| 2016-11-02 06:53:43 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16100546 |
| | ADD: 5444 N. HAVERHILL RD. |
| | CONT: SAMMET POOLS INC. |
| | TEL: 954-232-1915 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 02/2016 |
| | ACTION: DENIED |
| | |
| | 1) UNDER THE VIEW FOLDER THIS REVIEW THE CONTRACTOR |
| | HASN?T SUBMITTED THE MANUFACTURERS SPECIFICATIONS FOR |
| | COMMERCIAL POOL HEATERS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.4. SWIMMING POOLS. |
| | |
| | 2) PLEASE SHOW COMPLIANCE FOR GAS FIRED HEATERS HAVING |
| | A THERMAL EFFICIENCY OF 82 % ENERGY CODE TABLE C404.2 |
| | AND SECTION C404.71 |
| | |
| | 3) PLEASE PROVIDE WHERE COMPLIANCE WITH SECTION |
| | C404.7.2 OF THE 2014 FBC-ENERGY CODE. TIME SWITCHES OR |
| | OTHER CONTROL METHOD THAT CAN AUTOMATICALLY TURN OFF |
| | AND ON HEATERS AND PUMPS ACCORDING TO A PRESET SCHEDULE |
| | SHALL BE INSTALLED ON ALL HEATERS AND PUMPS. HEATERS, |
| | PUMPS AND MOTORS THAT HAVE BUILT IN TIMERS SHALL BE |
| | DEEMED IN COMPLIANCE WITH THIS REQUIREMENT. |
| | |
| | 4) PLEASE PROVIDE WHERE COMPLIANCE WITH SECTION |
| | C404.7.3 OF THE 2014 FBC-ENERGY CODE. TIME SWITCHES. |
| | TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN |
| | AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS |
| | ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON |
| | ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT |
| | HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH |
| | THIS REQUIREMENT. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |