| Plan Review Stops For Permit 16100209 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
N |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2017-05-24 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2017-05-24 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2017-05-24 12:36:38 | INCIDENTAL TO ELECTRICAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2016-10-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-10-20 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-10-20 |
Time |
08:56 |
Sent To |
G |
|
| Notes |
| 2016-10-20 09:18:53 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | 1. PROVIDE SITE PLAN/SURVEY TO DEMONSTRATE REQUIRED | | | SETBACKS. | | | 2. PROVIDE FOUNDATION PLAN FOR SLAB. | | | 3. DESIGNER OF RECORD TO SIGN AND SEAL PLANS. | | | 4. WORK DESCRIPTION ON APPLICATION STATES "INSTALL | | | 1-80KW DIESEL GENERATOR AND SWITCH W/CONCRETE SLAB". | | | DESCRIPTION OF WORK ON PLAN PAGE A1 STATES "LANDSCAPE | | | SCREEN FOR EXISTING GENERATOR". PLEASE CLARIFY SCOPE OF | | | WORK. | | | | | | DESIGN PROFESSIONAL ? REQUIRED | | | PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS | | | DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE | | | PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481. | | | SEE BELOW: | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-05 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-06-05 |
Time |
10:36 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-05-24 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-24 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2017-05-24 18:16:02 | 5/24/17 | | | | | | EMAILED CONTRACTOR TOLD HIM OF THE NEED FOR ONE MORE | | | SET TO REVIEW. | | | | | | NEED AN ADDITIONAL SET TO REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-10-19 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-10-19 |
Time |
18:54 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-10-19 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
| 2016-10-19 18:53:46 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE ACTUAL ONE-LINE RISER DIAGRAM OF THE | | | EXISTING ELECTRICAL SYSTEM, SHOW CONDUIT & WIRE SIZES, | | | PANEL SCHEDULE, GROUNDING DETAIL, AND LOAD | | | CALCULATIONS. FBC-107.3.5.3 | | | | | | 2] CLARIFY IF TRANSFER SWITCH IS SERVICE RATED AND THE | | | ELECTRICAL VOLTAGE OF EQUIPMENT IS IT SINGLE PHASE OR | | | THREE PHASE ? NEC 230.66 | | | | | | 3] NEW COMMENTS MAY BE NOTED UPON RE-REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-06 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2017-06-05 |
Time |
15:16 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2016-11-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-11-16 |
Time |
16:17 |
Sent To |
PC |
|
| Notes |
| 2016-11-16 16:54:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLAN INDICATES EXISTING GENERATOR AND | | | DESCRIPTION OF WORK INDICATES LANDSCAPE SCREEN FOR | | | EXISTING GENERATOR. | | | | | | PLEASE CLARIFY THE SCOPE OF WORK, WHAT IS EXISTING, | | | NEW, REPLACED, OR PROPOSED, ETC. | | | | | | | | | 2) WHAT WILL THE GNERATOR SUPPLY POWER FOR, I.E. WILL | | | SUPPLY POWER FOR THE LIFE SAFETY SYSTEMS. | | | | | | PLEASE PROVIDE DETAILED SCOPE OF WORK WHICH MAY INCLUDE | | | COMPLIANCE WITH NFPA 110 EMERGENCY AND STANDBY POWER | | | SYSTEMS. | | | | | | | | | 3) PROVIDE DETAIL AND DIMENSIONS TO THE FIRE HYDRANT | | | AND NEAREST BUILDINGS. WHICH SIDE OF THE GENERATOR IS | | | THE EXHAUST LOCATED? | | | | | | | | | | | | 4) THE GENERATOR SHALL BE PROTECTED FROM VEHICULAR | | | TRAFFIC IMPACT, ARE POLLARDS BEING PROVIDED | | | | | | PLEASE CLARIFY. | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2017-05-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2017-05-24 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2017-05-24 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2017-05-24 12:28:23 | FUEL IS DIESEL SELF CONTAINED |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-28 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-26 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2016-10-28 13:23:08 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE SITE PLAN THAT SHOWS THE NEW GENERATOR AND | | | FUEL STORAGE TANK. TO INCLUDE DISTANCES FROM | | | SURROUNDING STRUCTURES AND TRAFFIC BARRIERS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. PROVIDE COMPLETE RISER DIAGRAM FOR FUEL PIPING PER | | | WPB AMEND TO FBC 107.3.5.1.5(1)(9) | | | | | | 3. MANUFACTURE SPECIFICATION FOR STORAGE TANK. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. STRAPPING AND TIE DOWN DETAILS. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 4. MSDS SHEETS FO R DIESEL FUEL. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2017-06-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2017-06-06 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2017-05-30 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2017-05-31 10:35:08 | RESUB ROUTED TO NJWIRA VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2017-05-31 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2017-05-31 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2017-05-18 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2017-05-19 12:54:34 | RESUB ROUTED TO NJWIRA VIA ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-10-28 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-10-12 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2016-10-13 11:31:54 | ROUTED TO ZONING |
|
|
| Review Stop |
X |
PERMIT EXTENSION |
| Rev No |
1 |
Status |
N |
Date |
2017-05-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2017-05-18 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2017-05-18 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2017-05-18 11:11:01 | RECEIVED LETTER FROM CONTRACTOR REQUESTING EXTENSION OF | | | PERMIT APPLICATION. PERMIT APPLICATION EXTENDED TO | | | 8/16/17. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2017-06-01 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-06-01 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-05-31 |
Time |
16:34 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2017-05-22 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2017-05-22 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2017-05-19 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2016-10-14 |
|
|
Cont ID |
|
| Sent By |
njwira |
Date |
2016-10-14 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-10-13 |
Time |
14:48 |
Sent To |
E |
|
| Notes |
| 2016-10-14 16:14:12 | 10/14/16- FAILED | | | | | | DID NOT PROVIDE A SURVEY SHOWING WHERE THIS GENERATOR | | | WILL BE IN RELATION TO REQUIRED SETBACKS. | | | | | | PLEASE CONTACT | | | NATHAN WIRA | | | [email protected] | | | (561)822-1442 | | | |
|
|