Plan Review Details - Permit 16100614
Plan Review Stops For Permit 16100614
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2016-12-08 Time 14:30 Sent To  
Notes
2016-12-08 14:49:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16100614
 ADD: 7160 OKEECHOBEE BLVD. BLDG. # 2/ BLDG. TYPE: II
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. DEC. 089/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING# 2. BUILDING TYPE II,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) 2ND REQUEST. THE BUILDING OFFICIAL HAS APPROVED THE
 COST ANALYSIS AND REVIEWING THE DOCUMENTS. THE 4
 SUB-PERMITS THAT ARE A NO COST IF THEY CAME IN AT THE
 TIME OF THE PRIME PERMIT ARE MECHANICAL, ELECTRICAL,
 PLUMBING & ROOFING. IF THEY COME IN AFTER THE PRIME
 PERMIT WAS CREATED THEY ARE A $80.00 SUB-PERMIT, THE
 $80.00 IS AN ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $280,000.00 STATED UNDER BLDG. 2/
 TYPE II. NOTE, THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. AN ITEMIZED LIST OF SUB-PERMITS
 NOT COVERED UNDER THE MASTER AND THE COST OF WORK
 ASSOCIATED WITH THEM NEEDS TO BE SUBMITTED TO THE CITY
 FOR REVIEW SO WE CAN REDUCE THE OVERALL BUILDING VALUE
 SO WE DO NOT CHARGE YOU TWICE FOR ASSOCIATED PERMIT
 FEES. PROVIDE AN ITEMIZED LIST.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) AMENDMENT FOR THRESHOLD AGEEMENT FILED IN COMMUNITY
 PLUS NOTES. 12/09/2016. JW
  
 3A) IN THIS SUBMITTAL THE PLANS INDICATE THERE IS TO BE
 AN R-13 FIRE SPRINKLER SYSTEM. THERE IS NO HYDRAULIC
 CALCULATIONS SUBMITTED NOR PLANS FOR FIRE SPRINKLER
 LAYOUT PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 2014 FBC-B 903.2.11.3 BUILDINGS THREE STORIES OR MORE
 IN HEIGHT.
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1.
  
  
 3B) NO ACTION REQUIRED. ORIGINAL PAPER SIGNED AND
 SEALED SOILS REPORT FOR THE PROJECT IS FILED WITH THE
 RECREATION BUILDING PERMIT # 16020377.
  
 4) 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
  
 5A-5E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
  
 5B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 5E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 5F) COMPLIED. A/C STANDS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTAL:
  
 6A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 6C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & E5.01
 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By jwitmer Date 2016-11-09 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2016-11-09 Time 14:22 Sent To  
Notes
2016-11-09 14:23:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16100614
 ADD: 7160 OKEECHOBEE BLVD. BLDG. # 2/ BLDG. TYPE: II
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. NOV. 09/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING# 2. BUILDING TYPE II,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) THE BUILDING OFFICIAL HAS APPROVED THE COST ANALYSIS
 AND REVIEWING THE DOCUMENTS. THE 4 SUB-PERMITS THAT ARE
 A NO COST IF THEY CAME IN AT THE TIME OF THE PRIME
 PERMIT ARE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING.
 IF THEY COME IN AFTER THE PRIME PERMIT WAS CREATED THEY
 ARE A $80.00 SUB-PERMIT, THE $80.00 IS AN
 ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $280,000.00 STATED UNDER BLDG. 2/
 TYPE II. NOTE, THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. AN ITEMIZED LIST OF SUB-PERMITS
 NOT COVERED UNDER THE MASTER AND THE COST OF WORK
 ASSOCIATED WITH THEM NEEDS TO BE SUBMITTED TO THE CITY
 FOR REVIEW SO WE CAN REDUCE THE OVERALL BUILDING VALUE
 SO WE DO NOT CHARGE YOU TWICE FOR ASSOCIATED PERMIT
 FEES. PROVIDE AN ITEMIZED LIST.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) THIS BUILDING IS A THRESHOLD BUILDING AND ADDENDUM
 TO THE THRESHOLD DOCUMENTS NEEDS TO OCCUR PROVIDING THE
 BUILDING ADDRESS AND PERMIT NUMBERS IF APPLICABLE FROM
 THE THRESHOLD INSPECTION COMPANY ACKNOWLEDGING THE
 ENLARGED SCOPE OF WORK. IF THERE IS ANY CHANGE IN THE
 ONSITE INSPECTORS OR ADDITIONAL INSPECTORS THEIR
 SIGNATURES ON THE APPROPRIATE FORMS WILL ALSO BE
 REQUIRED. WE WOULD ALSO NEED CURRENT LICENSURE FOR THE
 NEW JOBSITE INSPECTOR AND RESUME TO BE REVIEWED AND
 APPROVED BY THE CITY. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING?.
  
  
 3A) IN THIS SUBMITTAL THE PLANS INDICATE THERE IS TO BE
 AN R-13 FIRE SPRINKLER SYSTEM. THERE IS NO HYDRAULIC
 CALCULATIONS SUBMITTED NOR PLANS FOR FIRE SPRINKLER
 LAYOUT PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 2014 FBC-B 903.2.11.3 BUILDINGS THREE STORIES OR MORE
 IN HEIGHT.
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1.
  
  
 3B) NO ACTION REQUIRED. ORIGINAL PAPER SIGNED AND
 SEALED SOILS REPORT FOR THE PROJECT IS FILED WITH THE
 RECREATION BUILDING PERMIT # 16020377.
  
 4) 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
  
 5A-5E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
  
 5B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 5E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 5F) COMPLIED. A/C STANDS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTAL:
  
 6A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 6C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & E5.01
 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By vperez Date 2016-12-08 Time 11:09 Rev Time 0.00
Received By vperez Date 2016-12-08 Time 11:09 Sent To  
Notes
2016-12-08 11:10:27PROVISO- SEE FIRE REVIEW PROVISO APPLICABLE TO
 ELECTRICAL. PLEASE PROVIDE AS NOTED. FBC 107.3.5
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By vperez Date 2016-11-08 Time 13:46 Rev Time 0.00
Received By vperez Date 2016-11-08 Time 13:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-11-04 Cont ID  
Sent By mgonzale Date 2016-11-04 Time   Rev Time 1.00
Received By   Date 2016-11-04 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-12-05 Cont ID  
Sent By scaldero Date 2016-12-05 Time 11:29 Rev Time 0.00
Received By scaldero Date 2016-12-05 Time 11:26 Sent To  
Notes
2016-12-05 11:29:37PERMIT #16100614
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
 FAILURE TO COMPLY WITH THE PROVISO COMMENTS BELOW MAY
 RESULT IN A FAILED INSPECTION.
  
 1) ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. ****THESE DOCUMENTS ARE TO
 BE SUBMITTED AS A REVISION TO THE PLAN AS SOON AS
 POSSIBLE, SO THAT THEY MAY BE REVIEWED AND APPROVED,
 PRIOR TO THE SUB-CONTRACTOR OBTAINING A PERMIT. FAILURE
 TO DO SO MAY RESULT IN THE SUBCONTRACTOR'S PERMIT
 APPLICATION BEING DENIED.*****
  
 2) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL. *****THE
 ENGINEER OF RECORD SHALL SUBMIT A REVISION TO THIS
 PLAN, IN RESPONSE TO THIS COMMENT. THE RESPONSE MAY BE
 IN NARRATIVE FORM, BUT SHALL CLEARLY STATE HOW
 COMPLIANCE WITH THE ABOVE REFERENCED CAPABILITIES IS TO
 BE ACHIEVED. FAILURE TO DO SO WILL RESULT IN A FAILED
 INSPECTION.******
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By scaldero Date 2016-10-26 Time 10:31 Rev Time 0.00
Received By scaldero Date 2016-10-26 Time 10:26 Sent To  
Notes
2016-10-26 10:31:53PERMIT #16100614
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) THE ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS SUBMITTED DO NOT MATCH THE
 BUILDING DRAWINGS. SHOP DRAWINGS APPEAR TO BE OLDER AND
 DO NOT INCLUDE THE SAME DETAILS. PLEASE CORRECT AND
 RESUBMIT.
  
 2) ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES). THIS STANDARD SHALL
 COVER THE CONSTRUCTION AND PROTECTION OF, AS WELL AS
 THE CONTROL OF THE HAZARDS IN, OPEN AND ENCLOSED
 PARKING STRUCTURES.
  
 3) PER NFPA 88A, SECTION 5.3.2: ALL ENCLOSED PARKING
 STRUCTURES SHALL BE VENTILATED BY A MECHANICAL SYSTEM
 CAPABLE OF PROVIDING A MINIMUM OF 1FT3/MIN PER FT2 OF
 FLOOR AREA. MECHANICAL VENTILATING SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 90A. DUCTWORK SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIAL.
  
 4) PLEASE PROVIDE AND/OR EXPLAIN THE MEANS OF CARBON
 MONOXIDE PROTECTION TO UNITS ATTACHED TO AND ABOVE THE
 PARKING GARAGES, IN THE ENGINEERED DRAWINGS.
  
 5) THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 6) SMOKE ALARMS ARE REQUIRED IN EVERY SLEEPING ROOM AND
 OUTSIDE OF THE SLEEPING ROOMS AND IN ALL LEVELS OF THE
 DWELLING UNITS. THESE DETECTORS SHALL BE HARD WIRED AND
 SHALL BE INTERCONNECTED TO ONE ANOTHER.
  
 7) FIRE ALARM NOTIFICATION DEVICES DO NOT APPEAR TO BE
 PLACED IN THE LIVING ROOM/KITCHEN AREA. PLEASE REVIEW
 AND CORRECT AS NEEDED TO ENSURE COMPLIANCE WITH NFPA 72
 AND NFPA 101 REQUIREMENTS.
  
 8) BASED ON THE LOCATION OF THE NOTIFICATION DEVICES IN
 THE CORRIDORS, THE REQUIRED DECIBEL LEVELS IN THE
 GARAGE MAY NOT BE MET.
  
 9) ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 10) ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH
 OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM
 TERMINAL LANDING AND THE TOP TERMINAL LANDING EXCEEDS
 25 FEET MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL AND WILL
 ACCOMMODATE AN AMBULANCE STRETCHER 76 INCHES LONG AND
 24 INCHES WIDE IN THE HORIZONTAL POSITION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2016-12-09 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-18 Cont ID  
Sent By lmarchan Date 2016-11-18 Time 14:10 Rev Time 0.00
Received By lmarchan Date 2016-10-21 Time 08:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-12-22 Cont ID  
Sent By jwitmer Date 2016-12-22 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2016-12-22 Time 09:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 08:55 Sent To  
Notes
2016-12-12 09:27:40BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2016-12-08 Time 14:50 Sent To  
Notes
2016-12-08 14:50:56BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By ccole Date 2016-12-08 Time 11:19 Rev Time 0.00
Received By ccole Date 2016-12-08 Time 08:00 Sent To  
Notes
2016-12-08 11:24:35NO NOTES
2016-12-08 11:22:56 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 12:18 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 12:18 Sent To  
Notes
2016-11-02 12:20:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100614
 11/2/16
  
 1) SUBMIT ENERGY CALCULATIONS AND AC COOLING AND
 HEATING CALCULATIONS.
  
 2) SHEET M4.02: THE 10X9 TRANSFER DUCT AT BEDROOM 2
 (AHU-1 SYSTEM) IS UNDERSIZED PER SECTION 601.5
 EXCEPTION 1.
  
 3) SHEET M501: MECHANICAL VENTILATION RATES CANNOT BE
 USED TO VERIFY COMPLIANCE WITH THE NATURAL VENTILATION
 REQUIREMENT FOR THE GARAGES. PLEASE REVIEW SECTIONS
 401.2 AND 402.2 AND PROVIDE THE CORRECT CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By tklarge Date 2016-12-08 Time 02:57 Rev Time 0.00
Received By tklarge Date 2016-12-08 Time 01:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-18 Cont ID  
Sent By tklarge Date 2016-11-18 Time 14:08 Rev Time 0.00
Received By tklarge Date 2016-11-18 Time 05:33 Sent To  
Notes
2016-11-18 05:55:511) SHT.A0.02 - THERE IS A CLOUDED NOTE THAT REFERS TO
 WOOD BLOCKING FOR FUTURE GRAB BARS IN FIRST FLOOR UNITS
 ONLY. REVISE NOTE TO INCLUDE ALL FLOORS PER THE FHA.
 2) SHEET A2.01 - REMOVE THE SHADING FROM THE FLOOR
 PLAN. THE CLEAR FLOOR SPACE AT THE PLUMBING FIXTURES IS
 DIFFICULT TO SEE. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A2.02 - REMOVE THE SHADING FROM THE ROOF PLAN.
 THE ROOF DRAINS AND NOTES ARE EXTREMELY DIFFICULT TO
 SEE AND READ. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A8.03 - DETAIL #12 - COMBUSTIBLES ARE NOT
 PERMITTED IN THE A/C CLOSET SINCE IT IS A RETURN AIR
 PLENUM. MATERIALS WITHIN A PLENUM SHALL COMPLY WITH THE
 FLORIDA MECHANICAL CODE SEC.602.2.1. THE CPVC PIPNG
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND
 THE SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 SPECIFICATIONS FOR THE CPVC PIPE SHALL BE ON THE
 JOBSITE FOR FIELD INSPECTOR REVIEW AND APPROVAL.
 5) SHT. P2.01 - THE HUB DRAIN AND FLOOR DRAIN IN THE
 TRASH ROOM AND IN THE DOMESTIC PUMP ROOM SHALL BE
 EQUIPPED WITH TRAP PRIMERS. 2014 FPC SEC.1002.4.
 6) SHT. P5.01 - THE WATER FOR THE JANITOR SINKS ON THE
 SECOND AND THIRD FLOORS HAS BEEN DELETED FROM THE RISER
 BUT THE SANITARY RISER STILL SHOWS THE DRAINS. CLARIFY.
 7) SHT. A2.01 - UNIT A.1R - THE DOOR IN THE MASTER BATH
 SWINGS INTO THE REQUIRED CLEAR FLOOR SPACE FOR THE
 FIXTURES PER THE FHA GUIDELINES. A 30 INCH BY 48 INCH
 MINIMUM CLEAR FLOOR SPACE SHALL BE PROVIDED OUSIDE THE
 SWING OF THE DOOR.THIS HAS BEEN CORRECTED ON SHT.A4.01
 BUT NOT ON A2.01.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By jwitmer Date 2016-12-12 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-12-08 Cont ID  
Sent By jwitmer Date 2016-12-08 Time 14:51 Rev Time 0.00
Received By jwitmer Date 2016-12-08 Time 14:51 Sent To  
Notes
2016-11-09 14:25:23ARCHITECTURAL & STRUCTURAL SHEETS REVIEWED FOR
 SIGNATURE, STRUCTURAL SHEETS MISSING SIGNATURE ON S3 &
 S5. 11/09/2016, JW
  
 2ND REQUEST STRUCTURAL SHEETS MISSING SIGNATURE ON S3 &
 S5. 12/08/2016, JW
  
2016-10-27 15:14:05HARD COPIES OF SITE SURVEY/GEO TECHNICAL REPORT/AMENDED
 THRESHOLD PLAN IN LIBRARY CP

Review Stop Z ZONING
Rev No 1 Status P Date 2016-11-08 Cont ID  
Sent By ajones Date 2016-11-08 Time 08:56 Rev Time 0.00
Received By ajones Date 2016-11-08 Time 08:56 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved