Plan Review Details - Permit 16100277
Plan Review Stops For Permit 16100277
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-09 Cont ID  
Sent By shill Date 2016-11-09 Time 06:52 Rev Time 0.00
Received By shill Date 2016-11-09 Time 06:52 Sent To  
Notes
2016-11-09 07:30:22****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE SOUTH EXTERIOR ENTRY DOOR ON THE FLOOR PLAN (PERMIT
 16100277) AND THE NORTH INTERIOR SECURITY VESTIBULE
 DOORS SHOWN ON THE FLOOR PLAN AS "EXISTING" HAVE DOOR
 SWING CONFIGURATION WHICH ARE NOT CONSISTENT WITH THE
 PERMIT ISSUED FOR THIS SCOPE OF WORK, EXPIRED ENTRY
 SECURITY VESTIBULE PERMIT 14020726, NEW "FINAL
 INSPECTION ONLY" PERMIT 16110426.
  
 PRIOR TO FINAL INSPECTION, THE TWO PLANS SHOULD
 CORRELATE AND SHOULD MATCH THE EXISTING CONDITIONS. A
 REVISION IS REQUIRED.
  
 THIS PERMIT IS ISSUED AT CONTRACTOR'S RISK. THE NEW
 PROPOSED (NOT YET SUBMITTED FOR PLAN REVIEW)
 CONFIGURATION IS TO BE SUBMITTED AND APPROVED AS A
 REVISION (TO 16110426) PRIOR TO FINAL INSPECTION. OR,
 THE INSTALLATION CAN BE MODIFIED TO BE CONSISTENT WITH
 THE ISSUED PERMIT. IN THAT CASE, THE "FINAL INSPECTION
 ONLY" PERMIT 16110426 SHOULD BE MODIFIED TO A "REISSUE"
 PERMIT AND THE FLOOR PLAN FOR RENOVATION PERMIT
 16100277 REVISED TO BE CONSISTENT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-03 Cont ID  
Sent By shill Date 2016-11-03 Time 16:37 Rev Time 0.00
Received By shill Date 2016-11-03 Time 14:55 Sent To  
Notes
2016-11-03 16:37:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. THE SECURITY VESTIBULE PERMIT IS EXPIRED. THE PLAN
 SHOWS THIS AS EXISTING, BUT IT IS EXISTING (FOR
 BUILDING CODE PURPOSES) ONLY IF IT WAS LEGALLY
 PERMITTED, CONSTRUCTED AS PERMITTED, AND FINALED. THE
 PLAN SHOWS THAT THE CONSTRUCTION IS NOT CONSISTENT WITH
 THE ISSUED PERMIT, DOES NOT APPEAR TO COMPLY WITH
 ACCESSIBILITY MANEUVERING CLEARANCE REQUIREMENT ON THE
 PULL SIDE, AND NO BUILDING INSPECTIONS WERE SCHEDULED
 (ONLY FIRE INSPECTIONS).
  
 EITHER APPLY FOR A SEPARATE PERMIT FOR THE VESTIBULE
 WORK, OR INCORPORATE THAT WORK INTO THIS PERMIT. SEE
 EXPIRED PERMIT 14020726. YOU MAY OBTAIN A COPY OF THE
 PLAN FOR THAT PERMIT BY SUBMITTING A REQUEST TO
 [email protected].
  
 2ND REVIEW, THE EXPIRED PERMIT HAS NOT BEEN ADDRESSED.
 THE WORK INSTALLED IS NOT CONSISTENT WITH THE ISSUED
 PERMIT. C M FREEMAN IS TO SUBMIT APPLICATION FOR A
 PERMIT FOR THAT WORK. PLEASE ADVISE WHEN THIS HAS BEEN
 DONE AND THE BUILDING REVIEW WILL BE PASSED (PENDING
 ITEM 3).
  
 2. OK
  
 3. SHEET A4.1 REFERS TO FBC 2007 IN MORE THAN ONE
 LOCATION, REVISE.
  
 THIS HAS BEEN REVISED TO FBC 2012, ALSO REFERS TO FBC
 ADA 2012, THE CODE IN EFFECT IS FBC 5TH EDITION OR FBC
 2014.
  
 THIS MAY BE A PROVISO ITEM UPON REQUEST.
  
 4, 5, 6. OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By shill Date 2016-10-21 Time 12:05 Rev Time 0.00
Received By shill Date 2016-10-21 Time 12:05 Sent To  
Notes
2016-10-21 12:26:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SECURITY VESTIBULE PERMIT IS EXPIRED. THE PLAN
 SHOWS THIS AS EXISTING, BUT IT IS EXISTING (FOR
 BUILDING CODE PURPOSES) ONLY IF IT WAS LEGALLY
 PERMITTED, CONSTRUCTED AS PERMITTED, AND FINALED. THE
 PLAN SHOWS THAT THE CONSTRUCTION IS NOT CONSISTENT WITH
 THE ISSUED PERMIT, DOES NOT APPEAR TO COMPLY WITH
 ACCESSIBILITY MANEUVERING CLEARANCE REQUIREMENT ON THE
 PULL SIDE, AND NO BUILDING INSPECTIONS WERE SCHEDULED
 (ONLY FIRE INSPECTIONS).
  
 EITHER APPLY FOR A SEPARATE PERMIT FOR THE VESTIBULE
 WORK, OR INCORPORATE THAT WORK INTO THIS PERMIT. SEE
 EXPIRED PERMIT 14020726. YOU MAY OBTAIN A COPY OF THE
 PLAN FOR THAT PERMIT BY SUBMITTING A REQUEST TO
 [email protected].
  
 2. UNNUMBERED DOOR WHICH SERVES THE BACK AREA, SHOW THE
 18IN PULL SIDE MANEUVERING CLEARANCE FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.1.
  
 3. SHEET A4.1 REFERS TO FBC 2007 IN MORE THAN ONE
 LOCATION, REVISE.
  
 4. PROVIDE THE PRODUCT APPROVAL FOR THE NEW DRIVE UP
 ATM. PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC 107.
  
 5. PLAN LACKS WIND DESIGN CRITERIA, FBC 1603.4.1., ADD
 TO PLAN.
  
 6. SEE PLUMBING COMMENTS AND REVISE PLAN ACCORDINGLY.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By vperez Date 2016-11-07 Time 14:10 Rev Time 0.00
Received By vperez Date 2016-11-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-19 Cont ID  
Sent By vperez Date 2016-10-19 Time 09:51 Rev Time 0.00
Received By vperez Date 2016-10-19 Time 09:51 Sent To  
Notes
2016-10-19 09:51:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS,ETC. A NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; SEE VERBIAGE IN CODE.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16- ARC FLASH WARNING; SEE VERBIAGE IN
 CODE.
 4. PERE NEC 110.15- PROVIDE NOTE FOR HIGH LEG MARKINGS
 REQUIREMENTS AT THE SERVICE AND PANELBOARDS. SEE NEC
 408.2F1
 5. PER FBC-EC 405.7- A MINIMUM OF 50% OF ALL
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED FOR
 OFFICE AREAS. SHOW COMPLIANCE
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-03 Cont ID  
Sent By pleduc Date 2016-11-03 Time   Rev Time 0.00
Received By pleduc Date 2016-11-03 Time 12:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-10-18 Cont ID  
Sent By pleduc Date 2016-10-18 Time   Rev Time 0.00
Received By pleduc Date 2016-10-18 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-12-01 Time 11:27 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 14:43 Sent To  
Notes
2016-11-21 14:43:38RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-07 Cont ID  
Sent By vperez Date 2016-11-07 Time 14:10 Rev Time 0.00
Received By vperez Date 2016-11-07 Time 14:10 Sent To  
Notes
2016-11-01 08:54:40C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-21 Cont ID  
Sent By shill Date 2016-10-21 Time 12:35 Rev Time 0.00
Received By shill Date 2016-10-13 Time 15:35 Sent To  
Notes
2016-10-13 15:34:51C12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-01 Cont ID  
Sent By ccole Date 2016-11-28 Time 15:52 Rev Time 0.00
Received By ccole Date 2016-11-28 Time 15:52 Sent To  
Notes
2016-11-28 15:54:40 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By ccole Date 2016-11-04 Time 10:12 Rev Time 0.00
Received By ccole Date 2016-11-04 Time 10:12 Sent To  
Notes
2016-11-04 10:32:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100277
 11/4/16
  
 1) SUBMIT AHRI CERTIFICATES FOR THE AC SYSTEMS TO
 VERIFY THAT THE REPLACED AIR HANDLERS MATCH THE
 EXISTING CONDENSERS
  
 2) THE 18X10 AND 12" TRANSFER DUCTS AT THE BREAKROOM
 AND BOLD SPACE ARE UNDERSIZED PER SECTION 601.5
 EXCEPTION 1. PLEASE PROVIDE THE TRANSFER AND RETURN
 GRILL SIZES ON THE PLANS.
  
 3) INDICATE THE TYPE OF LOUVERED DOORS THAT ARE
 ENCLOSING THE MECHANICAL CLOSET AND CONVEYING RETURN
 AIR. PLEASE NOTE THAT THE DOORS MUST BE NON-COMBUSTIBLE
 PER SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-10-19 Cont ID  
Sent By ccole Date 2016-10-19 Time 15:26 Rev Time 0.00
Received By ccole Date 2016-10-19 Time 15:26 Sent To  
Notes
2016-10-19 15:52:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100277
 10/19/16
  
 1) CLARIFY HOW THE O/A MOTORIZED DAMPER FOR AHU-1 &
 AHU-2 WILL FUNCTION INDIVDUALLY FOR EACH SYSTEM.
  
 2) LEVEL-2 ALTERATIONS SHALL BE IN COMPLIANCE WITH THE
 CURRENT CODES IN EFFECT- SEE SECTION 801.3 FBC-14
 EXISTING BUILDING CODE. PROVIDE DUCT SMOKE DETECTORS IN
 THE RETURN AIR SYSTEMS OF THE REPLACED AIR HANDLERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-07 Cont ID  
Sent By gjohnson Date 2016-11-07 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2016-11-07 Time 13:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-21 Cont ID  
Sent By gjohnson Date 2016-10-21 Time 10:12 Rev Time 0.00
Received By gjohnson Date 2016-10-21 Time 10:12 Sent To  
Notes
2016-10-21 10:28:351ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE GRAB BARS SHALL BE MEASURED FROM THE TOP OF THE
 GRIPPING SURFACE TO FINISH FLOOR AND BE MIN 33" MAX
 36". PER FBC ACC 609.4
  
 2. TH TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 3. LAVATORY'S SHALL BE SUPPLIED WITH TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. SHT. P-1.1 THE FLOOR PLAN DID NOT COPY WELL IT IS
 VERY LIGHT AND SOME OF THE WALLS AND FIXTURES CAN NOT
 BE SEEN PLEASE PROVIDE A DARKER COPY. PER WPB AMEND TO
 FBC 107.2.1.4
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1


Account Summary | Usage Policy | Privacy Policy