| Plan Review Stops For Permit 16100557 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-10-26 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-10-26 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-10-26 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2016-10-26 17:10:26 | REVISION 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PASSED WITH THE FOLLOWING PROVISO (RED-LINED ON | | | PLANS) | | | | | | 1] PLEASE REFER TO TABLE 310.15(B)(16) IN THE NEC FOR | | | ALLOWABLE AMPACITIES OF CONDUCTORS. ADJUST WIRE SIZE | | | FOR 100 AMP SUB PANEL ACCORDINGLY. |
|
|