Plan Review Details - Permit 16100540
Plan Review Stops For Permit 16100540
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-15 Cont ID  
Sent By skennedy Date 2016-12-15 Time 11:35 Rev Time 0.00
Received By skennedy Date 2016-12-15 Time 11:35 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-08 Cont ID  
Sent By cthroop Date 2016-11-08 Time 10:28 Rev Time 0.00
Received By cthroop Date 2016-11-07 Time 10:46 Sent To E
Notes
2016-11-08 10:33:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. NEW PARTITION WALLS ON FLOOR PLAN TO BE 8 FT HIGH.
 PARTITION HEIGHT ON PARTITION DETAIL IS 10 FT HIGH.
 PLEASE CLARIFY.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
2016-10-26 11:39:411ST REVIEW: FBC 2014 5TH ED.
  
 YOUR APPLICATION IS DEEMED DEFICIENT BASED UPON THE
 BELOW. THE PLANS DO NOT MEET MINIMUM PLAN REVIEW
 CRITERIA TO DETERMINE THE LEVEL OR SCPOE OF PROPOSED
 WORK WHICH MAY INCLUDE ELECTRICAL AND HVAC REQIREMENTS
 AMONG OTHERS. .
  
  
 553.792?BUILDING PERMIT APPLICATION TO LOCAL
 GOVERNMENT.?
 (1)?WITHIN 10 DAYS OF AN APPLICANT SUBMITTING AN
 APPLICATION TO THE LOCAL GOVERNMENT, THE LOCAL
 GOVERNMENT SHALL ADVISE THE APPLICANT WHAT INFORMATION,
 IF ANY, IS NEEDED TO DEEM THE APPLICATION PROPERLY
 COMPLETED IN COMPLIANCE WITH THE FILING REQUIREMENTS
 PUBLISHED BY THE LOCAL GOVERNMENT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By skennedy Date 2016-12-15 Time 11:35 Rev Time 0.00
Received By skennedy Date 2016-12-15 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-11-09 Cont ID  
Sent By mvaldes Date 2016-11-09 Time 17:55 Rev Time 0.00
Received By mvaldes Date 2016-11-09 Time 17:54 Sent To M
Notes
2016-11-09 18:00:37REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLARIFY THE ELECTRICAL SCOPE OF WORK, IF THESE WALLS
 HAVE ELECTRICAL OUTLETS PLEASE SHOW LOCATION ON THE
 PLANS. FBC-107
  
 2] IF ANY ELECTRICAL WORK IS TO BE DONE AN ELECTRICAL
 SUB PERMIT WILL BE REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-12-20 Cont ID  
Sent By skennedy Date 2016-12-19 Time 16:20 Rev Time 0.00
Received By skennedy Date 2016-12-19 Time 16:19 Sent To  
Notes
2016-12-20 16:20:30REVIEW BY PLEDUC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-20 Cont ID  
Sent By skennedy Date 2016-12-20 Time 16:20 Rev Time 0.00
Received By skennedy Date 2016-11-02 Time 10:28 Sent To  
Notes
2016-11-15 19:17:00ROUTED TO FIRE DEPT. 11/15/2016 - JORGE V.
2016-11-03 13:34:41RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-26 Cont ID  
Sent By skennedy Date 2016-10-26 Time 11:33 Rev Time 0.00
Received By skennedy Date 2016-10-19 Time 14:09 Sent To  
Notes
2016-10-20 14:09:29BLDG<5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-12-15 Cont ID  
Sent By skennedy Date 2016-12-15 Time 11:35 Rev Time 0.00
Received By skennedy Date 2016-12-15 Time 11:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-15 Cont ID  
Sent By jvalido Date 2016-11-15 Time 19:01 Rev Time 0.00
Received By jvalido Date 2016-11-15 Time 18:49 Sent To FIRE
Notes
2016-11-15 19:01:36CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
 (2) PROVIDE LOCATION, SIZE AND CFM VALUES OF ALL SUPPLY
 GRILLS.
 (3) PROVIDE BALANCED RETURN AIR FROM ALL ROOMS.
 (4) PROVIDE EXHAUST IN ALL BATHROOMS.
 (5) NO COMBUSTABLES IN RETURN AIR PLENUMS OR CLOSETS.
  
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  