Plan Review Details - Permit 16100625
Plan Review Stops For Permit 16100625
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-23 Cont ID  
Sent By cthroop Date 2017-01-23 Time 12:39 Rev Time 0.00
Received By cthroop Date 2017-01-23 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-03 Cont ID  
Sent By cthroop Date 2017-01-03 Time 09:08 Rev Time 0.00
Received By cthroop Date 2017-01-03 Time 09:08 Sent To  
Notes
2017-01-03 09:10:47BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLANS TO BE SIGNED AND SEALED PER FS 481.
 2. COMPLY WITH ZONING COMMENTS ANDF RE-SUBMIT.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-11-14 Cont ID  
Sent By cthroop Date 2016-11-14 Time 12:53 Rev Time 0.00
Received By cthroop Date 2016-11-14 Time 12:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-23 Cont ID  
Sent By vperez Date 2017-01-23 Time 07:27 Rev Time 0.00
Received By vperez Date 2017-01-23 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-27 Cont ID  
Sent By cthroop Date 2017-01-03 Time 09:08 Rev Time 0.00
Received By vperez Date 2016-12-27 Time 08:36 Sent To Z
Notes
2016-12-27 08:37:20PLANS APPROVED PENDING EOR SIGNATURE ON PLANS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-12 Cont ID  
Sent By vperez Date 2016-11-12 Time 14:52 Rev Time 0.00
Received By vperez Date 2016-11-12 Time 14:52 Sent To B
Notes
2016-11-12 14:53:17INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE AND REFLECT ON ELECTRICAL DRAWINGS
 THE ELECTRICAL DATA INFORMATION, EXAMPLE VOLTAGE, TOTAL
 AMPS, CIRCUITS POWER SUPPLY INFORMATION ETC. FBC
 107.3.5- MINIMUM PLAN REVIEW CRITERIA
 2. ADD GENERAL NOTES TO INDICATE THAT ALL MATERIALS AND
 FASTENERS MEET 3004.4
 3. ALL ELECTRICAL COMPONENTS ARE UL LISTED AND APPROVED
 (GENERAL NOTE)
 4. SIGN TO BE GROUNDED ACCORDING TO NEC 600.7 (GENERAL
 NOTE)
 5. SIGN TO BE MANUFACTURED AND LISTED NEC 600.3 AND
 MARKED PER NEC 600.4(GENERAL NOTE)
 6. ALL BRANCH CIRCUITS PER NEC 600.5(B)1 AND B2(GENERAL
 NOTE)
 7. SIGN TO BE CONTROLLED BY PHOTOCELL OR TIME CLOCK PER
 FBC 2014 ENERGY CONSERVATION C405.2.4(GENERAL NOTE)
 8. VISIBLE 20AMP DISCONNECT PER SIGN PER CIRCUIT NEC
 600.6 A1 AND 2. (GENERAL NOTE)
 9. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-23 Cont ID  
Sent By cthroop Date 2017-01-23 Time 12:39 Rev Time 0.00
Received By cthroop Date 2017-01-13 Time 14:06 Sent To  
Notes
2017-01-17 14:06:31RESUB ROUTED TO ESCHNEIDER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-03 Cont ID  
Sent By cthroop Date 2017-01-03 Time 09:08 Rev Time 0.00
Received By cthroop Date 2016-12-22 Time 05:40 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-14 Cont ID  
Sent By cthroop Date 2016-11-14 Time 12:53 Rev Time 0.00
Received By cthroop Date 2016-10-21 Time 15:57 Sent To  
Notes
2016-10-21 15:57:48ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-01-20 Cont ID  
Sent By eschneid Date 2017-01-20 Time 17:00 Rev Time 0.25
Received By eschneid Date 2017-01-20 Time 17:00 Sent To E
Notes
2017-01-17 15:13:19ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 2 Status F Date 2016-12-30 Cont ID  
Sent By eschneid Date 2016-12-30 Time 16:40 Rev Time 0.25
Received By eschneid Date 2016-12-30 Time 16:40 Sent To B
Notes
2016-12-30 16:40:11FAILED
  
 1) REPEAT COMMENT: THE CITYPLACE MANAGEMENT APPROVAL
 STAMP IS REQUIRED ON THE PLANS.
  
 2) REVISED COMMENT: THE CITYPLACE MASTER SIGN PLAN
 LIMITS THE SIZE OF THE PEDESTRIAN BLADE SIGN PANEL TO
 FOUR (4) SQUARE FEET. THE DIMENSIONS SHOWN ON PAGE 1
 SHOW A ONE (1) SQUARE FOOT SIGN PANEL (12 INCHES X 12
 INCHES). THE DIMENSIONS SHOWN ON PAGE 4 SHOW THE
 ORIGINAL 4.79 SQUARE FOOT SIGN PANEL (30 INCH X 23
 INCH) WHICH EXCEEDS THE PERMITTED SIGN SIZE.
  
 3) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT PEDESTRIAN BLADE SIGNS (INCLUDING
 MOUNTING FRAMES) PROVIDE A MINIMUM OF 8 FEET OF
 CLEARANCE. PROVIDE THE PEDESTRIAN BLADE SIGN CLEARANCE
 ON THE ELEVATION DRAWING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2016-12-28 15:31:54ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By eschneid Date 2016-11-10 Time 16:57 Rev Time 0.25
Received By eschneid Date 2016-11-10 Time 16:57 Sent To E
Notes
2016-11-10 16:58:36FAILED
  
 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE PLANS.
  
 2) PROVIDE TWO COPIES OF A BUILDING ELEVATION DRAWING
 WHICH SHOW WHERE THE SIGN WILL BE LOCATED. THE
 CITYPLACE MASTER SIGN PLAN ALLOWS EACH STORE TO INSTALL
 ONE (1), TWO-SIDED PEDESTRIAN BLADE SIGN FOR EACH STORE
 ENTRANCE, PLUS ONE (1) ADDITIONAL PEDESTRIAN BLADE SIGN
 PROVIDED, THE STOREFRONT HAS A MINIMUM OF SEVENTY FIVE
 (75) FEET OF FRONTAGE. THIS ADDITIONAL PEDESTRIAN BLADE
 SIGN SHALL PROVIDE A MINIMUM OF THIRTY (30) FEET OF
 SEPARATION FROM THE OTHER PEDESTRIAN BLADES SIGNS FOR
 THAT SAME STOREFRONT.
  
 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 PEDESTRIAN BLADE SIGNS SHALL NOT BE WITHIN SIX INCHES
 OF A NEUTRAL PIER.
  
 4) THE CITYPLACE MASTER SIGN PLAN LIMITS THE SIZE OF
 THE PEDESTRIAN BLADE SIGN PANEL TO FOUR (4) SQUARE
 FEET. THE SUBMITTED PEDESTRIAN BLADE SIGN PANEL IS 4.79
 SQUARE FEET.
  
 5) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT
 PEDESTRIAN BLADE SIGNS (INCLUDING MOUNTING FRAMES)
 PROVIDE A MINIMUM OF 8 FEET OF CLEARANCE. PROVIDE THE
 PEDESTRIAN BLADE SIGN CLEARANCE ON THE ELEVATION
 DRAWING.
  
 6) PROVIDE HOW THE POWER IS BEING PROVIDED TO THE LED
 LIGHTS WITHIN THE SIGN.
  
 A COPY OF THESE COMMENTS HAS BEEN SENT TO CARLOS BERNAL
 AT CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2016-10-27 11:24:56ROUTED TO ERIC SCHNEIDER