| Plan Review Stops For Permit 16100663 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2017-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-07 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-07 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2017-03-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-30 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-30 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2017-03-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-03-27 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-03-27 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2017-03-28 17:10:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FS553.79, PROVIDE THE BUILDING HEIGHT. IF THIS IS A | | | THRESHOLD BUILDING, A SPECIAL INSPECTOR MAY BE | | | REQUIRED. | | | | | | THE PLANS HAVE BEEN STAMPED. THIS INFORMATION MAY BE | | | PROVIDED IN A SIGNED AND SEALED LETTER. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-15 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-14 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-31 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-31 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2016-10-31 10:10:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED | | | IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN | | | SHOWING LOCATION OF PROPOSED IMPROVEMENT. | | | | | | 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY | | | COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED | | | BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN | | | "LICENSE"). | | | | | | 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN | | | THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN | | | CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND | | | SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL | | | COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE | | | COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA | | | BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD | | | WITH A COPY OF A CERTIFICATE OF COMPLETION, | | | FAC61G15-22.001. | | | | | | THE WEBSITE HAS NOT BEEN UPDATED TO REFLECT THAT MR. | | | COOKE AND MR. DAVIS HAVE TAKEN THE COURSE. CONTACT FBPE | | | FOR MORE INFORMATION. | | | | | | 4. THE TITLE BLOCK FOR THE ENGINEERS IS LACKING THE | | | CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM, | | | PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL | | | SIGNING AND SEALING THE PLAN. | | | | | | 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE | | | BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE, | | | OCCUPANCY CLASSIFICATION. | | | | | | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO | | | BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, | | | FBC 107. | | | | | | 7. FOR THE ROOF COVERING, INDICATE THE APPROVED | | | ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF | | | APPLICABLE. | | | | | | CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO | | | ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED. | | | THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE | | | SUBMITTED AS A REVISION. | | | | | | 8. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC | | | 1603.1.4. (THIS IS REQUIRED FOR BOTH A SHEETS AND S | | | SHEETS.) | | | | | | 9. METHOD OF MOUNTING OF EQUIPMENT NOT CLEAR, PROVIDE A | | | DETAIL, FBC 107, FBC 1609. IF USING A STAND, PROVIDE | | | THE PRODUCT APPROVAL. ON THE PRODUCT APPROVAL, INDICATE | | | THE INSTALLATION PROPOSED. NOTE THAT NO STRUCTURAL | | | DRAWINGS WERE SUBMITTED. WHEN RESUBMITTING, SHOW | | | COMPLIANCE WITH FBC TABLE 1509.6.5 IF APPLICABLE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2017-01-04 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2017-01-04 |
Time |
11:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-11-09 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-11-09 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-11-09 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2016-11-09 08:56:35 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR LIGHTNING | | | PROTECTION AS NOTED ON PLANS , ETC. A NOTE WILL | | | SUFFICE. | | | 2. PLEASE SHOW SPECIFIC CIRCUITS FEEDING UNITS AND | | | WHERE CIRCUITS ORIGINATE,(PANELBOARD SCHEDULE.) | | | 3. ADDRESS BUILDING AND MECHANICAL COMMENTS. | | | 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2017-04-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-04-24 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-20 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2017-04-21 12:23:20 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2017-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-04-07 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-04-05 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2017-04-06 14:35:51 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-03-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-29 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-15 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-01-19 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-12-07 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-11-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-23 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-24 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2017-04-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-04-24 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-24 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2017-04-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-04-07 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-04-07 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2017-04-07 09:38:17 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100663 | | | 4/7/16 | | | | | | 1) THE SUBMITTED LETTERS FROM MW/DAVIS DUMAS & | | | ASSOCIATES, INC. JIMMY JEFFCOAT PE FROM TRANE, ALONG | | | WITH THE DATA REPORTS FOR THE CONDENSERS AND COILS ARE | | | NOT INDICATING THAT THE THE TWO COMPONENTS OF THE | | | PROPOSED DX SYSTEM- NEW TRANE CONDENSERS PAIRED WITH | | | THE NEW TRANE AHU COILS- WILL MEET THE EFFICIENCY | | | RATING WHEN TESTED IN ACCORDANCE WITH AHRI 340/360- SEE | | | | | | TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. IN | | | ACCORDANCE WITH SECTION C101.4.7 THE MATCHING OF THE | | | PROPOSED SYSTEM COMPONENTS CAN BE VERIFIED BY AHRI | | | DATA, HOWEVER THE DATA SUBMITTED IS VERYING COMPLIANCE | | | FOR EACH COMPONENT INDIVIDUALLY - THE CONDENSERS UNDER | | | AHRI 365, AND THE COILS UNDER AHRI 410. I AM NOT SEEING | | | ANY DATA OR LANGUAGE IN EITHER OF THE LETTERS | | | | | | THAT STATES SPECIFICALLY THAT THE TWO COMPONENTS | | | FUNCTIONING TOGETHER WILL MEET OR EXCEED THE EFFIENCIES | | | REQUIRED BYTABLE C403.2.3(1). | | | | | | ADDITIONALLY, PLEASE NOTE THAT THE LETTER FROM JIMMY | | | JEFFCOAT PE REQUIRES AN ORIGNIAL SIGNATURE AND SEAL PER | | | SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2017-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2017-03-24 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2017-03-24 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2017-03-24 12:06:07 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100663 | | | 3/24/17 | | | | | | 1) THE REQUESTED DOCUMENTATION OF AHRI CERTIFICATION | | | FOR THE REPLACED AC SYSTEMS HAS NOT BEEN PROVIDED. | | | PLEASE SEE EXCEPTION #2 PRINTED BELOW | | | | | | SECTION C101.4.7 FBC-14 ENERGY CONSERVATION: BUILDING | | | SYSTEMS AND COMPONENTS. | | | THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING | | | BUILDING SYSTEMS AND COMPONENTS WHERE NEW PRODUCTS ARE | | | INSTALLED OR REPLACED IN EXISTING BUILDINGS, AND FOR | | | WHICH A PERMIT MUST BE OBTAINED. NEW PRODUCTS SHALL | | | MEET THE MINIMUM EFFICIENCIES ALLOWED BY THIS CODE FOR | | | THE FOLLOWING SYSTEMS AND COMPONENTS: | | | | | | HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS. | | | | | | SERVICE WATER OR POOL HEATING SYSTEMS. | | | | | | ELECTRICAL SYSTEMS AND MOTORS. | | | | | | LIGHTING SYSTEMS. | | | | | | REPLACEMENT FENESTRATION. | | | | | | EXCEPTIONS: | | | | | | 1. WHERE PART OF A FUNCTIONAL UNIT IS REPAIRED OR | | | REPLACED. FOR EXAMPLE, REPLACEMENT OF AN ENTIRE HVAC | | | SYSTEM IS NOT REQUIRED BECAUSE A NEW COMPRESSOR OR | | | OTHER PART DOES NOT MEET CODE WHEN INSTALLED WITH AN | | | OLDER SYSTEM. | | | | | | 2. IF THE UNIT BEING REPLACED IS ITSELF A FUNCTIONAL | | | UNIT, SUCH AS A CONDENSER, IT DOES NOT CONSTITUTE A | | | REPAIR. OUTDOOR AND INDOOR UNITS THAT ARE NOT DESIGNED | | | TO BE OPERATED TOGETHER MUST MEET THE U.S. DEPARTMENT | | | OF ENERGY CERTIFICATION REQUIREMENTS CONTAINED IN | | | SECTION C403.2.3. MATCHED SYSTEMS ARE REQUIRED; THIS | | | MATCH MAY BE VERIFIED BY ANY ONE OF THE FOLLOWING | | | MEANS: | | | | | | A. AHRI DATA. | | | | | | B. ACCREDITED LABORATORY. | | | | | | C. MANUFACTURER'S LETTER. | | | | | | D. LETTER FROM REGISTERED PROFESSIONAL ENGINEER (P.E.), | | | STATE OF FLORIDA. | | | | | | 3. WHERE EXISTING COMPONENTS ARE UTILIZED WITH A | | | REPLACEMENT SYSTEM, SUCH AS AIR DISTRIBUTION SYSTEM | | | DUCTS OR ELECTRICAL WIRING FOR LIGHTS, SUCH COMPONENTS | | | OR CONTROLS NEED NOT MEET CODE IF MEETING CODE WOULD | | | REQUIRE THAT COMPONENT?S REPLACEMENT. | | | | | | 4. REPLACEMENT EQUIPMENT THAT WOULD REQUIRE EXTENSIVE | | | REVISIONS TO OTHER SYSTEMS, EQUIPMENT OR ELEMENTS OF A | | | BUILDING WHERE SUCH REPLACEMENT IS A LIKE-FOR-LIKE | | | REPLACEMENT, SUCH AS THROUGH-THE-WALL CONDENSING UNITS | | | AND PTACS, CHILLERS, AND COOLING TOWERS IN CONFINED | | | SPACES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-12-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-12-13 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-12-13 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2016-12-13 17:20:17 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100663 | | | 12/13/16 | | | | | | 1) PROVIDE AHRI CERTIFCATION FOR THE REPLACED SYSTEMS- | | | SECTION C101.4.7 FBC-14 ENERGY CONSERVATION. | | | | | | 2) IN REFERENCE TO COMMENT #6 FROM THE 1ST REVIEW, | | | VERIFY THE SCREEN WALLS, WHICH ARE ALSO CONSIDERED | | | GUARDS, HAVE ADEQUATE STRENGTH AND ATTACHMENT PER | | | SECTION 1607.8 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-11-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-11-01 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-11-01 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2016-11-01 11:01:18 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16100663 | | | 11/1/16 | | | | | | 1) DESIGN CRITERIA: PROVIDE ON THE PLAN A LIST OF | | | CURRENT CODE REFERENCES AND STANDARDS USED IN THE | | | DESIGN OF THE PROJECT. | | | | | | 2) THE MECHANICAL PLANS MUST BE DESIGNED BY A FLORIDA | | | LICENSED ENGINEER PER FLORIDA STATUTE 471.003. THE SEAL | | | ON THE PLANS INDICATES THE DESIGNER HAS A "CERTIFICATE" | | | BUT IS NOT LICENSED. | | | | | | 3) REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION- | | | AC SYSTEM COMMISSIONING IS REQUIRED. | | | C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION | | | REQUIREMENTS. | | | PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE | | | REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE | | | OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN | | | ACCORDANCE THE PROVISIONS OF THIS SECTION. | | | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE | | | PROVISIONS FOR COMMISSIONING AND COMPLETION | | | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE | | | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER | | | REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE | | | GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE | | | OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS | | | C408.2.4 AND C408.2.5. | | | | | | 2A) C408.2.1 COMMISSIONING PLAN. | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED | | | DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL | | | INCLUDE THE FOLLOWING ITEMS: | | | | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED | | | TO CALIBRATIONS AND ECONOMIZER CONTROLS. | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER | | | DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE. | | | | | | 4) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR | | | INSTALLATION OF THE ROOF TOP AC EQUIPMENT PER SECTION | | | 301.15 FBC-14 MECHANICAL. PROVIDE ON THE PLAN THE WIND | | | LOAD DESIGN CRITERIA AND COMPLETE DETAILS FOR ANCHORING | | | THE ACCU'S AND OSA FAN TO THE ROOF STRUCTURE. | | | | | | 5) REFER TO SECTION 102.8 FBC-14 BUILDING: ALL NEW AND | | | REPLACED MECHANICAL EQUIPMENT MUST BE RAISED ABOVE THE | | | ROOF SURFACE AT THE CLEARANCE HEIGHTS SPECIFIED IN | | | TABLE 1522.3. PROVIDE DETAILS ON THE PLAN TO INDICATE | | | COMPLIANCE. | | | | | | 6) REFER TO SECTION 702.4 FBC-14 EXISTING BUILDING AND | | | VERIFY THAT ALL MECHANICAL ROOFTOP EQUIPMENT IS NOT | | | LOCATED WITHIN 10' OF ANY ROOF EDGE THAT DOES NOT HAVE | | | A GUARD OR PARAPET AT A MINIMUM HEIGHT OF 42"- SEE | | | SECTION 304.11 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-15 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-15 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2016-12-15 07:29:28 | ALTHOUGH A SMALL PORTION OF THE PARCEL IS LOCATED IN | | | THE SFHA, THIS STRUCTURE IS LOCATED OUTSIDE OF THE SFHA | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-10-31 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-10-31 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2016-10-31 09:44:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THIS | | | STRUCTURE, FBC 1612. IF AVAILABLE, PROVIDE A SURVEY FOR | | | THIS PROPERTY. | | | | | | THIS MAY BE SENT VIA EMAIL PRIOR TO RESUBMITTING. | | | | | | A COMPLETE REVIEW CANNOT BE DONE WITHOUT THIS | | | INFORMATION. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2017-03-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-03-29 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-03-29 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2017-01-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2017-01-12 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2017-01-12 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2016-11-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-11-23 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-11-23 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2016-11-23 13:41:02 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE DETAIL FOR ROOF DRAIN IT IS UNCLEAR WHAT IS | | | BEING REPLACED AND WHAT IS TO REMAIN. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 2. PROVIDE NOTE ON PLAN EXISTING 1" BACKFLOW TO BE | | | RECERTIFIED BY LIC. CONTRACTOR. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. ADDRESS COMMENTS FROM BUILDING AND MECHANICAL. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-12-15 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-12-15 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2016-12-15 07:40:01 | A SEPARATE PERMIT IS REQUIRED FOR THE ROOF COVERING. AN | | | APPLICATION, PRODUCT APPROVALS REVIEWED BY DESIGNER OF | | | RECORD, PROPOSED ASSEMBLY & FASTENING METHOD INDICATED, | | | AND ENGINEERING (IF APPLICABLE) IS REQUIRED TO BE | | | SUBMITTED PRIOR TO ROOF COVERING INSTALLATION. | | | | | | PLANS SPECIFY PVC INSULATED AND STANDING SEAM METAL | | | ROOFS | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2017-01-19 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2017-01-19 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-11-17 |
|
|
Cont ID |
|
| Sent By |
JR |
Date |
2016-11-17 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-11-17 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2016-11-17 11:27:19 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 11.17.2016 | | | PERMIT NO.: 16100663 | | | ADDRESS: 1111 S. FLAGLER DRIVE | | | CONTRACTOR/CONTACT: MIKE EVANS | | | TELEPHONE NO.: 205.313.3027 | | | SCOPE OF REVIEW: ROOFTOP HVAC, ROOFING DEMOLITION AND | | | REPLACEMENT | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PLEASE PROVIDE A CROSS-SECTION OR SIMILAR DRAWING | | | SHOWING THAT WITH THE DEMOLITION OF THE PARAPET THAT | | | THE ROOF-MOUNTED HVAC EQUIPMENT WILL NOT BE VISIBLE | | | FROM ADJACENT PROPERTY OR THE PUBLIC RIGHT-OF-WAY. | | | | | | 2. PLEASE EXPLAIN THE BASIS FOR REMOVING THE DECORATIVE | | | PARAPET FROM THE ENTIRE STRUCTURE. STAFF IS CONCERNED | | | AND DOES NOT SUPPORT REMOVAL OF THIS ELEMENT. IT IS ONE | | | OF THE PRIMARY ARCHITECTURAL ELEMENTS THAT EXISTS ON | | | THIS BUILDING. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|