Plan Review Details - Permit 16100533
Plan Review Stops For Permit 16100533
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 06:39 Rev Time 0.00
Received By shill Date 2016-12-27 Time 06:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-03 Cont ID  
Sent By shill Date 2016-11-03 Time 09:16 Rev Time 0.00
Received By shill Date 2016-11-02 Time 12:56 Sent To Z
Notes
2016-11-03 09:27:06****CORRECTIONS****
 REVISED 11/22/16
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SOILS REPORT IS FOR A WALL. THE PLAN IS FOR
 SHEET PILES. HAVE SOILS ENGINEER EITHER REVISE THE
 REPORT OR PROVIDE A LETTER WITH RECOMMENDATIONS, FBC
 5TH EDITION RESIDENTIAL 401.4.
  
 2. THE SOILS REPORT IS A PHOTOCOPY. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS FS471.
  
 3. THE ENGINEER FOR THE PROJECT IS TO REVIEW THE SOILS
 REPORT. EVIDENCE THAT THIS HAS BEEN DONE IS TO BE
 PROVIDED BY EITHER A SIGNED AND SEALED LETTER, A SHOP
 DRAWING REVIEW STAMP ON THE SOILS REPORT, OR REVISE THE
 PLAN TO ADD A NOTE. IF THE PLAN IS REVISED, REMOVE ALL
 REFERENCES TO THE CHAIN LINK FENCE.
  
 4. SHEET PILE INSTALLATION REQUIRES MONITORING. THE
 RESIDENT INSPECTOR AGREEMENT AND POLICY HAS BEEN SENT
 VIA EMAIL. ALL PARTIES ARE TO SIGN THE RESIDENT
 INSPECTOR AGREEMENT. THE RESIDENT INSPECTOR IS TO BE
 APPROVED BY KEN CONRAD. PROVIDE THE INSPECTOR'S RESUME
 AS WELL AS THE CONTRACTOR'S RESUME SHOWING EXPERIENCE
 WITH SIMILAR PROJECTS, FBC 110.3.9.
  
 5. PROVIDE SPECS AND INSTALLATION INSTRUCTIONS FOR THE
 PILINGS, FBC 107. PLANS REFER TO THE INSTRUCTIONS BUT
 THEY WERE NOT PROVIDED.
  
 6. PROVIDE A SURVEY FOR THIS PROPERTY. SURVEY IS TO
 SHOW ALL EASEMENTS. IF THE PROPOSED IMPROVEMENT IS
 LOCATED IN A UTILITY EASEMENT, PROVIDE EASEMENT
 RELEASES FROM ALL EASEMENT HOLDERS.
  
 7. PROVIDE INFORMATION REGARDING HOW THE SEISMIC
 MONITORING WILL BE DONE. PROVIDE INFORMATION REGARDING
 THE DISTANCE OF THE SHEET PILE TO OTHER STRUCTURES,
 INCLUDING POOLS, ON THE ADJACENT EAST LOT. HOW MUCH
 SEISMIC EFFECT IS ANTICIPATED, AND HOW FAR FROM OTHER
 STRUCTURES IS RECOMMENDED TO AVOID DAMAGE? THE SITE
 PLAN SHOWS A POOL AND CONCRETE PADS ON THE SUBJECT
 PARCEL; ISN'T THERE A HOUSE ON THIS LOT? THE SITE PLAN
 DOES NOT PROVIDE INFORMATION REGARDING THE ADJACENT
 LOT; ISN'T THERE A HOUSE AND POOL ON THE ADJACENT LOT?
  
 8. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 NEW COMMENT:
  
 9. DUE TO THE PROXIMITY TO THE NEIGHBOR, THE NEIGHBOR
 WILL BE NOTIFIED IF A SHEET PILING PERMIT IS ISSUED.
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-11-03 Cont ID  
Sent By njwira Date 2016-11-03 Time 15:44 Rev Time 0.00
Received By njwira Date 2016-11-03 Time 14:37 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By njwira Date 2016-10-26 Time 16:17 Rev Time 0.00
Received By njwira Date 2016-10-26 Time 16:17 Sent To B
Notes
2016-10-26 16:17:3510/26/16- FAILED
  
 SF14-C3
  
 FAILED
 1. CHAINLINK IS NOT PERMITTED IN A HISTORIC DISTRICT
  
 PASSED
 1. 6FT. HIGH FENCE IS PERMITTED IN A RESIDENTIAL
 DISTRICT OUTSIDE THE FRONT SETBACK.
 2. NOT BUILT INTO A CORNER SIGHTLINE
 3. NOT BUILT INTO A UTILITY EASEMENT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-27 Cont ID  
Sent By shill Date 2016-12-27 Time 06:39 Rev Time 0.00
Received By shill Date 2016-12-15 Time 09:05 Sent To  
Notes
2016-12-16 09:05:57RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-04 Cont ID  
Sent By shill Date 2016-11-04 Time 15:26 Rev Time 0.00
Received By shill Date 2016-11-02 Time 12:33 Sent To  
Notes
2016-11-02 12:33:4811/3 TO ZONING BOX
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-02 Cont ID  
Sent By shill Date 2016-11-02 Time 12:33 Rev Time 0.00
Received By shill Date 2016-10-19 Time 13:57 Sent To  
Notes
2016-10-20 13:58:00ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2016-12-16 Cont ID  
Sent By njwira Date 2016-12-16 Time 11:54 Rev Time 0.00
Received By njwira Date 2016-12-16 Time 10:53 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-03 Cont ID  
Sent By njwira Date 2016-11-03 Time 15:43 Rev Time 0.00
Received By njwira Date 2016-11-03 Time 14:36 Sent To HIST
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By njwira Date 2016-10-26 Time 16:15 Rev Time 0.00
Received By njwira Date 2016-10-21 Time 15:30 Sent To HIST
Notes
2016-10-26 16:17:0410/26/16- FAILED
  
 SF14-C3
  
 FAILED
 1. CHAINLINK IS NOT PERMITTED IN A HISTORIC DISTRICT
  
 PASSED
 1. 6FT. HIGH FENCE IS PERMITTED IN A RESIDENTIAL
 DISTRICT OUTSIDE THE FRONT SETBACK.
 2. NOT BUILT INTO A CORNER SIGHTLINE
 3. NOT BUILT INTO A UTILITY EASEMENT.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  