Plan Review Details - Permit 16100209
Plan Review Stops For Permit 16100209
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2017-05-24 Cont ID  
Sent By skennedy Date 2017-05-24 Time 12:36 Rev Time 0.00
Received By skennedy Date 2017-05-24 Time 12:36 Sent To  
Notes
2017-05-24 12:36:38INCIDENTAL TO ELECTRICAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-10-20 Cont ID  
Sent By cthroop Date 2016-10-20 Time 08:59 Rev Time 0.00
Received By cthroop Date 2016-10-20 Time 08:56 Sent To G
Notes
2016-10-20 09:18:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PROVIDE SITE PLAN/SURVEY TO DEMONSTRATE REQUIRED
 SETBACKS.
 2. PROVIDE FOUNDATION PLAN FOR SLAB.
 3. DESIGNER OF RECORD TO SIGN AND SEAL PLANS.
 4. WORK DESCRIPTION ON APPLICATION STATES "INSTALL
 1-80KW DIESEL GENERATOR AND SWITCH W/CONCRETE SLAB".
 DESCRIPTION OF WORK ON PLAN PAGE A1 STATES "LANDSCAPE
 SCREEN FOR EXISTING GENERATOR". PLEASE CLARIFY SCOPE OF
 WORK.
  
 DESIGN PROFESSIONAL ? REQUIRED
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE
 PREPARED BY A LICENSED PROFESSIONAL PURSUANT TO FS 481.
 SEE BELOW:
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-05 Time 11:46 Rev Time 0.00
Received By jleahy Date 2017-06-05 Time 10:36 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 18:15 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 18:15 Sent To  
Notes
2017-05-24 18:16:025/24/17
  
 EMAILED CONTRACTOR TOLD HIM OF THE NEED FOR ONE MORE
 SET TO REVIEW.
  
 NEED AN ADDITIONAL SET TO REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 18:54 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 16:38 Sent To B
Notes
2016-10-19 18:53:46REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE ACTUAL ONE-LINE RISER DIAGRAM OF THE
 EXISTING ELECTRICAL SYSTEM, SHOW CONDUIT & WIRE SIZES,
 PANEL SCHEDULE, GROUNDING DETAIL, AND LOAD
 CALCULATIONS. FBC-107.3.5.3
  
 2] CLARIFY IF TRANSFER SWITCH IS SERVICE RATED AND THE
 ELECTRICAL VOLTAGE OF EQUIPMENT IS IT SINGLE PHASE OR
 THREE PHASE ? NEC 230.66
  
 3] NEW COMMENTS MAY BE NOTED UPON RE-REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-06-05 Cont ID  
Sent By jleahy Date 2017-06-06 Time 07:33 Rev Time 0.00
Received By pleduc Date 2017-06-05 Time 15:16 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-11-16 Cont ID  
Sent By pleduc Date 2016-11-16 Time   Rev Time 0.00
Received By pleduc Date 2016-11-16 Time 16:17 Sent To PC
Notes
2016-11-16 16:54:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN INDICATES EXISTING GENERATOR AND
 DESCRIPTION OF WORK INDICATES LANDSCAPE SCREEN FOR
 EXISTING GENERATOR.
  
 PLEASE CLARIFY THE SCOPE OF WORK, WHAT IS EXISTING,
 NEW, REPLACED, OR PROPOSED, ETC.
  
  
 2) WHAT WILL THE GNERATOR SUPPLY POWER FOR, I.E. WILL
 SUPPLY POWER FOR THE LIFE SAFETY SYSTEMS.
  
 PLEASE PROVIDE DETAILED SCOPE OF WORK WHICH MAY INCLUDE
 COMPLIANCE WITH NFPA 110 EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
  
 3) PROVIDE DETAIL AND DIMENSIONS TO THE FIRE HYDRANT
 AND NEAREST BUILDINGS. WHICH SIDE OF THE GENERATOR IS
 THE EXHAUST LOCATED?
  
  
  
 4) THE GENERATOR SHALL BE PROTECTED FROM VEHICULAR
 TRAFFIC IMPACT, ARE POLLARDS BEING PROVIDED
  
 PLEASE CLARIFY.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2017-05-24 Cont ID  
Sent By skennedy Date 2017-05-24 Time 12:11 Rev Time 0.00
Received By skennedy Date 2017-05-24 Time 12:11 Sent To  
Notes
2017-05-24 12:28:23FUEL IS DIESEL SELF CONTAINED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-10-28 Cont ID  
Sent By gjohnson Date 2016-10-28 Time 13:14 Rev Time 0.00
Received By gjohnson Date 2016-10-26 Time 10:57 Sent To  
Notes
2016-10-28 13:23:081ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SITE PLAN THAT SHOWS THE NEW GENERATOR AND
 FUEL STORAGE TANK. TO INCLUDE DISTANCES FROM
 SURROUNDING STRUCTURES AND TRAFFIC BARRIERS. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PROVIDE COMPLETE RISER DIAGRAM FOR FUEL PIPING PER
 WPB AMEND TO FBC 107.3.5.1.5(1)(9)
  
 3. MANUFACTURE SPECIFICATION FOR STORAGE TANK. PER WPB
 AMEND TO FBC 107.2.1
  
 4. STRAPPING AND TIE DOWN DETAILS. PER WPB AMEND TO FBC
 107.2.1
  
 4. MSDS SHEETS FO R DIESEL FUEL. PER WPB AMEND TO FBC
 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-06 Cont ID  
Sent By jleahy Date 2017-06-06 Time 07:40 Rev Time 0.00
Received By jleahy Date 2017-05-30 Time 10:34 Sent To  
Notes
2017-05-31 10:35:08RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-31 Cont ID  
Sent By lmarchan Date 2017-05-31 Time 10:07 Rev Time 0.00
Received By lmarchan Date 2017-05-18 Time 12:54 Sent To  
Notes
2017-05-19 12:54:34RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-28 Cont ID  
Sent By gjohnson Date 2016-10-28 Time 13:23 Rev Time 0.00
Received By gjohnson Date 2016-10-12 Time 11:31 Sent To  
Notes
2016-10-13 11:31:54ROUTED TO ZONING

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2017-05-18 Cont ID  
Sent By rbrown Date 2017-05-18 Time 11:08 Rev Time 0.00
Received By rbrown Date 2017-05-18 Time 11:08 Sent To  
Notes
2017-05-18 11:11:01RECEIVED LETTER FROM CONTRACTOR REQUESTING EXTENSION OF
 PERMIT APPLICATION. PERMIT APPLICATION EXTENDED TO
 8/16/17.

Review Stop Z ZONING
Rev No 3 Status P Date 2017-06-01 Cont ID  
Sent By njwira Date 2017-06-01 Time 15:32 Rev Time 0.00
Received By njwira Date 2017-05-31 Time 16:34 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-22 Cont ID  
Sent By njwira Date 2017-05-22 Time 17:15 Rev Time 0.00
Received By njwira Date 2017-05-19 Time 15:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-10-14 Cont ID  
Sent By njwira Date 2016-10-14 Time 16:13 Rev Time 0.00
Received By njwira Date 2016-10-13 Time 14:48 Sent To E
Notes
2016-10-14 16:14:1210/14/16- FAILED
  
 DID NOT PROVIDE A SURVEY SHOWING WHERE THIS GENERATOR
 WILL BE IN RELATION TO REQUIRED SETBACKS.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  