Plan Review Details - Permit 16100503
Plan Review Stops For Permit 16100503
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By pleduc Date 2016-10-24 Time   Rev Time  
Received By pleduc Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-23 Cont ID  
Sent By pleduc Date 2016-11-23 Time   Rev Time 0.00
Received By pleduc Date 2016-11-23 Time 12:03 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-25 Cont ID  
Sent By pleduc Date 2016-10-25 Time   Rev Time 0.00
Received By pleduc Date 2016-10-20 Time 16:17 Sent To PC
Notes
2016-10-24 15:18:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 6 OF 7 SHOWS S(SMOKE) N1L1S59; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT AS ! (HEAT).
  
  
 2) SHEET 5 OF 7 SHOWS S, N1L1S43; HOEVER, ON SHEET 6 OF
 7 IT COULD NOT BE LOCATED.
  
  
 3) SHEET 6 OF 7 SHOWS SCF 3-4, N1L1S70; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S69.
  
  
 4) SHEET 6 OF 7 SHOWS FCU 2-1, N1L1S43; HOWEVER, ON
 SHEET 4 OF 7 ITS SHOWS IT AS N1L1S39.
  
  
 5) SHEET 6 OF 7 SHOWS FCU 3-2, N1L1S66; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S68.
  
  
 6) SHEET 6 OF 7 SHOWS SCF 3-1, N1L1S72; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S71.
  
  
 7) SHEET 6 OF 7 SHOWS FCU 3-7, N1L1S73; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S72.
  
  
 8) SHEET 6 OF 7 SHOWS FCU 3-6, N1L1S77; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S73.
  
  
 9) SHEET 6 OF 7 SHOWS FCU 3-5, N1L1S75; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S74.
  
  
 10) SHEET 6 OF 7 SHOWS SCF 3-3, N1L1S77; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S75.
  
  
 11) SHEET 6 OF 7 SHOWS SCF 3-2, N1L1S79; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S77.
  
  
 12) SHEET 6 OF 7 SHOWS SCF 3-5, N1L1S76; HOWEVER, ON
 SHEET 5 OF 7 IT COULD NOT BE LOCATED.
  
  
 13) SHEET 6 OF 7 SHOWS AHU 3-1, N1L1S78; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S76.
  
  
 14) SHEET 6 OF 7 SHOWS S , N1L1S68; HOWEVER, ON SHEET 5
 OF 7 IT COULD NOT BE LOCATED.
  
  
 15) SHEET 6 OF 7 A "C" INSIDE A SQUARE BOX IS
 INDICATED; HOWEVER, ON SHEET 7 OF 7 IT IS NOT
 IDENTIFIED IN THE LEGEND.
  
  
 16) SHEET 7 OF 7 A "T" INSIDE A SQUARE BOX IS
 INDICATED; HOWEVER, ON SHEET 7 OF 7 IT IS NOT
 IDENTIFIED IN THE LEGEND.
  
  
 18) SHEET 7 OF 7, THE ABOVE DEVICES, COUNTS AND
 VOLTAGES MAY NEED TO BE UPDATED IN EACH OF THE
 APPLICABLE CALCULATION TABLES.
  
  
 19) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE ON
 RESUBMITTAL.
  
  
 20) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-23 Cont ID  
Sent By pleduc Date 2016-11-23 Time   Rev Time 0.00
Received By pleduc Date 2016-11-21 Time 13:06 Sent To  
Notes
2016-11-22 13:06:26RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-25 Cont ID  
Sent By pleduc Date 2016-10-25 Time   Rev Time 0.00
Received By pleduc Date 2016-10-19 Time 13:33 Sent To  
Notes
2016-10-19 13:33:14ROUTED TO FIRE INBOX