| 2016-10-25 08:36:58 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 2200 INDIAN RD. |
| | DESCRIPTION: ELECTRICALLY WIRE MAU |
| | MASTER PERMIT: 16100513 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE CLARIFY IF THE PANEL IS A MAIN BREAKER PANEL |
| | OR A MAIN LUG ONLY. IF MAIN LUG ONLY INDICATE THE PANEL |
| | BUS RATING. |
| | 2. PROVIDE A RISER DIAGRAM WITH PROPER LOAD CALCS. |
| | 3. SHOW HOW THE NEW CONTROL PANEL WILL BE FED. |
| | 4. INDICATE HOW THE NEW CONTROL PANEL WILL BE |
| | SUPPORTED. |
| | 5. MARK ON THE PLANS THE CODE TO WHICH THE SYSTEM IS |
| | BEING DESIGNED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |