Plan Review Details - Permit 16100180
Plan Review Stops For Permit 16100180
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-20 Cont ID  
Sent By rmcdouga Date 2016-12-20 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2016-12-20 Time 07:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-11-15 Cont ID  
Sent By rmcdouga Date 2016-11-15 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2016-11-14 Time 18:44 Sent To  
Notes
2016-11-15 09:05:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE
 AREA OF THE STRUCTURE. THEREFORE, THIS PROJECT IS A
 LEVEL 3 ALTERATION PER FBC EXISTING BUILDING SECTION
 505.1.
  
 2) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. SPECIFY THE TYPE AND THE SIZE OF THE
 WINDOWS IN BEDROOM NUMBER 3 TO SHOW THAT THEY MEET THE
 REQUIREMENTS OF FBC-R310.1, R301.1.1, R301.1.2 &
 R301.1.3.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. THE
 PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE CGI
 MULLIONS WITH NOA NO. 15-0420.07 IS NOT LISTED IN THE
 PRODUCT APPROVAL SCHEDULE ON SHEET 2 AND DOES NOT HAVE
 A SHOP REVIEW STAMP FROM THE DESIGNER OF RECORD.
  
 4) THE PLANS ARE LABELED PHASE 1 AND PHASE 2. SINCE
 THEY WERE BOTH SUBMITTED UNDER THE SAME PERMIT NUMBER
 ALL OF THE WORK SHOWN FOR BOTH PHASES WILL NEED TO BE
 COMPLETED BEFORE A FINAL INSPECTION CAN BE APPROVED AND
 A CERTIFICATE OF COMPLETION ISSUED. FBC 111.4
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-06 Cont ID  
Sent By rlecky Date 2016-12-06 Time 14:41 Rev Time 0.00
Received By rlecky Date 2016-12-06 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-10-13 Cont ID  
Sent By albarran Date 2016-10-13 Time 18:28 Rev Time 0.00
Received By albarran Date 2016-10-13 Time 17:25 Sent To  
Notes
2016-10-13 18:30:09ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
  
 JOB ADDRESS: 7549 IRONHORSE BLVD.
 DESCRIPTION: RESIDENTIAL REMODEL
 MASTER PERMIT: 16100180 (PHASES 1 & 2)
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS. ITEMS 1 - 4 BELOW CAN BE
 ADDRESSED WITH A BLOCK NOTE ADDED TO THE PLANS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE. CORRECT NOTE 1 TO
 READ THE 2011 EDITION OF THE NEC.
 2. FBC-R4002.9/NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?.
 3. FBC-ER404.1: A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
 4. FBC-RE3905.6.2 NEC 314.27(A) LUMINAIRE OUTLETS.
 BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB.
 5. MARK ON THE PLANS THE LOCATION OF ALL HVAC EQUIPMENT
 IF WITHIN THE AREA OF WORK.
 6. PER FBC MECHANICAL VENTILATION IS REQUIRED IN THE
 TOILET ROOMS WHENEVER THE ROOM IS OCCUPIED. THEREFORE
 THE EXHAUST FANS SHALL BE CONTROLLED WITH THE LIGHT
 SWITCH.
 7. FBC-RE3901.2.1/NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL.
 THEREFORE, YOU SHALL ADD OR RELOCATE THE EXISTING
 OUTLETS IN THE MASTER BEDROOM TO COMPLY.
 8. FBC-RE3903.4 NEC 210.70(A)(3) STORAGE OR EQUIPMENT
 SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING
 OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT
 REQUIRING SERVICING. IF THERE IS EQUIPMENT INSIDE THE
 ATTIC A SERVICE GFI OUTLET IS ALSO REQUIRED.
 9. CORRECT NOTE 12 FROM ?SHEET CABLE? TO READ ?SHEATHED
 CABLE? NEC 334.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-01 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2017-01-19 Time 13:57 Sent To  
Notes
2017-01-20 13:58:11RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-20 Cont ID  
Sent By rmcdouga Date 2016-12-20 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2016-11-22 Time 07:45 Sent To  
Notes
2016-11-23 07:45:52R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-11-15 Cont ID  
Sent By rmcdouga Date 2016-11-15 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2016-10-11 Time 13:07 Sent To  
Notes
2016-10-12 13:07:29R16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-12-20 Cont ID  
Sent By rmcdouga Date 2016-12-20 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2016-12-20 Time 11:18 Sent To  
Notes
2016-12-20 11:30:43NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. A
 SEPARATE PERMIT, APPLICATION AND PLANS ARE REQUIRED TO
 BE SUBMITTED FOR THE REQUIRED MECHANICAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-11-15 Cont ID  
Sent By rmcdouga Date 2016-11-15 Time 06:57 Rev Time 0.00
Received By rmcdouga Date 2016-11-15 Time 06:57 Sent To  
Notes
2016-11-15 07:19:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-02-01 Cont ID  
Sent By gjohnson Date 2017-02-01 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-14 Cont ID  
Sent By gjohnson Date 2016-12-14 Time 13:22 Rev Time 0.00
Received By gjohnson Date 2016-12-14 Time 13:11 Sent To  
Notes
2016-12-14 13:49:342ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. 3 PLUMBING RISER IS NOT CODE COMPLIANT WC NOT
 VENTED, SHOWER SHALL CONNECT OFF HORIZONTAL DRAIN,
 COMPLY WITH FBC PL 912.1
 2.CLEAN OUT TO BE SAME SIZE AS PIPE BEING SERVED, SHALL
 COMPLY WITH FBC PL 708.7
 3. SHOW RELOCATED KITCHEN AND WASHING MACHINE ON RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
 3. SHUT OFF VALVES FOR STACKABLE WASHING MACHINE SHALL
 BE ACCESSIBLE WITHOUT MOVING MACHINE. FBC PL 606.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-10-27 Cont ID  
Sent By gjohnson Date 2016-10-27 Time 09:09 Rev Time 0.00
Received By gjohnson Date 2016-10-26 Time 16:08 Sent To  
Notes
2016-10-27 09:11:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING RISER. PER WPB AMEND TO FBC
 107.3.5.3(11)