Plan Review Details - Permit 16100655
Plan Review Stops For Permit 16100655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-02 Cont ID  
Sent By shill Date 2016-12-02 Time 07:41 Rev Time 0.00
Received By shill Date 2016-12-02 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By shill Date 2016-10-31 Time 08:00 Rev Time 0.00
Received By shill Date 2016-10-31 Time 07:17 Sent To  
Notes
2016-10-31 08:00:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. GRAB BAR IS TO BE MEASURED TO THE TOP OF THE BAR,
 FBC 5TH EDITION ACCESSIBILITY 609.4, REVISE DETAILS.
  
 2. FBC 1011.1, EXIT SIGNS TO BE READILY VISIBLE. REVISE
 PLAN TO ADD AN EXIT SIGN AT THE HALLWAY AT THE REAR OF
 THE UNIT (CLOSET/ RESTROOM WALL). NOTE THAT THIS ITEM
 WAS REDLINED BY FIRE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By vperez Date 2016-12-08 Time 09:41 Rev Time 0.00
Received By vperez Date 2016-12-08 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-07 Cont ID  
Sent By vperez Date 2016-11-07 Time 09:11 Rev Time 0.00
Received By vperez Date 2016-11-07 Time 09:11 Sent To  
Notes
2016-11-07 09:15:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A SHOW WINDOW RECEPTACLE AND SHOW LOAD ON
 PANEL SCHEDULE. NEC 21-.62
 2. PROVIDE A NOTE TO INDICATE ALL 125V RECEPTACLES
 WITHIN 6FT OF SINKS TO BE GFCI PROTECTED, A NOTE WILL
 SUFFICENEC 210.8B
 3. ADDRESS MECHANICAL AND FIRE COMMENTS RELATED TO
 ELECTRICAL.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-25 Cont ID  
Sent By pleduc Date 2016-10-25 Time   Rev Time 0.00
Received By pleduc Date 2016-10-25 Time 14:57 Sent To  
Notes
2016-10-25 15:13:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEETS A3 & I2.1 - PROVIDE AN EXIT SIGN/LIGHT AT THE
 REAR OF THE MAIN FLOOR AREA LEADING INTO BACK RESTROOM
 AND REAR EXIT DOOR AREA.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-22 Cont ID  
Sent By ccole Date 2016-12-22 Time 09:09 Rev Time 0.00
Received By ccole Date 2016-12-19 Time 14:40 Sent To  
Notes
2016-12-20 14:40:14RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By vperez Date 2016-12-08 Time 09:41 Rev Time 0.00
Received By vperez Date 2016-12-08 Time 09:41 Sent To  
Notes
2016-11-28 13:31:39B24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-15 Cont ID  
Sent By gjohnson Date 2016-11-15 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2016-10-21 Time 15:45 Sent To  
Notes
2016-10-24 15:45:42B02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-22 Cont ID  
Sent By ccole Date 2016-12-22 Time 09:27 Rev Time 0.00
Received By ccole Date 2016-12-22 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-05 Cont ID  
Sent By ccole Date 2016-12-05 Time 08:10 Rev Time 0.00
Received By ccole Date 2016-12-05 Time 07:59 Sent To  
Notes
2016-12-05 08:18:362ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100655
 12/5/16
  
 1) AS PREVIOUSLY REQUESTED, REVISE THE VENTILATION
 CALCULATIONS TO INCLUDE THE REQUIRED EXHAUST. PLEASE
 ALSO PROVIDE AN AIR BALANCE CALCULATION.
  
 2) INDICATE THE REQUIRED CLEARANCE DISTANCES FOR THE
 O/A INTAKE AND EXHAUST OUTLET- SEE SECTIONS 401.4 AND
 501.3.1.
  
 3) PROVIDE OPENING PROTECTION FOR THE O/A INTAKE PER
 SECTION 401.5.
  
 4) SUBMIT THE PRODUCT APPROVAL OR NOA FOR THE ROOF
 STAND PER RULE 9N-3 FLORIDA DEPT. OF COMMUNITY AFFAIRS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-31 Cont ID  
Sent By ccole Date 2016-10-31 Time 08:57 Rev Time 0.00
Received By ccole Date 2016-10-31 Time 08:57 Sent To  
Notes
2016-10-31 09:08:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100665
 10/31/16
  
 1) BARBER SHOPS ARE REQUIRED TO HAVE AN EXHAUST SYSTEM
 WITH A DESIGN CAPACITY OF 0.5 CFM PER SF. - REFER TO
 TABLE 403.3. PLEASE REVISE THE PLAN AND THE VENTILATION
 CALCULATIONS.
  
 2) PLEASE CLARIFY WHY AN EXHAUST FAN IS BEING INSTALLED
 IN THE EMPLOYEE LOUNGE AND PROVIDE A SIZING
 CALCULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-15 Cont ID  
Sent By gjohnson Date 2016-11-15 Time 15:23 Rev Time 0.00
Received By gjohnson Date 2016-11-15 Time 11:22 Sent To  
Notes
***NONE***