Plan Review Details - Permit 16100392
Plan Review Stops For Permit 16100392
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-02-08 Cont ID  
Sent By cthroop Date 2017-02-08 Time 09:41 Rev Time 0.00
Received By cthroop Date 2017-02-08 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 14:53 Rev Time 0.00
Received By cthroop Date 2016-12-08 Time 14:03 Sent To  
Notes
2016-12-08 14:32:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
  
 1. PLANS APPROVED BY DESIGN PROFFESIONAL HAVE BEEN
 ALTERED.
 2. 2ND SET OF PLANS HAVE BEEN PHOTO COPIED.
 3. NO RECORD FOUND APPROVING THE INSTALLATION OF
 MECHANICAL DROPS IN GARAGE/ GAME ROOM.
 4. PROVIDE ENERGY SUBMITTAL.
 5. PROVIDE DETAIL FOR CEILING AND WALL INSULATION.
 6. INCREASE OF CONDITIONED SPACE. PALM BEACH COUNTY
 IMPACT FEES REQUIRED.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R402.1.1 INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By cthroop Date 2016-11-10 Time 10:50 Rev Time 0.00
Received By cthroop Date 2016-11-10 Time 09:47 Sent To  
Notes
2016-11-10 11:00:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE ENERGY SUBMITTAL.
 2. PROVIDE LANDINGS AT EXT. DOORS.
 3. PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED BY
 EOR.
 4. ALL SUBMITTAL DOCUMENTS SHALL BE SUBMITTED IN
 DUPLICATE.
 5. PROVIDE DESIGN WIND LOADS FOR EACH OPENING IN THE
 BUILDING ENVELOPE.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW AND DOOR SUBMITTALS.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS). WHERE LOADS FOR GARAGE DOORS ARE NOT
 OTHERWISE SPECIFIED, THE LOADS LISTED IN TABLE
 R301.2(4) ADJUSTED FOR HEIGHT AND EXPOSURE USING TABLE
 R301.2(3) SHALL BE USED TO DETERMINE DESIGN LOAD
 PERFORMANCE REQUIREMENTS. ASPHALT SHINGLES SHALL BE
 DESIGNED FOR WIND SPEEDS IN ACCORDANCE WITH SECTION
 R905.2.4. A CONTINUOUS LOAD PATH SHALL BE PROVIDED TO
 TRANSMIT THE APPLICABLE UPLIFT FORCES IN SECTION R802.2
 FROM THE ROOF ASSEMBLY TO THE FOUNDATION.
  
2016-11-10 08:44:191ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-02-13 Cont ID  
Sent By vperez Date 2017-02-13 Time 10:58 Rev Time 0.00
Received By vperez Date 2017-02-13 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By mvaldes Date 2016-12-08 Time 12:48 Rev Time 0.00
Received By mvaldes Date 2016-12-08 Time 11:11 Sent To B
Notes
2016-12-08 13:00:502ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PLANS CANNOT BE MODIFIED WITHOUT THE APPROVAL OF THE
 ENGINEER OF RECORD. 61G15-31.001

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-26 Cont ID  
Sent By mvaldes Date 2016-10-26 Time 09:16 Rev Time 0.00
Received By mvaldes Date 2016-10-26 Time 08:43 Sent To  
Notes
2016-10-26 09:12:191ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CLARIFY IF PROPOSED "NEW GAME ROOM" WILL BE A
 SLEEPING AREA. THEREFORE IF DEFINED AS A SLEEPING ROOM
 PROVISIONS FOR SMOKE ALARMS IN ACCORDANCE WITH FBC-R
 SECTIONS 314 & 315 WILL APPLY.
  
 2] ADD A GENERAL ELECTRICAL NOTES FOR TAMPER-RESISTANT
 AND AFCI PROTECTION PER FBC-R SECTIONS E4002.14 &
 E3902.13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-03 Cont ID  
Sent By hmoser Date 2017-03-03 Time 13:11 Rev Time 0.00
Received By hmoser Date 2017-02-03 Time 16:10 Sent To  
Notes
2017-02-03 16:10:10R06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-08 Cont ID  
Sent By skennedy Date 2016-12-08 Time 16:14 Rev Time 0.00
Received By skennedy Date 2016-11-18 Time 11:55 Sent To  
Notes
2016-11-21 11:55:52R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-10 Cont ID  
Sent By cthroop Date 2016-11-10 Time 09:47 Rev Time 0.00
Received By cthroop Date 2016-10-17 Time 10:58 Sent To  
Notes
2016-10-18 10:58:17R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-08 Cont ID  
Sent By cthroop Date 2017-02-08 Time 09:41 Rev Time 0.00
Received By cthroop Date 2017-02-08 Time 09:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By skennedy Date 2016-11-10 Time 08:43 Rev Time 0.00
Received By skennedy Date 2016-11-10 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-07 Cont ID  
Sent By hmoser Date 2017-03-07 Time 12:58 Rev Time 0.00
Received By hmoser Date 2017-03-07 Time 12:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-03 Cont ID  
Sent By hmoser Date 2017-03-03 Time 11:57 Rev Time 0.00
Received By hmoser Date 2017-03-03 Time 11:08 Sent To  
Notes
2017-03-03 12:01:06PLAN DENIED
 ONLY ONE PLAN WAS SUBMITTED
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By skennedy Date 2016-12-08 Time 16:14 Rev Time 0.00
Received By skennedy Date 2016-12-08 Time 16:14 Sent To  
Notes
2016-12-08 16:16:562ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLEASE SEE 1ST REVIEW COMMENTS BELOW WHICH ARE STILL
 APPLICABLE BASED ON THE RESUBMITTAL. NOTE THE
 RE-SUBMITTAL CONTAINS NOTES, MODIFICATIONS, AND
 DRAWINGS PLACED ON THE PLAN BY SOMEONE OTHER THAN THE
 RESPONSIBLE DESIGN PROFESSIONAL. THE PLAN CONTAINS
 MECHANICAL INDICATIONS THAT AN EXISTING GARAGE HAS AN
 EXISTING SYSTEM WHICH DOES NOT NEED TO BE MODIFIED.
 THEIS IS INCONSISTENT WITH THE PREVIOUS PLAN BY A
 DESIGNER AND CITY PERMIT RECORDS. AS ORIGINALLY
 INDICATED BELOW, AN ENERGY SUBMITTAL AND A MECHANICAL
 PLAN IS REQUIRED.
  
 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 A MECHANICAL DESIGN IS REQUIRED. THE PLAN NOTES
 INDICATE HVAC BY OTHERS. PLEASE COORDINATE THE DESIGN
 WITH THE RE-SUBMITTAL FOR THIS PROJECT. IT MUST INCLUDE
 AN ENERGY SUBMITTAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 ALTERNATIVELY
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-10 Cont ID  
Sent By skennedy Date 2016-11-10 Time 09:07 Rev Time 0.00
Received By skennedy Date 2016-11-10 Time 08:44 Sent To  
Notes
2016-11-10 09:14:451ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 A MECHANICAL DESIGN IS REQUIRED. THE PLAN NOTES
 INDICATE HVAC BY OTHERS. PLEASE COORDINATE THE DESIGN
 WITH THE RE-SUBMITTAL FOR THIS PROJECT. IT MUST INCLUDE
 AN ENERGY SUBMITTAL.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 ALTERNATIVELY
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-03-07 Cont ID  
Sent By gjohnson Date 2017-02-10 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2017-02-10 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-12-07 Cont ID  
Sent By gjohnson Date 2016-12-07 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2016-12-07 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-29 Cont ID  
Sent By gjohnson Date 2016-10-29 Time 13:51 Rev Time 0.00
Received By gjohnson Date 2016-10-29 Time 13:51 Sent To  
Notes
2016-10-29 13:57:211ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.3.5.3(11)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-02-23 Cont ID  
Sent By awooten Date 2017-02-23 Time 09:23 Rev Time 0.00
Received By awooten Date 2017-02-23 Time 09:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2016-12-01 Time   Rev Time 0.00
Received By awooten Date 2016-12-01 Time 10:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-24 Cont ID  
Sent By awooten Date 2016-10-24 Time 11:30 Rev Time 0.00
Received By awooten Date 2016-10-21 Time 14:33 Sent To  
Notes
2016-10-24 11:30:16*******ZONING FAILED******************
  
 PROVIDE A SURVEY OF PROPERTY SHOWING DRIVEWAY, REQUIRED
 PARKING, AND THE EXISTING HOME.
  
 PLEASE LET ME KNOW IF YOU HAVE ANY QUESTIONS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
 PLANNING DIVISION
 [email protected]
 561-822-1449