Plan Review Details - Permit 16100185
Plan Review Stops For Permit 16100185
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-12-14 Cont ID  
Sent By rmcdouga Date 2016-12-14 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2016-12-14 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2016-12-13 Time 06:52 Sent To  
Notes
2016-12-13 09:00:37PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLAN SHEETS 1, 3 AND 4 DO NOT HAVE THE PROFESSIONAL
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE OR SEAL AS
 REQUIRED BY FAC 61G15-23.002.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 ASPHALT ROOF SHINGLES (NOA NO. 03-0219.04) EXPIRED IN
 2008. SUBMIT TWO SETS OF CURRENT PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107.3.4
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 WINDOWS AND DOORS WERE NOT REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-22 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2016-11-22 Time 07:09 Sent To  
Notes
2016-11-22 16:24:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ROOFING MATERIALS, WINDOW/GLASS TYPES AND EXTERIOR
 DOOR TYPES. ONLY ONE PRODUCT APPROVAL WAS SUBMITTED FOR
 THE SINGLE HUNG WINDOWS AND NONE WERE SUBMITTED FOR THE
 DOORS OR ROOFING MATERIAL.
  
 2) THE WALL SECTION AT THE MASTER BATHROOM SPECIFIES
 ONLY THE ONE LAYER OF FELT ON THE PAPER BACK LATH,
 WHICH DOES NOT COMPLY WITH R703.6.3 WATER-RESISTIVE
 BARRIERS. WATER-RESISTIVE BARRIERS SHALL BE INSTALLED
 AS REQUIRED IN SECTION R703.2 AND, WHERE APPLIED OVER
 WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-12 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 13:50 Rev Time 0.00
Received By mvaldes Date 2016-12-12 Time 15:58 Sent To B
Notes
2016-12-12 16:49:232ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 1] A SWITCHED LIGHTING OUTLET REQUIRED BY MECHANICAL
 UNIT IN THE ATTIC. NEC 210.70(A)(3)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-19 Cont ID  
Sent By mvaldes Date 2016-10-19 Time 11:22 Rev Time 0.00
Received By mvaldes Date 2016-10-19 Time 10:27 Sent To  
Notes
2016-10-19 11:23:16JOB PERMIT NUMBER: 16100185
 JOB ADDRESS: 816 41 STREET
 WEST PALM BEACH FLORIDA
 DATE: OCTOBER 19, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. BELOW IS A LIST OF ITEMS NOTED.
  
 1] IF THE SERVICE IS OVERHEAD PLEASE REMOVE THE LATERAL
 UNDERGROUND CONDUIT SHOWN AT THE METER IN THE RISER
 DIAGRAM. FBC-107
  
 2] ADD AN INTERSYSTEM BONDING TERMINAL TO THE GROUNDING
 DETAIL IN THE RISER DIAGRAM. FBC-R SEC E3609.3
  
 3] PROVIDE THE 200 AMP PANEL LOCATION ON THE FLOOR PLAN
 TO VERIFY WORK CLEARANCE, SHOW COMPLIANCE. FBC-R SEC
 E3405
  
 4] ADD A SMOKE ALARM OUTSIDE OF THE MASTER BED IN THE
 IMMEDIATE VICINITY OF THE SLEEPING AREA. FBC-R SEC
 314.3
  
 5] ADD A WALL SWITCHED CONTROLLED LIGHTING OUTLET TO
 PROVIDE OUTDOOR ILLUMINATION FOR THE EXTERIOR DINING
 ROOM DOOR. FBC-R SEC E3903.3
  
 6] PROVIDE A GFCI SERVICE RECEPTACLE OUTLET WITHIN 25'
 OF THE OUTSIDE CONDENSER UNIT. FBC-R SEC E3901.11
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-14 Cont ID  
Sent By rmcdouga Date 2016-12-14 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2016-12-14 Time 11:25 Sent To  
Notes
2016-12-14 11:26:08RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-13 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2016-12-05 Time 13:05 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-22 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2016-10-12 Time 14:02 Sent To  
Notes
2016-10-13 14:02:13R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2016-12-14 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2016-11-22 Time 11:01 Sent To  
Notes
2016-11-22 11:17:50IMPACT FEES WERE PAID UNDER PREVIOUS PERMIT #07040598.
 PR #08-2831

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-12-14 Cont ID  
Sent By rmcdouga Date 2016-12-14 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2016-12-14 Time 11:27 Sent To  
Notes
2016-12-14 11:27:41MECHANICAL PROVISO
  
 M1305.1.3 APPLIANCES IN ATTICS. ATTICS CONTAINING
 APPLIANCES SHALL BE PROVIDED WITH AN OPENING AND A
 CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE, BUT NOT LESS THAN 30
 INCHES (762 MM) HIGH AND 22 INCHES (559 MM) WIDE AND
 NOT MORE THAN 20 FEET (6096 MM) LONG MEASURED ALONG THE
 CENTERLINE OF THE PASSAGEWAY FROM THE OPENING TO THE
 APPLIANCE. THE PASSAGEWAY SHALL HAVE CONTINUOUS SOLID
 FLOORING IN ACCORDANCE WITH CHAPTER 5 NOT LESS THAN 24
 INCHES (610 MM) WIDE. A LEVEL SERVICE SPACE AT LEAST 30
 INCHES (762 MM) DEEP AND 30 INCHES (762 MM) WIDE SHALL
 BE PRESENT ALONG ALL SIDES OF THE APPLIANCE WHERE
 ACCESS IS REQUIRED. THE CLEAR ACCESS OPENING DIMENSIONS
 SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES (508 MM BY
 762 MM), AND LARGE ENOUGH TO ALLOW REMOVAL OF THE
 LARGEST APPLIANCE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-13 Cont ID  
Sent By rmcdouga Date 2016-12-13 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2016-12-13 Time 06:52 Sent To  
Notes
2016-12-13 13:50:04PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ANCHORING DETAIL ON SHEET M-1 SPECIFIES A 2 INCH
 CONCRETE PAD. M1305.1.4.1 GROUND CLEARANCE. EQUIPMENT
 AND APPLIANCES SUPPORTED FROM THE GROUND SHALL BE LEVEL
 AND FIRMLY SUPPORTED ON A CONCRETE SLAB OR OTHER
 APPROVED MATERIAL EXTENDING NOT LESS THAN 3 INCHES (76
 MM) ABOVE THE ADJOINING GROUND. SUCH SUPPORT SHALL BE
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. APPLIANCES SUSPENDED FROM THE FLOOR SHALL
 HAVE A CLEARANCE OF NOT LESS THAN 6 INCHES (152 MM)
 FROM THE GROUND.
  
 2) THE PLANS SHOW THE AIR HANDLER IN THE ATTIC AND IT
 APPEARS THAT THE DUCTWORK BLOCKS ACCESS FROM THE ACCESS
 OPENING TO THE APPLIANCE. M1305.1.3 APPLIANCES IN
 ATTICS. ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED
 WITH AN OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY
 LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE,
 BUT NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 20 FEET (6096 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 3) ONLY ONE OF THE ENERGY FORMS WAS SIGNED AND DATED BY
 THE OWNER. PLEASE HAVE THE OWNER SIGN AND DATE THE
 OTHER SET. FBC ENERGY R405-2014
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-22 Cont ID  
Sent By rmcdouga Date 2016-11-22 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2016-11-22 Time 15:28 Sent To  
Notes
2016-11-22 14:45:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WALLS OF THE STRUCTURE ARE NOT CLEARLY VISIBLE
 ON THE HVAC PLAN. FBC 107.2.1
  
 2) THE EQUIPMENT SCHEDULE ON SHEET M-1 DOES NOT MATCH
 THE ENERGY FORM OR LOAD CALCULATIONS. THE EER AND SEER
 ARE DIFFERENT AND THE MODEL NUMBER FOR THE AHU IS
 DIFFERENT.
  
 3) ONLY ONE COPY OF THE ENERGY AND LOAD CALCULATIONS
 WERE SUBMITTED. TWO SETS ARE REQUIRED. FBC 107.1
  
 4) THE OWNER / AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM R405-2014.
  
 5) PROVIDE AN EQUIPMENT ANCHORING DETAIL FOR THE
 MECHANICAL EQUIPMENT THAT IS LOCATED ON THE EXTERIOR OF
 THE STRUCTURE.FBC- M301.15
  
 5) THE AC EQUIPMENT SCHEDULE SPECIFIES THAT THE AIR
 HANDLER IS LOCATED IN A UTILITY CLOSET AND THE HVAC
 PLAN SHOWS IT MOUNTED HORIZONTALLY IN THE ATTIC. REVISE
 AS NECESSARY AND SHOW THE LOCATION OF THE A/H ON THE
 ARCHITECTURAL PLANS, AS WELL AS, THE HVAC PLANS. FBC
 107.2.1
  
 6) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE MECHANICAL PLANS SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-11-04 Cont ID  
Sent By gjohnson Date 2016-11-04 Time 08:26 Rev Time 0.00
Received By gjohnson Date 2016-11-03 Time 15:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2016-10-24 Cont ID  
Sent By awooten Date 2016-10-24 Time 14:32 Rev Time 0.00
Received By awooten Date 2016-10-21 Time 14:32 Sent To  
Notes
***NONE***