THE MATCHING OF THE
 PROPOSED SYSTEM COMPONENTS CAN BE VERIFIED BY AHRI
 DATA, HOWEVER THE DATA SUBMITTED IS VERYING COMPLIANCE
 FOR EACH COMPONENT INDIVIDUALLY - THE CONDENSERS UNDER
 AHRI 365, AND THE COILS UNDER AHRI 410. I AM NOT SEEING
 ANY DATA OR LANGUAGE IN EITHER OF THE LETTERS
  
 THAT STATES SPECIFICALLY THAT THE TWO COMPONENTS
 FUNCTIONING TOGETHER WILL MEET OR EXCEED THE EFFIENCIES
 REQUIRED BYTABLE C403.2.3(1).
  
 ADDITIONALLY, PLEASE NOTE THAT THE LETTER FROM JIMMY
 JEFFCOAT PE REQUIRES AN ORIGNIAL SIGNATURE AND SEAL PER
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-24 Cont ID  
Sent By ccole Date 2017-03-24 Time 12:00 Rev Time 0.00
Received By ccole Date 2017-03-24 Time 07:13 Sent To  
Notes
2017-03-24 12:06:073RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100663
 3/24/17
  
 1) THE REQUESTED DOCUMENTATION OF AHRI CERTIFICATION
 FOR THE REPLACED AC SYSTEMS HAS NOT BEEN PROVIDED.
 PLEASE SEE EXCEPTION #2 PRINTED BELOW
  
 SECTION C101.4.7 FBC-14 ENERGY CONSERVATION: BUILDING
 SYSTEMS AND COMPONENTS.
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS AND COMPONENTS WHERE NEW PRODUCTS ARE
 INSTALLED OR REPLACED IN EXISTING BUILDINGS, AND FOR
 WHICH A PERMIT MUST BE OBTAINED. NEW PRODUCTS SHALL
 MEET THE MINIMUM EFFICIENCIES ALLOWED BY THIS CODE FOR
 THE FOLLOWING SYSTEMS AND COMPONENTS:
  
 HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS.
  
 SERVICE WATER OR POOL HEATING SYSTEMS.
  
 ELECTRICAL SYSTEMS AND MOTORS.
  
 LIGHTING SYSTEMS.
  
 REPLACEMENT FENESTRATION.
  
 EXCEPTIONS:
  
 1. WHERE PART OF A FUNCTIONAL UNIT IS REPAIRED OR
 REPLACED. FOR EXAMPLE, REPLACEMENT OF AN ENTIRE HVAC
 SYSTEM IS NOT REQUIRED BECAUSE A NEW COMPRESSOR OR
 OTHER PART DOES NOT MEET CODE WHEN INSTALLED WITH AN
 OLDER SYSTEM.
  
 2. IF THE UNIT BEING REPLACED IS ITSELF A FUNCTIONAL
 UNIT, SUCH AS A CONDENSER, IT DOES NOT CONSTITUTE A
 REPAIR. OUTDOOR AND INDOOR UNITS THAT ARE NOT DESIGNED
 TO BE OPERATED TOGETHER MUST MEET THE U.S. DEPARTMENT
 OF ENERGY CERTIFICATION REQUIREMENTS CONTAINED IN
 SECTION C403.2.3. MATCHED SYSTEMS ARE REQUIRED; THIS
 MATCH MAY BE VERIFIED BY ANY ONE OF THE FOLLOWING
 MEANS:
  
 A. AHRI DATA.
  
 B. ACCREDITED LABORATORY.
  
 C. MANUFACTURER'S LETTER.
  
 D. LETTER FROM REGISTERED PROFESSIONAL ENGINEER (P.E.),
 STATE OF FLORIDA.
  
 3. WHERE EXISTING COMPONENTS ARE UTILIZED WITH A
 REPLACEMENT SYSTEM, SUCH AS AIR DISTRIBUTION SYSTEM
 DUCTS OR ELECTRICAL WIRING FOR LIGHTS, SUCH COMPONENTS
 OR CONTROLS NEED NOT MEET CODE IF MEETING CODE WOULD
 REQUIRE THAT COMPONENT?S REPLACEMENT.
  
 4. REPLACEMENT EQUIPMENT THAT WOULD REQUIRE EXTENSIVE
 REVISIONS TO OTHER SYSTEMS, EQUIPMENT OR ELEMENTS OF A
 BUILDING WHERE SUCH REPLACEMENT IS A LIKE-FOR-LIKE
 REPLACEMENT, SUCH AS THROUGH-THE-WALL CONDENSING UNITS
 AND PTACS, CHILLERS, AND COOLING TOWERS IN CONFINED
 SPACES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By ccole Date 2016-12-13 Time 17:15 Rev Time 0.00
Received By ccole Date 2016-12-13 Time 17:11 Sent To  
Notes
2016-12-13 17:20:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100663
 12/13/16
  
 1) PROVIDE AHRI CERTIFCATION FOR THE REPLACED SYSTEMS-
 SECTION C101.4.7 FBC-14 ENERGY CONSERVATION.
  
 2) IN REFERENCE TO COMMENT #6 FROM THE 1ST REVIEW,
 VERIFY THE SCREEN WALLS, WHICH ARE ALSO CONSIDERED
 GUARDS, HAVE ADEQUATE STRENGTH AND ATTACHMENT PER
 SECTION 1607.8 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-01 Cont ID  
Sent By ccole Date 2016-11-01 Time 10:41 Rev Time 0.00
Received By ccole Date 2016-11-01 Time 10:40 Sent To  
Notes
2016-11-01 11:01:181ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16100663
 11/1/16
  
 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF
 CURRENT CODE REFERENCES AND STANDARDS USED IN THE
 DESIGN OF THE PROJECT.
  
 2) THE MECHANICAL PLANS MUST BE DESIGNED BY A FLORIDA
 LICENSED ENGINEER PER FLORIDA STATUTE 471.003. THE SEAL
 ON THE PLANS INDICATES THE DESIGNER HAS A "CERTIFICATE"
 BUT IS NOT LICENSED.
  
 3) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION-
 AC SYSTEM COMMISSIONING IS REQUIRED.
 C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
 2A) C408.2.1 COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
 5. MEASURABLE CRITERIA FOR PERFORMANCE.
  
 4) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 INSTALLATION OF THE ROOF TOP AC EQUIPMENT PER SECTION
 301.15 FBC-14 MECHANICAL. PROVIDE ON THE PLAN THE WIND
 LOAD DESIGN CRITERIA AND COMPLETE DETAILS FOR ANCHORING
 THE ACCU'S AND OSA FAN TO THE ROOF STRUCTURE.
  
 5) REFER TO SECTION 102.8 FBC-14 BUILDING: ALL NEW AND
 REPLACED MECHANICAL EQUIPMENT MUST BE RAISED ABOVE THE
 ROOF SURFACE AT THE CLEARANCE HEIGHTS SPECIFIED IN
 TABLE 1522.3. PROVIDE DETAILS ON THE PLAN TO INDICATE
 COMPLIANCE.
  
 6) REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING AND
 VERIFY THAT ALL MECHANICAL ROOFTOP EQUIPMENT IS NOT
 LOCATED WITHIN 10' OF ANY ROOF EDGE THAT DOES NOT HAVE
 A GUARD OR PARAPET AT A MINIMUM HEIGHT OF 42"- SEE
 SECTION 304.11 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 07:28 Rev Time 0.00
Received By shill Date 2016-12-15 Time 07:28 Sent To  
Notes
2016-12-15 07:29:28ALTHOUGH A SMALL PORTION OF THE PARCEL IS LOCATED IN
 THE SFHA, THIS STRUCTURE IS LOCATED OUTSIDE OF THE SFHA
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 09:23 Rev Time 0.00
Received By shill Date 2016-10-31 Time 09:23 Sent To  
Notes
2016-10-31 09:44:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS
 STRUCTURE, FBC 1612. IF AVAILABLE, PROVIDE A SURVEY FOR
 THIS PROPERTY.
  
 THIS MAY BE SENT VIA EMAIL PRIOR TO RESUBMITTING.
  
 A COMPLETE REVIEW CANNOT BE DONE WITHOUT THIS
 INFORMATION.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-03-29 Cont ID  
Sent By gjohnson Date 2017-03-29 Time 12:52 Rev Time 0.00
Received By gjohnson Date 2017-03-29 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 15:58 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 15:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-23 Cont ID  
Sent By gjohnson Date 2016-11-23 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2016-11-23 Time 13:41 Sent To  
Notes
2016-11-23 13:41:021ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAIL FOR ROOF DRAIN IT IS UNCLEAR WHAT IS
 BEING REPLACED AND WHAT IS TO REMAIN. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN EXISTING 1" BACKFLOW TO BE
 RECERTIFIED BY LIC. CONTRACTOR. PER WPB AMEND TO FBC
 107.2.1
  
 3. ADDRESS COMMENTS FROM BUILDING AND MECHANICAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-12-15 Cont ID  
Sent By shill Date 2016-12-15 Time 07:34 Rev Time 0.00
Received By shill Date 2016-12-15 Time 07:34 Sent To  
Notes
2016-12-15 07:40:01A SEPARATE PERMIT IS REQUIRED FOR THE ROOF COVERING. AN
 APPLICATION, PRODUCT APPROVALS REVIEWED BY DESIGNER OF
 RECORD, PROPOSED ASSEMBLY & FASTENING METHOD INDICATED,
 AND ENGINEERING (IF APPLICABLE) IS REQUIRED TO BE
 SUBMITTED PRIOR TO ROOF COVERING INSTALLATION.
  
 PLANS SPECIFY PVC INSULATED AND STANDING SEAM METAL
 ROOFS
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-01-19 Cont ID  
Sent By jroach Date 2017-01-19 Time 14:10 Rev Time 0.00
Received By jroach Date 2017-01-19 Time 14:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-17 Cont ID  
Sent By JR Date 2016-11-17 Time 11:27 Rev Time 0.00
Received By jroach Date 2016-11-17 Time 09:56 Sent To  
Notes
2016-11-17 11:27:19ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.17.2016
 PERMIT NO.: 16100663
 ADDRESS: 1111 S. FLAGLER DRIVE
 CONTRACTOR/CONTACT: MIKE EVANS
 TELEPHONE NO.: 205.313.3027
 SCOPE OF REVIEW: ROOFTOP HVAC, ROOFING DEMOLITION AND
 REPLACEMENT
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A CROSS-SECTION OR SIMILAR DRAWING
 SHOWING THAT WITH THE DEMOLITION OF THE PARAPET THAT
 THE ROOF-MOUNTED HVAC EQUIPMENT WILL NOT BE VISIBLE
 FROM ADJACENT PROPERTY OR THE PUBLIC RIGHT-OF-WAY.
  
 2. PLEASE EXPLAIN THE BASIS FOR REMOVING THE DECORATIVE
 PARAPET FROM THE ENTIRE STRUCTURE. STAFF IS CONCERNED
 AND DOES NOT SUPPORT REMOVAL OF THIS ELEMENT. IT IS ONE
 OF THE PRIMARY ARCHITECTURAL ELEMENTS THAT EXISTS ON
 THIS BUILDING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved