Plan Review Details - Permit 16100600
Plan Review Stops For Permit 16100600
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2017-02-01 Time 11:20 Sent To  
Notes
2017-02-01 13:46:57NO REVISION FOUND, FOR REFERENCE ONLY, NO SIGNATURE
 REQUIRED. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-29 Cont ID  
Sent By jwitmer Date 2016-12-29 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2016-12-29 Time 13:21 Sent To  
Notes
2016-12-29 15:29:26BUILDING PLAN REVIEW
 W. P. B. REVISION: 16100600
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: POOLE & KENT
 CONTACT: KURT PFEFFER, P. E.
 TEL:
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. DEC. 29/ 2016
 ACTION: DENIED
  
 1) THE SHEET 0385-A-ADF-07 IS NOT A SUBMITTAL BUT A
 REVISION. IN THE ORIGINAL PERMIT DOCUMENT SET OF PLANS
 V2 SHOWED A REVISION NUMBER (3) DATED 10/15. IN THE
 LATEST SET OF PLANS SUBMITTED, THERE IS A REVISION # 4.
 THE NEW VERSION # 2 DOES NOT AND ORIGINAL ARE
 IDENTICAL. IN BOTH CASES REVISION # 4 SHOWS AS EXISTING
 REVISION. THE FOR REFERENCE ONLY IS WHEN THERE ARE
 PLANS ALREADY ON FILE AND NO CHANGES HAVE BEEN MADE.
 THESE PLANS ARE A REVISION REQUIRING FEES AND THEY WILL
 ALSO NEED THE ENGINEER OF RECORD TO ELECTRONICALLY SIGN
 AND SEAL PLANS. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE SHEET BOILER-GAS HANDLING BUILDING, ROOF PLAN
 HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0386-A-ADF-08 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 3) THE SUBMITTED SHEET M1-M4 SLUDGE PUMPING BUILDING
 ROOF PLAN HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0387-A-ADF-09 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-11-04 Time 07:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-28 Cont ID  
Sent By lmarchan Date 2017-02-28 Time 13:42 Rev Time 0.00
Received By lmarchan Date 2017-01-27 Time 08:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 11:39 Rev Time 0.00
Received By gjohnson Date 2016-12-20 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-28 Cont ID  
Sent By cpuell Date 2016-11-28 Time 08:16 Rev Time 0.00
Received By cpuell Date 2016-10-25 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2017-02-27 Cont ID  
Sent By tklarge Date 2017-02-27 Time 13:00 Rev Time 0.00
Received By gjohnson Date 2017-02-27 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 11:37 Sent To  
Notes
2017-01-13 11:38:14GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 1) THE SHEET 0385-A-ADF-07 IS NOT A SUBMITTAL BUT A
 REVISION. IN THE ORIGINAL PERMIT DOCUMENT SET OF PLANS
 V2 SHOWED A REVISION NUMBER (3) DATED 10/15. IN THE
 LATEST SET OF PLANS SUBMITTED, THERE IS A REVISION # 4.
 THE NEW VERSION # 2 DOES NOT AND ORIGINAL ARE
 IDENTICAL. IN BOTH CASES REVISION # 4 SHOWS AS EXISTING
 REVISION. THE FOR REFERENCE ONLY IS WHEN THERE ARE
 PLANS ALREADY ON FILE AND NO CHANGES HAVE BEEN MADE.
 THESE PLANS ARE A REVISION REQUIRING FEES AND THEY WILL
 ALSO NEED THE ENGINEER OF RECORD TO ELECTRONICALLY SIGN
 AND SEAL PLANS. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE SHEET BOILER-GAS HANDLING BUILDING, ROOF PLAN
 HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0386-A-ADF-08 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 3) THE SUBMITTED SHEET M1-M4 SLUDGE PUMPING BUILDING
 ROOF PLAN HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0387-A-ADF-09 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-11-27 Cont ID  
Sent By tklarge Date 2016-11-27 Time 06:38 Rev Time 0.00
Received By tklarge Date 2016-11-27 Time 06:27 Sent To  
Notes
2016-11-27 06:28:17ROOF PLAN NOT ELECTRONICALLY SIGNED NOR SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2017-02-28 Cont ID  
Sent By lmarchan Date 2017-02-28 Time 13:42 Rev Time 0.00
Received By lmarchan Date 2017-02-28 Time 13:42 Sent To  
Notes
2017-02-28 13:42:19PER JWITMER'S COMMENTS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2017-01-13 Cont ID  
Sent By gjohnson Date 2017-01-13 Time 11:38 Rev Time 0.00
Received By gjohnson Date 2017-01-13 Time 11:38 Sent To  
Notes
2017-01-13 11:39:12ROOF PLAN NOT ELECTRONICALLY SIGNED NOR SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-11-04 Cont ID  
Sent By jwitmer Date 2016-11-04 Time 08:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2016-11-04 08:40:19ROOF PLAN NOT ELECTRONICALLY SIGNED NOR SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.