Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-10-18 Cont ID  
Sent By tklarge Date 2016-10-20 Time 09:34 Rev Time 0.00
Received By pleduc Date 2016-10-18 Time 15:01 Sent To M
Notes
2016-10-18 15:15:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DETAIL INDICATED TO DETERMINE
 COMPLIANCE WITH FIRE AND LIFE SAFETY STANDARDS.
  
  
 1) IS THE TANK UNDER OR ABOVE GROUND? THERE IS NO
 DETAIL INDICATING EITHER INCLUDING DEPTH OF COVER, SLAB
 SIZE, TIE DOWN TYPE, SPECS, DOUBLE WALLED, ETC.
  
  
  
 2) THERE IS NO INDICATION WHAT FIRE CODE IT IS
 COMPLIANCE WITH. THE INSTALLATION SHALL COMPLY WITH
 NFPA 58 AND/OR OTHER APPLICABLE CODES.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEGEMENT OF FIRE CODE
 COMPLIANCE.
  
  
  
 3) THERE IS NO ACTUAL INDICATION OF DISTANCE FROM ALL
 PROPERTY LINES AND BUILDINGS.
  
 PLEASE PROVIDE DIMENSIONS OF ALL APPLICABLE AREAS PER
 NFPA SEPARATION REQUIREMENTS.
  
  
  
  
 4) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By tklarge Date 2016-11-07 Time 13:15 Rev Time 0.00
Received By tklarge Date 2016-11-07 Time 06:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-10-20 Cont ID  
Sent By tklarge Date 2016-10-20 Time 09:34 Rev Time 0.00
Received By tklarge Date 2016-10-20 Time 08:38 Sent To  
Notes
2016-10-20 09:34:051) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 4)SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (REGULATOR / LP TANK) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL THE
 GAS APPLIANCES. WPB AMEND. TO FBC SEC. 107.2.1.
 7) THE PROPOSAL FROM APS REFERS TO THE INSTALLATION OF
 A COOKTOP/RANGE AND A TANKLESS WATER HEATER IN ADDITION
 TO THE GENERATOR AND THE BBQ. THIS INFO IS NOT ON THE
 APPLICATION AND THESE APPLIANCES ARE NOT SHOWN ON THE
 PLANS.
 8) SUBMIT A GAS RISER THAT SHOWS ALL OF THE GAS
 APPLIANCES/EQUIPMENT ON THE RISER. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9) SHOW THE DISTANCE OF THE LP TANK FROM THE PROPERTY
 LINE.
 10) SHOW THE SIZE AND TYPE OF PIPE/TUBING FROM THE LP
 TANK TO THE FIRST STAGE REGULATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-07 Cont ID  
Sent By tklarge Date 2016-11-07 Time 13:15 Rev Time 0.00
Received By tklarge Date 2016-10-31 Time 16:21 Sent To  
Notes
2016-10-31 16:21:37RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-20 Cont ID  
Sent By tklarge Date 2016-10-20 Time 09:34 Rev Time 0.00
Received By tklarge Date 2016-10-14 Time 15:46 Sent To FIRE
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved