Plan Review Details - Permit 16100550
| Plan Review Stops For Permit 16100550 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2017-03-13 |
|
|
Cont ID |
|
| Sent By |
rsklarew |
Date |
2017-03-10 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-10 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2017-03-13 15:33:09 | APPROVED BY T.LARGE |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2017-03-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-09 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-09 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2017-03-09 14:19:57 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE POOL | | | HEATERS. WPB AMEND. TO FBC SEC.107.2.1. | | | 2) GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82 PERCENT PER 2014 FBC-ENERGY, TABLE | | | C404.2, SEC.C404.7.1. | | | 3) ALL POOL HEATERS SHALL BE EQUIPPED WITH A READILY | | | ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE OF THE | | | HEATER TO ALLOW SHUTTING OFF THE HEATER WITHOUT | | | ADJUSTING THE THE THERMOSTAT SETTING.GAS - FIRED | | | HEATERS SHALL NOT BE EQUIPPED WITH CONSTANT BURNING | | | PILOT LIGHTS.2014 FBVC- ENERGY SEC.C404.7.1. | | | 4) THE GAS POOL HEATERS SHALL BE LISTED AND LABELED PER | | | THE 2014 FBC-FUEL GAS SEC. 301.3. | | | 5) THE MANUFACTURER'S INSTALLATION MANUAL FOR THE POOL | | | HEATERS SHALL BE ON THE JOBSITE FOR INSPECTION. 2014 | | | FBC - FUEL GAS SEC.305.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2017-01-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-01-10 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-01-10 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2017-01-10 14:26:08 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. . PROVIDE COMPLETE PLANS THAT REFLECT THE | | | ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC | | | SEC.107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2017-03-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2017-03-09 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2017-03-08 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2017-03-08 16:20:42 | RESUB ROUTED TO TKLARGE |
|
|
|